VII | FIRE PROTECTION | ORDINARY-HAZARD STORAGE |
A |
DETECTION ALARM AND COMMUNICATION SYSTEMS |
|
|
1 |
FIRE ALARM SYSTEM |
EXCEEDING 9300 SQM |
REQUIRED |
PROTECTED WITH AUTOMATIC SPRINKLER SYSTEM |
NOT REQUIRED |
B |
EXTINGUISHING REQUIREMENTS |
|
|
1 |
PORTABLE FIRE EXTINGUISHERS |
TYPE AND RATING IN ACCORDANCE WITH NFPA 10 |
REQUIRED |
2 |
FIRE BLANKETS |
IN KITCHEN OR PANTRY |
REQUIRED |
3 |
STANDPIPE SYSTEM |
COMPLYING WITH NFPA 14 |
REQUIRED |
4 |
FIRE HOSE REELS |
25MM DIAMETER HOSE |
REQUIRED |
5 |
AUTOMATIC SPRINKLER SYSTEM |
3 OR MORE STORIES IN HEIGHT |
REQUIRED |
FIRE AREA EXCEEDING 1115 SQM |
REQUIRED |
TOTAL AREA OF ALL FLOORS EXCEEDS 2230 SQM |
REQUIRED |
BULK STORAGE OF TIRES EXCEEDS 566 SQM |
REQUIRED |
MINI-STORAGE BUILDINGS 232 SQM |
REQUIRED |
6 |
OTHER EXTINGUISHING EQUIPMENT |
COMPLIANCE FROM INDIVIDUAL NFPA CODES & STANDARDS |
PERMITTED |