QCD

Home

BUILDING AND SITE ACCESS FOR FIRE FIGHTING & RESCUE

IIIBUILDING AND SITE ACCESS FOR FIRE FIGHTING & RESCUEVILLAS TO PRIMARY SCH
 FIRE SAFETY PROVISIONSMINIMUM REQUIREMENTS 
A SITE ACCESS 4.0M MINIMUM CLEAR WIDTH & 4.5M MINIMUM CLEAR HEIGHT REQUIRED
B FIRE ENGINE HARDSTANDING HABITABLE HEIGHT EXCEEDS 10M NOT REQUIRED
C FIRE COMMAND CENTER COMPLYING WITH ALL FCC REQUIREMENTS NOT REQUIRED
D FIRE LIFT COMPLYING WITH ALL FIRE LIFT REQUIREMENTS NOT REQUIRED

MEANS OF EGRESS

IVMEANS OF EGRESSVILLAS TO PRIMARY SCHOOL
 FIRE SAFETY PROVISIONSMINIMUM REQUIREMENTS 
A MEANS OF EGRESS GENERAL REQUIREMENTS    
1 GUARDS PROVIDED AT THE OPEN SIDES OF MEANS OF EGRESS 760MM ABOVE THE FLOOR OR FINISHED GROUND LEVEL REQUIRED
2 IMPEDIMENT TO EGRESS & MEANS OF EGRESS RELIABILITY CONTINUOUSLY MAINTAINED FREE OF ALL OBSTRUCTION OR IMPEDIMENTS REQUIRED
3 FURNISHING AND DECORATION FURNITURES, MOVABLE OBJECTS, MIRRORS, ETC. NOT PERMITTED
  ART WORK & TEACHING MATERIALS COVERAGE NOT TO EXCEED 20% OF THE WALL AREA REQUIRED
B MEANS OF EGRESS COMPONENTS    
1 FIRE DOORS FRR* FIRE PROTECTION RATING 1-HR FPR*
SIDE-HINGE OR PIVOTED-SWINGING TYPE ANY DOOR ASSEMBLY IN A MEANS OF EGRESS REQUIRED
MINIMUM DOOR LEAF WIDTH 810MM
SELF-CLOSING DEVICES DOORS REQUIRED TO BE NORMALLY KEPT CLOSED REQUIRED
2 STAIRS COMPLYING WITH CHAPTER 7 NFPA 101  
STANDARD STAIRS FEWER THAN 50 PERSON (CLEAR WIDTH) 915MM
MORE THAN 50 PERSON (CLEAR WIDTH) 1120MM
GUARDS AND HANDRAILS COMPLYING WITH CHAPTER 7 NFPA 101 REQUIRED
STAIRWAY IDENTIFICATION & EXIT STAIR PATH MARKINGS ALL STAIR COMPONENTS REQUIRED
3 STAIR ENCLOSURES ALL INSIDE STAIRS SERVING AS AN EXIT COMPONENT NOT REQUIRED
4 FIRE FIGHTING LOBBY COMPLYING WITH ALL FF LOBBY REQUIREMENTS NOT REQUIRED
5 SMOKE-STOP LOBBY (VESTIBULE) COMPLYING WITH ALL SS LOBBY REQUIREMENTS NOT REQUIRED
6 FIRE ESCAPE STAIRS (EXTERNAL EXIT STAIR) AS SECONDARY MEANS OF EXIT REQUIRED ON ALL UPPER FLOOR LEVELS
C CAPACITY OF MEANS OF EGRESS  
1 OCCUPANT LOAD NFPA 101 TABLE 7.3.1.2 OCCUPANT LOAD FACTOR NOT APPLICABLE
AGES 0-24 MONTHS OLD NOT APPLICABLE
AGES 25-36 MONTHS OLD NOT APPLICABLE
AGES 37-60 MONTHS OLD NOT APPLICABLE
CLASSROOMS 1.9 NET SQM / PERSON
SHOPS & LABORATORIES 4.6 NET SQM / PERSON
D NUMBER OF EXITS    
1 SINGLE EXIT   NOT PERMITTED
2 NOT LESS THAN 2 SEPARATE EXITS PROVIDED ON EVERY STORY REQUIRED
ACCESIBLE FROM EVERY PART OF EVERY STORY
E ARRANGEMENT OF EXITS NS*-NOT SPRINKLERED / S**-SPRINKLERED NS* S**
1 TRAVEL DISTANCE NFPA 1-1 TABLE A.7.6 30M NA
BETWEEN ANY ROOM DOOR INTENDED AS EXIT ACCESS ANS AS AN EXIT NA NA
BETWEEN ANY POINT IN A ROOM TO AN EXIT NA NA
BETWEN ANY POINT IN CHILDRENS SLEEPING ROOM AND AN EXIT ACCESS DOOR IN THAT ROOM NA NA
2 COMMON PATH LIMIT NFPA 101 TABLE A.7.6 23M NA
3 DEAD-END CORRIDOR NFPA 101 TABLE A.7.6 6.1M NA
4 ROOM OR SPACES WITH MORE THAN 93 SQM OR WITH AN OCCUPANT LOAD OF MORE THAN 50 PERSONS MINIMUM TWO (2) ACCESS DOORS REQUIRED
REQUIRED DOORS ACCESS TO SEPARATE EXITS
DOORS OPEN INTO THE DIRECTION OF EXIT TRAVEL
5 EVERY ROOM NORMALLY SUBJECT TO STUDENT OCCUPANCY EXIT ACCESS DOORS LEADS DIRECTLY TO AN EXIT ACCESS CORRIDOR OR EXIT REQUIRED
6 DOORS SWINGING INTO EXIT ACCESS CORRIDOR ARRANGED TO PREVENT INTERFERENCE WITH CORRIDOR TRAVEL REQUIRED
7 AISLES MINIMUM AISLE WIDTH 760MM
8 SPACES (AISLE) BETWEEN PARALLEL ROWS OD SEATS MINIMUM WIDTH 760MM NOT REQUIRED IF THE NUMBER OF SEATS THAT INTERVENES BETWEEN ANY SEAT AND AN AISLE DOES NOT EXCEED SIX (6)
9 EXIT DISCHARGE (DIRECT TO BUILDING EXTERNAL) COMPLYING WITH CHAPTER 7 NFPA 101 REQUIRED
10 ACCESIBLE MEANS OF EGRESS EXIT PROVISIONS FOR PEOPLE WITH SEVERE MOBILITY IMPAIRMENT (NOT LESS THAN 2 EXITS REQUIRED) 2 EXIT REQUIRED
11 ILLUMINATION OF EXITS / EMERGENCY LIGHTING COMPLYING WITH CHAPTER 7 NFPA 101 REQUIRED
12 MARKINGS OF MEANS OF EGRESS COMPLYING WITH CHAPTER 7 NFPA 101 REQUIRED
F SPECIAL MEANS OF EGRESS PROVISIONS    
1 FIREMEN ACCESS PANELS HABITABLE HEIGHT EXCEEDING 10M NOT REQUIRED
2 WINDOWS FOR RESCUE ROOMS OR SPACE GREATER THAN 23.2 SQM AND NORMALLY SUBJECT TO STUDENT OCCUPANCY REQUIRED
3 LOCKUPS DOORS AND PHYSICAL RESTRAINTS TO FREE EGRESS CAN BE READILY RELEASED BY STAFF WITHIN 2 MINUTES OF ONSET OF FIRE OR SIMILAR EMERGENCY REQUIRED ON DOORS PROVIDED WITH LOCKUPS

FEATURES OF FIRE PROTECTION

VFEATURES OF FIRE PROTECTION (NFPA 5000 TABLES 7.2.1.1, 7.3.2.1, 7.3.5 (a), (b), 7.3.5.5, 7.4.1)VILLAS TO PRIMARY SCHOOL
A CONSTRUCTION COMPLYING WITH CHAPTER 7 & 8 OF NFPA 5000  
1 CONSTRUCTION (NON-COMBUSTIBLE OR LIMITED COMBUSTIBLE MATERIALS) TYPE I OR TYPE II EXTERIOR BEARING WALLS 1-HR FRR* FIRE RESISTANCE RATING OF ALL BUILDING ELEMENTS
FRAMING, COLUMNS, BEAMS, GIRDERS, TRUSSES
FLOOR CONSTRUCTION
B COMPARTMENTATION/SUBDIVISION OF BUILDING SPACES COMPLYING WITH NFPA 101 & NFPA 5000 NOT REQUIRED
1 SEPARATION FROM OTHER OCCUPANCIES AS PER NFPA 101 TABLE 6.1.14.4.1 (a), (b) REQUIRED

OPERATING FEATURES

VIIIOPERATING FEATURESVILLAS TO PRIMARY SCHOOL
A EMERGENCY PLAN  
1 EMERGENCY PLAN REQUIREMENTS 1 PROCEDURES FOR REPORTING OF EMERGENCY REQUIRED
2 OCCUPANT AND STAFF RESPONSE TO EMERGENCY
3 EVACUATION PROCEDURES APPROPRIATE TO THE OCCUPANCY, EMERGENCIES AND HAZARD
1 EMERGENCY PLAN REQUIREMENTS (CONTINUED) 4 APPROPRIATENESS OF THE USE OF ELEVATORS REQUIRED
5 DESIGN & CONDUCT OF FIRE DRILLS
6 TYPE & COVERAGE OF OF BUILDING FIRE PROTECTION SYSTEM
7 OTHER ITEMS THAT ARE NECESSARY IN AN EMERGENCY PLANS AS MAY BE REQUIRED BY QCD
B EMERGENCY EXIT DRILLS    
1 EMERGENCY EGRESS AND RELOCATION DRILLS    
  DRILL FREQUENCY NOT LESS THAN 1 PER MONTH REQUIRED
IN SUMMER SEASON OR OTHER SEVERE WEATHER CONDITIONS PERMITTED TO BE DEFERRED
CONDITION NOT LESS THAN 4 DRILLS CONDUCTED BEFORE THE DRILLS ARE DEFFERED
2 ORDERLY EVACUATION EMPHASIS ON ORDERLY EVACUATION RATHER SPEED REQUIRED
3 SIMULATED CONDITIONS DRILLS HELD AT EXPECTED & UNEXPECTED TIMES REQUIRED
4 RELOCATION AREA   REQUIRED
C INSPECTION  
  DUTY OF PRINCIPALS, TEACHER AND STAFF TO INSPECT ALL EXIT FACILITIES TO ENSURE THAT ALL STAIRWAYS, DOORS & OTHER EXITS ARE IN PROPER CONDITION DAILY INSPECTION REQUIRED

FIRE PROTECTION

VIFIRE PROTECTION (FRR* FIRE RESISTANCE RATING / FPR** FIRE PROTECTION RATING)VILLAS TO PRIMARY SCHOOL
A DETECTION ALARM AND COMMUNICATION SYSTEMS    
1 FIRE ALARM SYSTEM AUTOMATIC AND MANUAL SYSTEM REQUIRED
B EXTINGUISHING REQUIREMENTS COMPLIANCE WITH INDIVIDUAL CODES & STANDARDS  
1 PROTABLE FIRE EXTINGUISHERS TYPE AND RATING IN ACCORDANCE WITH NFPA 10 REQUIRED THROUGHOUT
2 FIRE BLANKETS IN KITCHEN OR PANTRY REQUIRED
3 STANDPIPE SYSTEM   NOT REQUIRED
4 FIRE HOSE REELS 25MM DIAMETER HOSE NOT REQUIRED
5 AUTOMATIC SPRINKLER SYSTEM THROUGHOUT PROTECTION NOT REQUIRED

Main Menu