VIIFIRE PROTECTION (FRR* FIRE RESISTANCE RATING / FPR** FIRE PROTECTION RATING)MEDIUM-RISE HOTEL
A DETECTION ALARM AND COMMUNICATION SYSTEMS    
1 FIRE ALARM SYSTEM COMPLYING WITH NFPA 72 REQUIRED
  CARBON MONOXIDE ALARMS AND DETECTION SYSTEM GUEST ROOM/SUITES WITH COMMUNICATING ATTACHED GARAGE REQUIRED
GUEST ROOM/SUITES CONTAINING A PERMANENTLY INSTALLED FUEL-BURNING APPLIANCE REQUIRED
IN GARAGE NOT REQUIRED
GUEST ROOMS/SUITES WITH COMMUNICATING ATTACHED GARAGE THAT ARE CONSIDERED AS OPEN PARKING STRUCTURE NOT REQUIRED
GUEST ROOMS/SUITES WITH COMMUNICATING ATTACHED GARAGE THAT ARE MECHANICALLY VENTILATED NOT REQUIRED
B EXTINGUISHING REQUIREMENTS COMPLIANCE WITH INDIVIDUAL CODES & STANDARDS REQUIRED
1 PROTABLE FIRE EXTINGUISHERS TYPE AND RATING IN ACCORDANCE WITH NFPA 10 REQUIRED
2 FIRE BLANKETS IN KITCHEN OR PANTRY REQUIRED
3 STANDPIPE SYSTEM BUILDING EXCEEDING 9M IN HABITABLE HEIGHT REQUIRED
4 FIRE HOSE REELS 25MM DIAMETER HOSE REQUIRED
5 AUTOMATIC SPRINKLER SYSTEM THROUGHOUT PROTECTION REQUIRED
WITH GUEST ROOMS OR GUEST SUITES HAVING A DOOR OPENING DIRECTLY OUTSIDE AT THE STREET LEVEL NOT APPLICABLE
WITH GUEST ROOMS OR GUEST SUITES HAVING AN EXTERIOR ACCESS COMPLYING WITH CHAPTER 7 OF NFPA 101 NOT APPLICABLE
PROVIDED IN LIEAU OF THE REQUIRED DRAFTSTOPS IN CONCEALED SPACES PERMITTED
ONE BASEMENT LEVEL USED AS CARPARK ONLY (WITH FLOOR AREA EXCEEDING 1115 SQM) REQUIRED
ONE BASEMENT LEVEL USED AS MIXED OCCUPANCY REQUIRED
BUILDING HAS MORE THAN ONE BASEMENT LEVEL REQUIRED
6 OTHER EXTINGUISHING EQUIPMENT COMPLIANCE FROM INDIVIDUAL NFPA CODES & STANDARDS NOT REQUIRED

Medium rise Hotel

HEIGHT & AREA ALLOWED

Height : > 15m to < 28m

Area : > 500 sqm - < 1000sqm


HOTEL BUILDINGS

A BUILDING OR GROUP OF BUILDINGS UNDER THE SAME MANAGEMENT IN WHICH THERE ARE SLEEPING ACCOMMODATIONS FOR MORE THAN 16 PERSONS AND PRIMARILY USED BY TRANSIENTS FOR LODGING WITH OR WITHOUT MEALS (AND WITH NO COOKING FACILITIES)