IIIBUILDING AND SITE ACCESS FOR FIRE FIGHTING & RESCUEHIGH HAZARD INDUSTRIAL BUILDINGS
   LOW HAZARD ORDINARY HAZARD
A SITE ACCESS 4.0M MINIMUM CLEAR WIDTH & 4.5M MIN. CLEAR HEIGHT REQUIRED
B ACCESS ROAD 4.0M MIN. WIDTH AND 24 TON LOAD CAPACITY REQUIRED
WITHIN A TRAVEL DISTANCE OF 45M FROM EVERY POINT ON PROJECTED PLAN AREA OF ANY BUILDING.
C FIRE ENGINE HARDSTANDING LENGTH OR NUMBER BASE ON THE GROSS FLOOR AREA OF THE BUILDING REQUIRED
6M X 15M (MINIMUM), WITH LONGER SIDE PARALLEL TO THE FACADE OF THE BUILDING
POSITIONED SO THAT THE NEARER EDGE SHALL BE NOT LESS THAN 2M OR NOT MORE THAN 10M FROM THE CENTER POSITION OF THE ACCESS OPENING, MEASURED HORIZONTALLY. REQUIRED
D FIRE COMMAND CENTER OTHER THAN HIGH-RISE WITH EMERGENCY VOICE COMMUNICATION SYSTEM AND/OR SMOKE CONTROL SYSTEM REQUIRED
9 SQM MINIMUM FLOOR AREA (LEAST DIMENSION 2.5M)
E FIRE LIFT COMPLYING WITH ALL FIRE LIFTS REQUIREMENTS TO COMPLY WITH REQUIREMENTS WHEN PROVIDED AS REQUIRED

High Hazard Industrial

HEIGHT & AREA ALLOWED

IN ACCORDANCE WITH NFPA 5000 CHAPTER 7 TABLE 7.4.1 FOR THE ALLOWABLE BUILDING HEIGHT AND AREA REQUIREMENTS


40.1.4.1.3* HIGH HAZARD INDUSTRIAL OCCUPANCY 

INDUSTRIAL OCCUPANCY THAT CONDUCT INDUSTRIAL OPERATIONS THAT USE HIGH HAZARD MATERIALS OR PROCESSES OR HOUSE HIGH HAZARD CONTENTS

INDUSTRIAL OCCUPANCY IN WHICH INCIDENTAL HIGH HAZARD OPERATIONS IN LOW OR ORDINARY HAZARD OCCUPANCY THAT ARE PROTECTED IN ACCORDANCE WITH SECTION 9.7 AND 40.3.2 ARE NOT REQUIRED TO BE THE BASIS FOR OVERALL OCCUPANCY CLASSIFICATION

INDUSTRIAL OCCUPANCY - FACTORY AND WORKSHOPS

AN OCCUPANCY IN WHICH PRODUCTS ARE MANUFACTURED OR IN WHICH PROCESSING, ASSEMBLING, MIXING, PACKAGING, FINISHING, DECORATING, OR REPAIR OPERATIONS ARE CONDUCTED

APPLICATIONS 

DRY CLEANING PLANTS / FACTORIES OF ALL KINDS / FOOD PROCESSING PLANTS / GAS PLANTS / HANGARS (FOR SERVICING/MAINTENANCE) / LAUNDRIES / POWER PLANTS / PUMPING STATIONS / REFINERIES / SAWMILLS / TELEPHONE EXCHANGES