BUILDING AND SITE ACCESS FOR FIRE FIGHTING & RESCUE

COLLEGE DORMITORIES / STUDENT HOUSING / MILITARY BARRACKS / LABOR/WORKERS & STAFF HOUSING.A BUILDING OR GROUP OF BUILDINGS THAT PROVIDES SLEEPING ACCOMODATIONS ON A TRANSIENT OR PERMANENT BASIS WITH OR WITHOUT MEALS BUT WITHOUT SEPARATE COOKING FACILITIES FOR INDIVIDUAL OCCUPANTS

IIIBUILDING AND SITE ACCESS FOR FIRE FIGHTING & RESCUEHIGH-RISE DORMITORY & ACCOMODATIONS BUILDINGS
A SITE ACCESS 4.0M MINIMUM CLEAR WIDTH REQUIRED
4.5M MINIMUM CLEAR HEIGHT
B ACCESS ROAD 4.0M MIN. WIDTH AND 24 TON LOAD CAPACITY NOT REQUIRED
WITHIN A TRAVEL DISTANCE OF 45M FROM EVERY POINT ON PROJECTED PLAN AREA OF ANY BUILDING.
C FIRE ENGINE HARDSTANDING LENGTH OR NUMBER BASE ON THE GROSS FLOOR AREA OF THE BUILDING REQUIRED
6M X 15M (MINIMUM), WITH LONGER SIDE PARALLEL TO THE FACADE OF THE BUILDING
POSITIONED SO THAT THE NEARER EDGE SHALL BE NOT LESS THAN 2M OR NOT MORE THAN 10M FROM THE CENTER POSITION OF THE ACCESS OPENING, MEASURED HORIZONTALLY.
D FIRE COMMAND CENTER HIGH-RISE BUILDING AND OTHER THAN HIGH-RISE WITH EMERGENCY VOICE COMMUNICATION SYSTEM AND/OR SMOKE CONTROL SYSTEM REQUIRED
9 SQM MINIMUM AREA (LEAST DIMENSION 2.4M)
AT LEAST WITH 1M CLEARANCE FROM ALL EQUIPMENT
2-HOURS ENCLOSURES (WALLS, OPENINGS & PENETRATIONS)
PROVIDED WITH PROMINENTLY MARKED EXTERIOR ENTRANCES
INSTEAD OF A DEDICATED FIRE RATED ROOM: LOBBIES OR OTHER SPACES ADJACENT TO THE MAIN ENTRANCE OF THE BUILDING
E FIRE LIFT BUILDINGS EQUAL OR MORE THAN 28M HIGH ABOVE ENGINE ACCESS LEVEL. REQUIRED
BUILDINGS EXCEEDS 9.0M BELOW THE LEVEL OF EXIT DISCHARGE REQUIRED
SERVES ALL HABITABLE FLOORS REQUIRED IN EVERY FIRE SERVICE ACCESS ELEVATOR/FIRE LIFT PROVISIONS
CONTAINED WITHIN A DEDICATED PROTECTED SHAFT
APPROACHED BY FIRE FIGHTING LOBBY AT EACH STOREY
ADJACENT AND ACCESIBLE TO AN EXIT STAIRCASE
FIRE SERVICE ACCESS ELEVATORS/FIRE LIFT AS PER NFPA 5000 (2012 Ed.) CHAPTER 54.12 REQUIRED
AMBULANCE STRETCHER ACCOMODATION ELEVATOR/LIFT AS PER NFPA 5000 (2012 Ed.) CHAPTER 54.3 TO SERVE AS THE OTHER REQUIRED FIRE SERVICE ACCESS ELEVATORS/FIRE LIFT
WHEN REQUIRED, AT LEAST ONE (1) FIRE LIFT FOR EVERY 900 SQM. FLOOR AREA REQUIRED IN EVERY FIRE LIFT PROVISIONS

MEANS OF EGRESS

COLLEGE DORMITORIES / STUDENT HOUSING / MILITARY BARRACKS / LABOR/WORKERS & STAFF HOUSING.A BUILDING OR GROUP OF BUILDINGS THAT PROVIDES SLEEPING ACCOMODATIONS ON A TRANSIENT OR PERMANENT BASIS WITH OR WITHOUT MEALS BUT WITHOUT SEPARATE COOKING FACILITIES FOR INDIVIDUAL OCCUPANTS

IVMEANS OF EGRESSHIGH-RISE DORMITORY & ACCOMODATIONS BUILDINGS
A MEANS OF EGRESS GENERAL REQUIREMENTS  
1 SEPARATION OF MEANS OF EGRESS COMPLYING WITH CHAPTER 7 NFPA 101 REQUIRED
  EXIT ACCESS CORRIDORS SERVING AN AREA HAVING AN OCCUPANT LOAD EXCEEDING 30 1-HR FRR*
  EXITS CONNECTS 3 OR FEWER STORIES 1-HR FRR*
CONNECTS 4 OR MORE STORIES 2-HRS FRR*
  OPENING PROTECTIVE FIRE DOOR ASSEMBLIES EQUIPPED WITH DOOR CLOSERS REQUIRED
  CONSTRUCTION LIMITED OR NON-COMBUSTIBLE MATERIALS REQUIRED
  OPENINGS AND PENETRATIONS IN EXIT ENCLOSURE COMPLYING WITH CHAPTER 7 NFPA 101 PERMITTED
2 EXITS HEADROOM NOT LESS THAN 2285MM REQUIRED
  HEADROOM ON STAIRS NOT LESS TAHN 2285MM REQUIRED
3 WALKING SURFACES IN THE MEANS OF EGRESS COMPLYING WITH CHAPTER 7 NFPA 101 REQUIRED
4 CHANGES IN LEVEL IN THE MEANS OF EGRESS COMPLYING WITH CHAPTER 7 NFPA 101 REQUIRED
5 GUARDS PROVIDED AT THE OPEN SIDES OF MEANS OF EGRESS 760MM ABOVE THE FLOOR OR FINISHED GROUND LEVEL REQUIRED
6 IMPEDIMENT TO EGRESS   NOT PERMITTED
7 MEANS OF EGRESS RELIABILITY CONTINUOUSLY MAINTAINED FREE OF ALL OBSTRUCTION OR IMPEDIMENTS REQUIRED
  FURNISHING AND DECORATION FURNITURES, MOVABLE OBJECTS, MIRRORS, ETC. NOT PERMITTED
B MEANS OF EGRESS COMPONENTS    
1 FIRE DOORS COMPLYING WITH CHAPTER 7 NFPA 101 REQUIRED
SIDE-HINGE OR PIVOTED-SWINGING TYPE ANY DOOR ASSEMBLY IN A MEANS OF EGRESS REQUIRED
MINIMUM DOOR LEAF WIDTH 810MM
HORIZONTAL SLIDING DOORS COMPLYING WITH CHAPTER 7 NFPA 101 NOT PERMITTED ACROSS CORRIDORS
VERTICAL ROLLING DOORS COMPLYING WITH CHAPTER 7 NFPA 101 NOT PERMITTED
REVOLVING DOOR / POWERED DOORS COMPLYING WITH CHAPTER 7 NFPA 101 PERMITTED
SELF-CLOSING DEVICES IN ALL DOORS REQUIRED TO BE NORMALLY KEPT CLOSED REQUIRED
2 STAIRS COMPLYING WITH CHAPTER 7 NFPA 101 REQUIRED
STANDARD STAIRS FEWER THAN 50 PERSON (CLEAR WIDTH) 915MM
1120MM
>2000 PERSON (CLEAR WIDTH) 1420MM
SPRIRAL STAIRS COMPLYING WITH CHAPTER 7 NFPA 101 NOT PERMITTED
CURVE STAIRS COMPLYING WITH CHAPTER 7 NFPA 101 NOT PERMITTED
WINDERS COMPLYING WITH CHAPTER 7 NFPA 101 NOT PERMITTED
GUARDS AND HANDRAILS COMPLYING WITH CHAPTER 7 NFPA 101 REQUIRED
ENCLOSURE AND PROTECTION OF STAIRS COMPLYING WITH CHAPTER 7 NFPA 101 REQUIRED
ENCLOSURES ALL INSIDE STAIR SERVING AS AN EXIT COMPONENT REQUIRED
DOORS FPR* < 3 STOREYS / > 3 STOREYS 1-HR FPR** / 1.5-HRS FPR**
ENCLOSURES FRR* < 3 STOREYS / > 3 STOREYS 1-HR FRR** / 2-HRS FRR**
ENCLOSURE EXEMPTION PENETRATING ONE FLOOR LEVEL OR SERVING MEZZANINE ONLY PERMITTED
EXPOSURES WALLS AND OPENINGS WITHIN 3050MM HORIZONTALLY OF AN EXTERIOR STAIRWAY ENCLOSURE 1-HR FRR*
USABLE SPACE WITHIN EXIT ENCLOSURE NOT PERMITTED
UNDER STAIRS IN ACCORDANCE WITH NFPA 101 PERMITTED
STAIRWAY IDENTIFICATION SERVING 3 OR MORE STOREYS REQUIRED
EXIT STAIR PATH MARKINGS ALL STAIR COMPONENTS REQUIRED
PERIMETER DEMARCATION MARKING COMPLYING WITH NFPA 101 REQUIRED
LOCK, LATCHES & ALARM DEVICES COMPLYING WITH NFPA 101 PERMITTED
RE-ENTRY PROVISIONS LOCKED STAIRS EXCEEDING 4 STOREYS REQUIRED
3 RAMPS COMPLYING WITH NFPA 101 PERMITTED
AS SECONDARY EXIT FOR ONE (1) BASEMENT LEVEL NOT PERMITTED
4 ROOF ACCESS BUILDING EQUAL OR MORE THAN 4 STOREYS (G+3) OR ROOFS 12M ABOVE GRADE PLANE REQUIRED
WHERE OPEN STAIR/S ARE PERMITTED AND PROVIDED IN LOW-RISE DORMITORY OR ACCOMODATION NOT APPLICABLE
ONE AT EACH 9300 SQM ROOF AREA OR FLAT ROOFS OR ROOF PITCHREQUIRED
ROOF ACCESS COMPONENTS SMOKE VENTS (FIXED WALL OPENING/S) AT THE TOP OF THE STAIRWELL WITH A MINIMUM AREA OF 1.5 SQM NOT APPLICABLE
STAIR ACCESS TO ROOF EQUIPPED WITH OPERABLE DOORS REQUIRED
5 SMOKE PROOF ENCLOSURES FRR* (FIRE RESISTANCE RATING)  
STAIR ENCLOSURES INTERIOR STAIRS SERVING AS AN EXIT COMPONENT REQUIRED
OPEN STAIR PENETRATING ONE (1) FLOOR / LEVEL ONLY PERMITTED
FIRE FIGHTING LOBBY (F/F LOBBY) IN EVERY FIRE LIFT PROVISIONS REQUIRED
ADJACENT AND ACCESIBLE TO AN EXIT STAIRCASE REQUIRED IN EVERY FIRE SERVICE ACCESS EEVATOR / FIRE LIFT PROVISIONS
SERVES AS A COMMON LOBBY FOR BOTH FIRE LIFT AND THE ADJACENT EXIT STAIRCASE
6 SQM MINIMUM AREA / WORKING SPACE (LEAST SIDE DIMENSION 2.0M)
PROVISIONS AT THE LEVEL OF EXIT DISCHARGE NOT REQUIRED IF EXITS COMPLIES WITH EXIT DISCHARGE REQUIREMENTS
SMOKE-STOP LOBBY (S/S LOBBY) HIGH-RISE BUILDINGS WITH HABITABLE HEIGHT HIGHER THAN 28 METERS REQUIRED ON ALL FLOOR LEVELS
BASEMENT LEVEL/S EXCEED 9.0 M DEPTH REQUIRED
BUILDING TRAVERSES MORE THAN FIVE (5) FLOOR LEVELS INCLUDING BASEMENT/S AND BELONGS TO A PLACE OF PUBLIC RESORT REGARDLESS OF THE HABITABLE HEIGHT. NOT APPLICABLE
3 SQM MIN. AREA (LEAST SIDE DIMENSION 1.8M) REQUIRED
PROVISIONS AT THE LEVEL OF EXIT DISCHARGE NOT REQUIRED IF EXITS COMPLIES WITH EXIT DISCHARGE REQUIREMENTS
  S/S & F/F LOBBY DOORS & WALL ENCLOSURES 1.5-HR FPR** FIRE PROTECTION RATING / 2-HRS FRR* FIRE RESISTANCE RATING REQUIRED
6 HORIZONTAL EXITS COMPLYING WITH CHAPTER 7 NFPA 101 PERMITTED
7 EXIT PASSAGEWAYS ENCLOSURE AND SEPARATION FIRE RESISTANCE RATING COMPLYING WITH CHAPTER 7 NFPA 101 REQUIRED 1-HR FRR*
MIN. WIDTH NOT LESS THAN 2/3 OF THE WIDTH OF THE EXIT STAIR REQUIRED
8 ESCALATORS & MOVING WALKS AS PART OF THE REQUIRED MEANS OF EGRESS NOT PERMITTED
9 FIRE ESCAPE STAIRS COMPLYING WITH CHAPTER 7 NFPA 101 PERMITTED
10 FIRE ESCAPE LADDERS COMPLYING WITH CHAPTER 7 NFPA 101 NOT PERMITTED
11 SLIDE ESCAPES COMPLYING WITH CHAPTER 7 NFPA 101 PERMITTED
12 ALTERNATING TREAD DEVICES COMPLYING WITH CHAPTER 7 NFPA 101 NOT PERMITTED
13 AREAS OF REFUGE COMPLYING WITH CHAPTER 7 NFPA 101 REQUIRED
14 ELEVATORS AS PART OF THE REQUIRED MEANS OF EGRESS NOT PERMITTED
ELEVATOR DOORS OPENING INTO EXIT ENCLOSURES NOT PERMITTED
C CAPACITY OF MEANS OF EGRESS  
1 OCCUPANT LOAD NFPA 101 TABLE 7.3.1.2 OCCUPANT LOAD FACTOR 18.6 SQM / PERSON
2 EGRESS CAPACITY NFPA 101 TABLE 7.3.3.1 CAPACITY FACTORS REQUIRED
D NUMBER OF EXITS COMPLYING WITH NFPA 101 CHAPTER 7  
1 SINGLE EXIT SERVING ALL FLOOR LEVELS NOT PERMITTED
IN MEZZANINES OR ANY SECTIONS WITH EXIT TRAVEL WITHIN COMMON PATH LIMIT PERMITTED
SLEEPING ROOMS HAS AN EXIT DOOR OPENING DIRECTLY TO A STREET OR YARD AT FINISHED GROUND LEVEL NOT APPLICABLE
SLEEPING ROOMS HAS DIRECT ACCESS TO OUTSIDE STAIR & SERVES A MAXIMUM OF 2 UNITS BOTH OF WHICH ARE LOCATED ON THE SAME FLOOR. PERMITTED
SLEEPING ROOMS HAS DIRECT ACCESS TO AN INSIDE STAIR SERVING ONLY THAT UNIT & SEPARATED FROM OTHER PARTS OF THE BLDG. WITH 1-HR FIRE BARRIERS PERMITTED
CONDITIONS * PERMITTING SINGLE EXIT PROVISIONS (REQUIRES COMPLIANCE TO ALL STATED CONDITIONS) 1 FLOOR AREA IS EQUAL OR LESS THAN 500 SQM NOT APPLICABLE
2 TRAVEL DISTANCE FROM THE ENTRANCE DOOR OF ANY DWELLING UNIT TO AN EXIT DOES NOT EXCEED 10.7M. NOT APPLICABLE
3 EXIT STAIRWAY IS COMPLETELY ENCLOSED OR SEPARATED FROM THE REST OF THE BUILDING NOT APPLICABLE
4 STAIRWAY SERVE ONLY 1 BASEMENT LEVEL NOT APPLICABLE
5 ALL OPENINGS BETWEEN THE EXIT ENCLOSURE AND THE BUILDING ARE PROTECTED WITH SELF-CLOSING DOOR ASSEMBLIES OF 1-HOUR FPR** NOT APPLICABLE
6 ALL CORRIDORS SERVING AS ACCESS TO EXITS HAVE A MINIMUM OF 1-HOUR FRR* NOT APPLICABLE
7 HORIZONTAL & VERTICAL SEPARATION OF 1.0-HR FRR* PROVIDED BETWEEN SLEEPING ROOMS NOT APPLICABLE
8 PROVIDED WITH SMOKE VENTS (FIXED WALL OPENING/S) THE TOP OF THE STAIRWELL WITH A MINIMUM AREA OF 1.5SQM. NOT APPLICABLE
9 EXIT STAIR (TRAVERSES MORE THAN 5 STORIES INCLUDING BASEMENTS) IS PRESSURIZED. REQUIRED
2 NOT LESS THAN 2 SEPARATE EXITS / EXIT ACCESS DOORS SLEEPING ROOMS EXCEEDING 185 SQM REQUIRED
50 - 500 OCCUPANTS REQUIRED
ON EVERY STORY AND ACCESIBLE FROM EVERY PART OF EVERY STORY REQUIRED
3 NOT LESS THAN THREE (3) SEPARATE EXITS EQUAL OR MORE THAN 500 OCCUPANTS REQUIRED
4 NOT LESS THAN FOUR (4) SEPARATE EXITS EQUAL OR MORE THAN 1000 OCCUPANTS REQUIRED
E ARRANGEMENT OF EXITS NS*-NOT SPRINKLERED / S**-SPRINKLERED NS* S**
1 TRAVEL DISTANCE NFPA 101 TABLE A.7.6 TOTAL TRAVEL DISTANCES PERMITTED 53M 99M
WITHIN A SLEEPING ROOM TO A CORRIDOR DOOR 23M 38M
FROM THE CORRIDOR DOOR OF SLEEPING ROOM TO THE NEAREST EXIT 30M 61M
FROM A SLEEPING ROOM ENTRANCE DOOR TO THE NEAREST EXIT FOR EXTERIOR WAYS OR EXIT ACCESS 61M 61M
2 COMMON PATH LIMIT NFPA 101 TABLE A.7.6 10.7M 15M
3 DEAD-END CORRIDOR NFPA 101 TABLE A.7.6 10.7M 15M
4 EXIT DISCHARGE    
  EXTERIOR DISCHARGE COMPLYING WITH NFPA 101 REQUIRED
  DISCHARGE THROUGH AREAS ON LEVEL OF EXIT DISCHARGE MAXIMUM 10M TRAVEL DISTANCE TO BUILDING EXTERNAL PERMITTED
50% OF THE REQUIRED NUMBER OF EXITS & 50% OF THE REQUIRED EXIT CAPACITY (SPRINKLER PROTECTED) PERMITTED
5 EXTERIOR WAYS OF EXIT COMPLYING WITH NFPA 101 PERMITTED
6 ACCESIBLE MEANS OF EGRESS EXIT PROVISIONS FOR PEOPLE WITH SEVERE MOBILITY IMPAIRMENT (NOT LESS THAN 2 EXITS REQUIRED) REQUIRED
7 ILLUMINATION OF MEANS OF EGRESS COMPLYING WITH CHAPTER 7 NFPA 101 REQUIRED
8 EMERGENCY LIGHTING COMPLYING WITH CHAPTER 7 NFPA 101 REQUIRED
9 MARKINGS OF MEANS OF EGRESS COMPLYING WITH CHAPTER 7 NFPA 101 REQUIRED
F SPECIAL MEANS OF EGRESS PROVISIONS    
1 FIREMEN ACCESS PANELS HABITABLE HEIGHT EXCEEDING 10M REQUIRED
2 REFUGE FLOORS BUILDING EXCEEDING 30 STORIES REQUIRED
3 ELEVATORS FOR OCCUPANT CONTROLLED EVACUATION PRIOR TO PHASE 1 EMERGENCY RECALL OPERATIONS COMPLYING WITH CHAPTER 7 NFPA 101 PERMITTED

FEATURES OF FIRE PROTECTION

COLLEGE DORMITORIES / STUDENT HOUSING / MILITARY BARRACKS / LABOR/WORKERS & STAFF HOUSING.A BUILDING OR GROUP OF BUILDINGS THAT PROVIDES SLEEPING ACCOMODATIONS ON A TRANSIENT OR PERMANENT BASIS WITH OR WITHOUT MEALS BUT WITHOUT SEPARATE COOKING FACILITIES FOR INDIVIDUAL OCCUPANTS

VIFEATURES OF FIRE PROTECTION (NFPA 5000 TABLES 7.2.1.1, 7.3.2.1, 7.3.5 (a), 7.3.5.5, 7.4.1)HIGH-RISE DORMITORY & ACCOMODATIONS BUILDINGS
A CONSTRUCTION COMPLYING WITH CHAPTER 7 & 8 OF NFPA 5000 REQUIRED
1 CONSTRUCTION (NON-COMBUSTIBLE OR LIMITED COMBUSTIBLE MATERIALS) TYPE I OR TYPE II EXTERIOR BEARING WALLS HOURLY RATINGS REQUIRED PER TYPE OF CONSTRUCTION BASED ON NFPA 5000 HEIGHT & AREA REQUIREMENTS
FRAMING, COLUMNS, BEAMS, GIRDERS, TRUSSES
FLOOR CONSTRUCTION
B SUBDIVISION OF BUILDING SPACES COMPLYING WITH NFPA 101 & NFPA 5000 REQUIRED
1 FIRE BARRIERS COMPLYING WITH NFPA 101 & NFPA 5000 REQUIRED
  SEPARATION BETWEEN GUEST ROOM/SUITES SPRINKLERED 0.5-HR FRR*
2 SEPARATION FROM OTHER OCCUPANCIES AS PER NFPA 101 TABLE 6.1.14.4.1 (a), (b) REQUIRED
3 CORRIDORS RATED SEPARATION COMPLYING WITH NFPA 101.28 & 29 REQUIRED
  REQUIRED SEPARATION SPRINKLERED (S) / NOT SPRINKLERED (NS) 0.5-HR FRR*
  DOORS OPENING ONTO EXIT ACCES CORRIDORS (S/NS) 20-MIN FPR**
4 SMOKE PARTITIONS COMPLYING WITH NFPA 101 & NFPA 5000 NOT REQUIRED
5 SMOKE BARRIERS COMPLYING WITH NFPA 101 & NFPA 5000 NOT REQUIRED
C VERTICAL OPENINGS PROTECTION PROTECTION COMPLYING WITH NFPA CODES REQUIRED
1 COMMUNICATING SPACES COMPLYING WITH CHAPTER 8 NFPA 101 PERMITTED
2 ATRIUMS COMPLYING WITH CHAPTER 8 NFPA 101 PERMITTED
3 CONVENIENCE OPENINGS COMPLYING WITH CHAPTER 8 NFPA 101 PERMITTED
4 SHAFTS COMPLYING WITH CHAPTER 8 NFPA 101 PERMITTED
5 MEZZANINES COMPLYING WITH CHAPTER 8 NFPA 101 PERMITTED
6 CONCEALED SPACES & DRAFTSTOPS COMPLYING WITH CHAPTER 8 NFPA 101 REQUIRED
  EXTERIOR & INTERIOR WALL & PARTITION FIRE STOPPED AT EACH LEVEL, TOP STORY CEILING LEVEL & AT THE LEVEL OF SUPPORT FOR ROOFS REQUIRED
  UNOCCUPIED ATTIC SPACES DRAFTSTOPS INTO AREAS NOT EXCEEDING 280 SQM REQUIRED
  CONCEALED SPACES (CEILINGS & FLOORS) DRAFTSTOPS INTO AREAS NOT EXCEEDING 93 SQM REQUIRED
  CONCEALED SPACES (FLOORS & ROOFS) DRAFTSTOPS INTO AREAS NOT EXCEEDING 280 SQM REQUIRED
D HAZARDOUS AREA PROTECTION IN ACCORDANCE WITH TABLE 28.3.2.2.2 OF NFPA 101 REQUIRED
1 BOILER ROOM & FUEL-FIRE HEATER ROOM SERVING MORE THAN A SINGLE SLEEPING ROOM SEPARATION AND PROTECTION REQUIRED 1-HRS FRR* AND SPRINKLERS
2 EMPLOYEE LOCKER ROOMS SEPARATION AND PROTECTION REQUIRED 1-HR FRR* OR SPRINKLERS
3 BULK LAUNDRIES SEPARATION AND PROTECTION REQUIRED 1-HR FRR* AND SPRINKLERS
4 MAINTENANCE SHOPS SEPARATION AND PROTECTION REQUIRED 1-HR FRR* AND SPRINKLERS
5 STORAGE ROOMS SEPARATION AND PROTECTION REQUIRED 1-HR FRR* OR SPRINKLERS
6 TRASH COLLECTION ROOMS SEPARATION AND PROTECTION REQUIRED 1-HR FRR* AND SPRINKLERS

INTERIOR FINISH CONTENTS AND FURNISHING

COLLEGE DORMITORIES / STUDENT HOUSING / MILITARY BARRACKS / LABOR/WORKERS & STAFF HOUSING.A BUILDING OR GROUP OF BUILDINGS THAT PROVIDES SLEEPING ACCOMODATIONS ON A TRANSIENT OR PERMANENT BASIS WITH OR WITHOUT MEALS BUT WITHOUT SEPARATE COOKING FACILITIES FOR INDIVIDUAL OCCUPANTS

VINTERIOR FINISH CONTENTS AND FURNISHINGHIGH-RISE DORMITORY & ACCOMODATIONS BUILDINGS
A INTERIOR FINISH COMPLYING WITH CHAPTER 10 OF NFPA 101 REQUIRED
1 INTERIOR WALL & CEILING FINISHES EXIT ENCLOSURES CLASS A
LOBBIES & CORRIDORS CLASS A OR CLASS B
OTHER SPACES CLASS A, CLASS B OR CLASS C
2 INTERIOR FLOOR FINISHES EXIT ENCLOSURES, EXIT ACCESS CORRIDORS AND SPACES NOT SEPARATED FROM THEM CLASS II

FIRE PROTECTION

COLLEGE DORMITORIES / STUDENT HOUSING / MILITARY BARRACKS / LABOR/WORKERS & STAFF HOUSING.A BUILDING OR GROUP OF BUILDINGS THAT PROVIDES SLEEPING ACCOMODATIONS ON A TRANSIENT OR PERMANENT BASIS WITH OR WITHOUT MEALS BUT WITHOUT SEPARATE COOKING FACILITIES FOR INDIVIDUAL OCCUPANTS

VIIFIRE PROTECTION (FRR* FIRE RESISTANCE RATING / FPR** FIRE PROTECTION RATING)HIGH-RISE DORMITORY & ACCOMODATIONS BUILDINGS
A DETECTION ALARM AND COMMUNICATION SYSTEMS    
1 FIRE ALARM SYSTEM COMPLYING WITH NFPA 72 REQUIRED
B EXTINGUISHING REQUIREMENTS COMPLIANCE WITH INDIVIDUAL CODES & STANDARDS REQUIRED
1 PORTABLE FIRE EXTINGUISHERS TYPE AND RATING IN ACCORDANCE WITH NFPA 10 REQUIRED
2 FIRE BLANKETS IN KITCHEN OR PANTRY REQUIRED
3 STANDPIPE SYSTEM BUILDING EXCEEDING 9M IN HABITABLE HEIGHT REQUIRED
4 FIRE HOSE REELS 25MM DIAMETER HOSE REQUIRED
5 AUTOMATIC SPRINKLER SYSTEM THROUGHOUT PROTECTION (ALL FLOOR LEVELS) REQUIRED
IN BASEMENTS IRREGARDLESS OF USAGE REQUIRED
ACCOMODATIONS OF NOT MORE THAN 2 STORIES & FLOOR AREA NOT EXCEEDING 1115 SQM, PROVIDED WITH NOT LESS THAN 2-EXITS COMPLYING WITH EXIT DISCHARGE REQUIREMENTS NOT APPLICABLE
SLEEPING ROOMS HAVING A DOOR OPENING DIRECTLY OUTSIDE AT THE STREET LEVEL NOT APPLICABLE
SLEEPING ROOMS HAVING AN EXTERIOR ACCESS COMPLYING WITH CHAPTER 7 OF NFPA 101 NOT APPLICABLE
6 OTHER EXTINGUISHING EQUIPMENT PROVIDED IN LIEAU OF THE REQUIRED DRAFTSTOPS IN CONCEALED SPACES PERMITTED