Site Access

IIIBUILDING AND SITE ACCESS FOR FIRE FIGHTING & RESCUEHIGH HAZARD INDUSTRIAL BUILDINGS
   LOW HAZARD ORDINARY HAZARD
A SITE ACCESS 4.0M MINIMUM CLEAR WIDTH & 4.5M MIN. CLEAR HEIGHT REQUIRED
B ACCESS ROAD 4.0M MIN. WIDTH AND 24 TON LOAD CAPACITY REQUIRED
WITHIN A TRAVEL DISTANCE OF 45M FROM EVERY POINT ON PROJECTED PLAN AREA OF ANY BUILDING.
C FIRE ENGINE HARDSTANDING LENGTH OR NUMBER BASE ON THE GROSS FLOOR AREA OF THE BUILDING REQUIRED
6M X 15M (MINIMUM), WITH LONGER SIDE PARALLEL TO THE FACADE OF THE BUILDING
POSITIONED SO THAT THE NEARER EDGE SHALL BE NOT LESS THAN 2M OR NOT MORE THAN 10M FROM THE CENTER POSITION OF THE ACCESS OPENING, MEASURED HORIZONTALLY. REQUIRED
D FIRE COMMAND CENTER OTHER THAN HIGH-RISE WITH EMERGENCY VOICE COMMUNICATION SYSTEM AND/OR SMOKE CONTROL SYSTEM REQUIRED
9 SQM MINIMUM FLOOR AREA (LEAST DIMENSION 2.5M)
E FIRE LIFT COMPLYING WITH ALL FIRE LIFTS REQUIREMENTS TO COMPLY WITH REQUIREMENTS WHEN PROVIDED AS REQUIRED