Table 8.3.4.2 Minimum Fire Ratings for Opening Protectives in Fire Resistance–Rated Assemblies and Fire-Rated Glazing Markings

Component Walls and Partitions Fire Door Assemblies Door Vision Panel Maximum Size Fire-Rated Glazing Marking Door Vision Panel Minimum Side Light/Transom Assembly Rating (hr) Fire-Rated Glazing Marking Side Light/Transom Panel Minimum Fire-Rated Windows Rating a,b (hr) Fire-RatedWindowMarking
(hr) (hr) (in.2) Fire protection Fire resistance Fire protection Fire resistance Fire protection Fire resistance Fire protection Fire resistance
Elevator hoistways 2 1-1⁄2 155in.2c D-H-90 or D-H-W-90 NP 2 NP D-H-W-120 NP 2 NP W-120
1 1 155in.2c D-H-60orD-H-W-60 NP 1 NP D-H-W-60 NP 1 NP W-60
1⁄2 1⁄3 85in.2d D-20 or D-W-20 1⁄3 1⁄3 D-H-20 D-W-20 1⁄3 1⁄3 OH-20 W-30
Elevator lobby (per7.2.13.4) 1 1 100in.2a ≤100in.2, D-H-T-60 or D-H-W-60 >100in.2, D-H-W-60 NP 1 NP D-H-W-60 NP 1 NP W-60
Vertical shafts (including stairways, exits and refuse chutes 2 1-1⁄2 Maximum size tested D-H-90 or D-H-W-90 NP 2 NP D-H-W-120 NP 2 NP W-120
1 1 Maximum size tested D-H-60 or D-H-W-60 NP 1 NP D-H-W-60 NP 1 NP W-60
                         
                         

 

ReplacementPanelsinExistingVerticalShafts1⁄21⁄3MaximumsizetestedD-20orD-W-201⁄31⁄3D-H-20D-W-201⁄31⁄3OH-20W-30Firebarriers33100in.2a≤100in.2,D-H-180orD-H-W-180NP3NPD-H-W-180NP3NPW-180>100in.2,D-H-W-18021-1⁄2MaximumsizetestedD-H-90orD-H-W-90NP2NPD-H-W-120NP2NPW-12013⁄4MaximumsizetestedeD-H-45orD-H-W-453⁄4e3⁄4eD-H-45D-H-W-453⁄43⁄4OH-45W-601⁄21⁄3MaximumsizetestedD-20orD-W-201⁄31⁄3D-H-20D-W-201⁄31⁄3OH-20W-30

Horizontalexits21-1⁄2MaximumsizetestedD-H-90orD-H-W-90NP2NPD-H-W-120NP2NPW-120Horizontalexitsservedbybridgesbetweenbuildings23⁄4MaximumsizetestedeD-H-45orD-H-W-453⁄4e3⁄4eD-H-45D-H-W-453⁄43⁄4OH-45W-120Exitaccesscorridorsf11⁄3MaximumsizetestedD-20orD-W-203⁄43⁄4D-H-45D-H-W-203⁄43⁄4OH-45W-601⁄21⁄3MaximumsizetestedD-20orD-W-201⁄31⁄3D-H-20D-H-W-201⁄31⁄3OH-20W-30Smokebarriersf11⁄3MaximumsizetestedD-20orD-W-203⁄43⁄4D-H-45D-H-W-203⁄43⁄4OH-45W-60Smokepartitionsf,g1⁄21⁄3MaximumsizetestedD-20orD-W-201⁄31⁄3D-H-20D-H-W-201⁄31⁄3OH-20W-30ForSIunits,1in.2=0.00064516m2.NP:Notpermitted.aFireresistance–ratedglazingtestedtoASTME119,StandardTestMethodsforFireTestsofBuildingConstructionandMaterials;orANSI/UL263,StandardforFireTestsofBuildingConstructionandMaterials,shallbepermittedinthemaximumsizetested(see8.3.3.7).bFire-ratedglazinginexteriorwindowsshallbemarkedinaccordancewithTable8.3.3.12.cSeeASMEA17.1,SafetyCodeforElevatorsandEscalators,foradditionalinformation.dSeeASMEA17.3,SafetyCodeforExistingElevatorsandEscalators,foradditionalinformation.eMaximumareaofindividualexposedlightsshallbe1296in.2(0.84m2),withnodimensionexceeding54in.(1.37m)unlessotherwisetested.[80:Table4.4.5Noteband80:4.4.5.1].fFiredoorsarenotrequiredtohaveahosestreamtestperANSI/UL10B,Standardfor