Level of Protection | General Industrial Occupancy | Special-Purpose Industrial Occupancy | High Hazard Industrial Occupancy |
---|---|---|---|
(m) | (m) | (m) | |
Dead-End Corridor |
|||
Protected throughout by an approved, supervised automatic sprinkler system in accordance with 9.7.1.1(1) | 15 | 15 | Prohibited, except as permitted by 7.11.4 |
Not protected throughout by an approved, supervised automatic sprinkler system in accordance with 9.7.1.1(1) | 15 | 15 | Prohibited, except as permitted by 7.11.4 |
Common Path of Travel |
|||
Protected throughout by an approved, supervised automatic sprinkler system in accordance with 9.7.1.1(1) | 30 | 30 | Prohibited, except as permitted by 7.11.4 |
Not protected throughout by an approved, supervised automatic sprinkler system in accordance with 9.7.1.1(1) | 15 | 15 | Prohibited, except as permitted by 7.11.4 |
NL = Not Limited