Level of Protection | General Industrial Occupancy | Special-Purpose Industrial Occupancy | High Hazard Industrial Occupancy |
---|---|---|---|
(m) | (m) | (m) | |
Protected throughout by an approved, supervised automatic sprinkler system in accordance with 9.7.1.1(1) | 76† | 122 | 23 |
Not protected throughout by an approved, supervised automatic sprinkler system in accordance with 9.7.1.1(1) | 61 | 91 | NP |
NP = Not Permitted
†In one-story buildings, a travel distance of 122m is permitted, provided that a performance-based analysis demonstrates that safe egress can be accomplished.