Fire Protection

VIIFIRE PROTECTION (NR-NOT REQUIRED / R-REQUIRED)HIGH HAZARD INDUSTRIAL BUILDINGS
A DETECTION ALARM AND COMMUNICATION SYSTEMS    
1 FIRE ALARM SYSTEM COMPLYING WITH NFPA 72 REQUIRED
B EXTINGUISHING REQUIREMENTS    
1 PROTABLE FIRE EXTINGUISHERS TYPE AND RATING IN ACCORDANCE WITH NFPA 10 REQUIRED
2 FIRE BLANKETS IN KITCHEN OR PANTRY REQUIRED
3 STANDPIPE SYSTEM COMPLYING WITH NFPA 14 REQUIRED
4 FIRE HOSE REELS 25MM DIAMETER HOSE REQUIRED
5 AUTOMATIC SPRINKLER SYSTEM   LOW HAZARD ORDINARY
3 OR MORE STORIES IN HEIGHT NR R
FIRE AREA EXCEEDING 1115 SQM NR R
TOTAL AREA OF ALL FLOORS EXCEEDS 2230 SQM NR R
WOODWORKING OPERATIONS EXCEEDING 232 SQM REQUIRED
POWER GENERATION BUILDING REQUIRED
6 OTHER EXTINGUISHING SYSTEM COMPLIANCE FROM INDIVIDUAL CODES & STANDARDS IN LIEAU OF AN AUTOMATIC SUPPRESSION SYSTEM

High Hazard Industrial

HEIGHT & AREA ALLOWED

IN ACCORDANCE WITH NFPA 5000 CHAPTER 7 TABLE 7.4.1 FOR THE ALLOWABLE BUILDING HEIGHT AND AREA REQUIREMENTS


40.1.4.1.3* HIGH HAZARD INDUSTRIAL OCCUPANCY 

INDUSTRIAL OCCUPANCY THAT CONDUCT INDUSTRIAL OPERATIONS THAT USE HIGH HAZARD MATERIALS OR PROCESSES OR HOUSE HIGH HAZARD CONTENTS

INDUSTRIAL OCCUPANCY IN WHICH INCIDENTAL HIGH HAZARD OPERATIONS IN LOW OR ORDINARY HAZARD OCCUPANCY THAT ARE PROTECTED IN ACCORDANCE WITH SECTION 9.7 AND 40.3.2 ARE NOT REQUIRED TO BE THE BASIS FOR OVERALL OCCUPANCY CLASSIFICATION

INDUSTRIAL OCCUPANCY - FACTORY AND WORKSHOPS

AN OCCUPANCY IN WHICH PRODUCTS ARE MANUFACTURED OR IN WHICH PROCESSING, ASSEMBLING, MIXING, PACKAGING, FINISHING, DECORATING, OR REPAIR OPERATIONS ARE CONDUCTED

APPLICATIONS 

DRY CLEANING PLANTS / FACTORIES OF ALL KINDS / FOOD PROCESSING PLANTS / GAS PLANTS / HANGARS (FOR SERVICING/MAINTENANCE) / LAUNDRIES / POWER PLANTS / PUMPING STATIONS / REFINERIES / SAWMILLS / TELEPHONE EXCHANGES