Table 40.2.5

Level of Protection General Industrial Occupancy Special Purpose Industrial Occupancy High Hazard Industrial Occupancy
Dead-End Corridor
Sprinklered 15-m 15-m Prohibited except if permitted by 7.11.4
Not Sprinklered 15-m 15-m Prohibited except if permitted by 7.11.4
Common Path of Travel
Sprinklered 30-m 30-m Prohibited except if permitted by 7.11.4
Not Sprinklered 15-m 15-m Prohibited except if permitted by 7.11.4
Travel Distance
Sprinklered 76-m 122-m 23-m
Not Sprinklered 61-m 91-m Not Permitted