FIRE PROTECTION

VIIFIRE PROTECTIONORDINARY-HAZARD STORAGE
A DETECTION ALARM AND COMMUNICATION SYSTEMS    
1 FIRE ALARM SYSTEM EXCEEDING 9300 SQM REQUIRED
PROTECTED WITH AUTOMATIC SPRINKLER SYSTEM NOT REQUIRED
B EXTINGUISHING REQUIREMENTS    
1 PORTABLE FIRE EXTINGUISHERS TYPE AND RATING IN ACCORDANCE WITH NFPA 10 REQUIRED
2 FIRE BLANKETS IN KITCHEN OR PANTRY REQUIRED
3 STANDPIPE SYSTEM COMPLYING WITH NFPA 14 REQUIRED
4 FIRE HOSE REELS 25MM DIAMETER HOSE REQUIRED
5 AUTOMATIC SPRINKLER SYSTEM 3 OR MORE STORIES IN HEIGHT REQUIRED
FIRE AREA EXCEEDING 1115 SQM REQUIRED
TOTAL AREA OF ALL FLOORS EXCEEDS 2230 SQM REQUIRED
BULK STORAGE OF TIRES EXCEEDS 566 SQM REQUIRED
MINI-STORAGE BUILDINGS 232 SQM REQUIRED
6 OTHER EXTINGUISHING EQUIPMENT COMPLIANCE FROM INDIVIDUAL NFPA CODES & STANDARDS PERMITTED