IV | MEANS OF EGRESS | LOW-HAZARD STORAGE |
A |
MEANS OF EGRESS GENERAL REQUIREMENTS |
|
1 |
SEPARATION OF MEANS OF EGRESS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
REQUIRED |
|
EXIT ACCESS CORRIDORS |
SERVING AN AREA HAVING AN OCCUPANT LOAD EXCEEDING 30 |
1-HR FRR* |
|
EXITS |
CONNECTS 3 OR FEWER STORIES |
1-HR FRR* |
CONNECTS 4 OR MORE STORIES |
2-HRS FRR* |
|
OPENING PROTECTIVE |
FIRE DOOR ASSEMBLIES EQUIPPED WITH DOOR CLOSERS |
REQUIRED |
|
CONSTRUCTION |
LIMITED OR NON-COMBUSTIBLE MATERIALS |
REQUIRED |
|
OPENINGS AND PENETRATIONS IN EXIT ENCLOSURE |
COMPLYING WITH CHAPTER 7 NFPA 101 |
PERMITTED |
2 |
EXITS HEADROOM |
NOT LESS THAN 2285MM |
REQUIRED |
|
HEADROOM ON STAIRS |
NOT LESS TAHN 2285MM |
REQUIRED |
|
HEADROOM IN INDUSTRIAL EQUIPMENT ACCESS |
AS PROVIDED IN CHAPTER 40 NFPA 101 |
PERMITTED |
3 |
WALKING SURFACES IN THE MEANS OF EGRESS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
REQUIRED |
4 |
CHANGES IN LEVEL IN THE MEANS OF EGRESS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
REQUIRED |
5 |
GUARDS |
AT THE OPEN SIDES OF MEANS OF EGRESS 760MM ABOVE THE FLOOR OR FINISHED GROUND LEVEL |
REQUIRED |
6 |
IMPEDIMENT TO EGRESS |
|
NOT PERMITTED |
7 |
MEANS OF EGRESS RELIABILITY |
CONTINUOUSLY MAINTAINED FREE OF ALL OBSTRUCTION OR IMPEDIMENTS |
REQUIRED |
|
FURNISHING AND DECORATION |
FURNITURES OR MOVABLE OBJECTS, MIRRORS, ETC. |
NOT PERMITTED |
B |
MEANS OF EGRESS COMPONENTS |
|
|
1 |
FIRE DOORS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
REQUIRED |
SIDE-HINGE OR PIVOTED-SWINGING TYPE |
ANY DOOR ASSEMBLY IN A MEANS OF EGRESS |
REQUIRED |
MINIMUM DOOR LEAF WIDTH |
810MM |
HORIZONTAL SLIDING DOORS |
OCCUPANT LOAD OF FEWER THAN 10 |
PERMITTED |
VERTICAL ROLLING DOORS |
OCCUPANT LOAD OF FEWER THAN 10 |
PERMITTED |
REVOLVING DOOR / POWERED DOORS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
PERMITTED |
SELF-CLOSING DEVICES |
DOORS REQUIRED TO BE NORMALLY KEPT CLOSED |
REQUIRED |
2 |
STAIRS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
REQUIRED |
NON-COMBUSTIBLE GRATED STAIR TREADS AND LANDINGS |
PERMITTED |
STANDARD STAIRS |
FEWER THAN 50 PERSON |
915MM CLEAR WIDTH |
1120MM CLEAR WIDTH |
≥2000 PERSON |
1420MM CLEAR WIDTH |
SPIRAL STAIRS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
PERMITTED |
CURVE STAIRS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
NO REQUIREMENTS |
WINDERS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
NO REQUIREMENTS |
GUARDS AND HANDRAILS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
REQUIRED |
OUTSIDE STAIRS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
PERMITTED |
ENCLOSURE AND PROTECTION OF STAIRS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
REQUIRED |
ENCLOSURES |
ALL INSIDE STAIR SERVING AS AN EXIT COMPONENT |
REQUIRED |
DOORS FRR* |
≤3 STORIES / >3 STORIES |
1-HR FRR* |
1.5-HRS FRR** |
ENCLOSURES FPR* |
≤3 STORIES / >3 STORIES |
1-HR FPR** |
2-HRS FPR** |
ENCLOSURE EXEMPTION |
PENETRATING ONE FLOOR LEVEL OR SERVING MEZZANINE ONLY |
PERMITTED |
EXPOSURES |
WALLS AND OPENINGS WITHIN 3050MM HORIZONTALLY OF AN EXTERIOR STAIRWAY ENCLOSURE |
1-HR FRR* |
USABLE SPACE |
WITHIN EXIT ENCLOSURE |
NOT PERMITTED |
UNDER STAIRS IN ACCORDANCE WITH NFPA 101 |
PERMITTED |
STAIRWAY IDENTIFICATION |
SERVING 3 OR MORE STOREYS |
REQUIRED |
EXIT STAIR PATH MARKINGS |
ALL STAIR COMPONENTS |
REQUIRED |
PERIMETER DEMARCATION MARKING |
COMPLYING WITH NFPA 101 |
REQUIRED |
LOCK, LATCHES & ALARM DEVICES |
COMPLYING WITH NFPA 101 |
PERMITTED |
RE-ENTRY PROVISIONS |
LOCKED STAIRS EXCEEDING 4 STOREYS |
REQUIRED |
3 |
RAMPS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
PERMITTED |
4 |
INDUSTRIAL EQUIPMENT ACCESS RAMPS / PLATFORMS / WALKWAYS / STAIRS AND DOORS |
COMPLYING WITH THE DIMENSIONAL CRITERIA IN NFPA 101 TABLE 40.2.5.2.1 |
PERMITTED |
5 |
ROOF ACCESS |
BUILDING EQUAL OR MORE THAN 4 STOREYS (G+3) OR ROOFS 12M ABOVE GRADE PLANE |
REQUIRED |
ONE AT EACH 9300 SQM ROOF AREA |
REQUIRED |
FLAT ROOFS OR ROOF PITCHREQUIRED |
STAIRS AS ACCESS WITH OPERABLE DOORS |
REQUIRED |
6 |
SMOKE PROOF ENCLOSURES |
FRR* (FIRE RESISTANCE RATING) |
|
|
STAIR ENCLOSURES |
ALL INSIDE STAIRS SERVING AS AN EXIT COMPONENT |
REQUIRED |
OPEN STAIR PENETRATING ONE (1) FLOOR / LEVEL ONLY |
PERMITTED |
|
FIRE FIGHTING LOBBY (F/F LOBBY) |
IN EVERY FIRE LIFT PROVISIONS |
REQUIRED WHEN FIRE LIFTS PROVIDED |
ADJACENT AND ACCESIBLE TO AN EXIT STAIRCASE |
SERVES AS A COMMON LOBBY FOR BOTH FIRE LIFT AND THE ADJACENT EXIT STAIRCASE |
6 SQM MINIMUM AREA / WORKING SPACE (LEAST SIDE DIMENSION 2.0M) |
PROVISIONS AT THE LEVEL OF EXIT DISCHARGE |
NOT REQUIRED IF EXITS COMPLIES WITH EXIT DISCHARGE REQUIREMENTS |
|
SMOKE-STOP LOBBY (S/S LOBBY) |
HIGH-RISE BUILDINGS WITH HABITABLE HEIGHT HIGHER THAN 28 METERS |
REQUIRED |
BASEMENT LEVEL/S EXCEED 9.0 M DEPTH |
REQUIRED |
BUILDING TRAVERSES MORE THAN FIVE (5) FLOOR LEVELS INCLUDING BASEMENT/S AND BELONGS TO A PLACE OF PUBLIC RESORT (ASSEMBLY & HEALTHCARE OCCUPANCY) REGARDLESS OF THE HABITABLE HEIGHT. |
NOT APPLICABLE |
3 SQM MIN. AREA (LEAST SIDE DIMENSION 1.8M) |
REQUIRED |
PROVISIONS AT THE LEVEL OF EXIT DISCHARGE |
NOT REQUIRED IF EXITS COMPLIES WITH EXIT DISCHARGE REQ'TS |
|
SMOKE-STOP LOBBY AND FIRE FIGHTING LOBBY DOORS AND WALL ENCLOSURES |
1.5-HR FPR** FIRE PROTECTION RATING / 2-HRS FRR* FIRE RESISTANCE RATING |
REQUIRED WHEN LOBBY'S PROVIDED |
7 |
HORIZONTAL EXITS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
PERMITTED |
8 |
EXIT PASSAGEWAYS |
ENCLOSURE AND SEPARATION FIRE RESISTANCE RATING COMPLYING WITH CHAPTER 7 NFPA 101 |
REQUIRED |
MIN. WIDTH NOT LESS THAN 2/3 OF THE WIDTH OF THE EXIT STAIR |
REQUIRED |
8 |
ESCALATORS & MOVING WALKS |
AS PART OF THE REQUIRED MEANS OF EGRESS |
NOT PERMITTED |
9 |
FIRE ESCAPE STAIRS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
PERMITTED |
10 |
FIRE ESCAPE LADDERS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
PERMITTED |
11 |
SLIDE ESCAPES |
COMPLYING WITH CHAPTER 7 NFPA 101 |
PERMITTED |
12 |
ALTERNATING TREAD DEVICES |
COMPLYING WITH CHAPTER 7 NFPA 101 |
PERMITTED |
13 |
AREAS OF REFUGE |
COMPLYING WITH CHAPTER 7 NFPA 101 |
REQUIRED |
14 |
ELEVATORS |
AS PART OF THE REQUIRED MEANS OF EGRESS |
NOT PERMITTED |
AS PER NFPA 101 & ASME A17.1 / CSA B44 |
PERMITTED |
ELEVATOR DOORS |
OPENING INTO EXIT ENCLOSURES |
NOT PERMITTED |
C |
CAPACITY OF MEANS OF EGRESS |
|
1 |
OCCUPANT LOAD |
NFPA 101 TABLE 7.3.1.2 OCCUPANT LOAD FACTOR |
THE MAXIMUM PROBABLE NUMBER OF OCCUPANTS PRESENT AT ANYTIME |
2 |
EGRESS CAPACITY |
NFPA 101 TABLE 7.3.3.1 CAPACITY FACTORS |
REQUIRED |
D |
NUMBER OF EXITS |
COMPLYING WITH NFPA 101 CHAPTER 7 |
|
1 |
SINGLE EXIT |
SERVING ALL FLOOR LEVELS |
NOT LESS THAN 2 EXITS REQUIRED |
IN MEZZANINES OR ANY SECTIONS WITH EXIT TRAVEL WITHIN COMMON PATH LIMIT |
PERMITTED |
ANY STORY OR SECTION WITH EXIT TRAVEL WITHIN COMMON PATH LIMIT |
PERMITTED |
2 |
2 SEPARATE EXITS |
50 - 500 OCCUPANTS |
REQUIRED |
3 |
3 SEPARATE EXITS |
EQUAL OR MORE THAN 500 OCCUPANTS |
REQUIRED |
4 |
4 SEPARATE EXITS |
EQUAL OR MORE THAN 1000 OCCUPANTS |
REQUIRED |
E |
ARRANGEMENT OF EXITS |
NS*-NOT SPRINKLERED / S**-SPRINKLERED |
NS* |
1 |
TRAVEL DISTANCE |
NFPA 101 TABLE 42.2.6 |
NOT LIMITED |
2 |
COMMON PATH LIMIT |
NFPA 101 TABLE 42.2.5 |
NOT LIMITED |
3 |
DEAD-END CORRIDOR |
NFPA 101 TABLE 42.2.5 |
NOT LIMITED |
4 |
EXIT DISCHARGE |
COMPLYING WITH NFPA 101 |
REQUIRED |
5 |
EXTERIOR WAYS OF EXIT |
COMPLYING WITH NFPA 101 |
PERMITTED |
6 |
ACCESIBLE MEANS OF EGRESS |
FOR PEOPLE WITH SEVERE MOBILITY IMPAIRMENT |
2 EXITS REQUIRED |
7 |
ILLUMINATION OF MEANS OF EGRESS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
REQUIRED |
8 |
EMERGENCY LIGHTING |
COMPLYING WITH CHAPTER 7 NFPA 101 |
REQUIRED |
9 |
MARKINGS OF MEANS OF EGRESS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
REQUIRED |
F |
SPECIAL MEANS OF EGRESS PROVISIONS |
|
|
1 |
FIREMEN ACCESS PANELS |
ANY NUMBER OF STORIES |
REQUIRED |
2 |
REFUGE FLOORS |
AT AN INTERVAL OF 20 STORIES |
BUILDINGS EXCEEDING 30 STORIES |
3 |
ELEVATORS FOR OCCUPANT CONTROLLED EVACUATION PRIOR TO PHASE 1 EMERGENCY RECALL OPERATIONS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
PERMITTED |