VIIFIRE PROTECTION (NR-NOT REQUIRED / R-REQUIRED)GENERAL INDUSTRIAL BUILDINGS
A DETECTION ALARM AND COMMUNICATION SYSTEMS    
1 FIRE ALARM SYSTEM COMPLYING WITH NFPA 72 REQUIRED
B EXTINGUISHING REQUIREMENTS    
1 PROTABLE FIRE EXTINGUISHERS TYPE AND RATING IN ACCORDANCE WITH NFPA 10 REQUIRED
2 FIRE BLANKETS IN KITCHEN OR PANTRY REQUIRED
3 STANDPIPE SYSTEM COMPLYING WITH NFPA 14 REQUIRED
4 FIRE HOSE REELS 25MM DIAMETER HOSE REQUIRED
5 AUTOMATIC SPRINKLER SYSTEM   LOW HAZARD ORDINARY
3 OR MORE STORIES IN HEIGHT NR R
FIRE AREA EXCEEDING 1115 SQM

NR

R
TOTAL AREA OF ALL FLOORS EXCEEDS 2230 SQM NR R
WOODWORKING OPERATIONS EXCEEDING 232 SQM REQUIRED
POWER GENERATION BUILDING REQUIRED
6 OTHER EXTINGUISHING SYSTEM COMPLIANCE FROM INDIVIDUAL CODES & STANDARDS IN LIEAU OF AN AUTOMATIC SUPPRESSION SYSTEM

General Industrial

HEIGHT & AREA ALLOWED

IN ACCORDANCE WITH NFPA 5000 CHAPTER 7 TABLE 7.4.1 FOR THE ALLOWABLE BUILDING HEIGHT AND AREA REQUIREMENTS


40.1.4.1.1 GENERAL INDUSTRIAL OCCUPANCY 

INDUSTRIAL OCCUPANCY THAT CONDUCT ORDINARY AND LOW HAZARD INDUSTRIAL OPERATIONS IN BUILDINGS OF CONVENTIONAL DESIGN THAT ARE USABLE FOR VARIOUS TYPES OF INDUSTRIAL PROCESSES.

INDUSTRIAL OCCUPANCY THAT INCLUDE MULTISTORY BUILDINGS WHERE FLOORS ARE OCCUPIED BY DIFFERENT TENANTS, OR BUILDINGS THAT ARE USABLE FOR SUCH OCCUPANCY AND, THEREFORE, ARE SUBJECT TO POSSIBLE USE FOR TYPES OF INDUSTRIAL PROCESSES WITH A HIGH DENSITY OF EMPLOYEE POPULATION

INDUSTRIAL OCCUPANCY - FACTORY AND WORKSHOPS

AN OCCUPANCY IN WHICH PRODUCTS ARE MANUFACTURED OR IN WHICH PROCESSING, ASSEMBLING, MIXING, PACKAGING, FINISHING, DECORATING, OR REPAIR OPERATIONS ARE CONDUCTED

APPLICATIONS 

DRY CLEANING PLANTS / FACTORIES OF ALL KINDS / FOOD PROCESSING PLANTS / GAS PLANTS / HANGARS (FOR SERVICING/MAINTENANCE) / LAUNDRIES / POWER PLANTS / PUMPING STATIONS / REFINERIES / SAWMILLS / TELEPHONE EXCHANGES