VII | FIRE PROTECTION (FRR* FIRE RESISTANCE RATING / FPR** FIRE PROTECTION RATING) | MEDIUM-RISE HOTEL | |
---|---|---|---|
A | DETECTION ALARM AND COMMUNICATION SYSTEMS | ||
1 | FIRE ALARM SYSTEM | COMPLYING WITH NFPA 72 | REQUIRED |
CARBON MONOXIDE ALARMS AND DETECTION SYSTEM | GUEST ROOM/SUITES WITH COMMUNICATING ATTACHED GARAGE | REQUIRED | |
GUEST ROOM/SUITES CONTAINING A PERMANENTLY INSTALLED FUEL-BURNING APPLIANCE | REQUIRED | ||
IN GARAGE | NOT REQUIRED | ||
GUEST ROOMS/SUITES WITH COMMUNICATING ATTACHED GARAGE THAT ARE CONSIDERED AS OPEN PARKING STRUCTURE | NOT REQUIRED | ||
GUEST ROOMS/SUITES WITH COMMUNICATING ATTACHED GARAGE THAT ARE MECHANICALLY VENTILATED | NOT REQUIRED | ||
B | EXTINGUISHING REQUIREMENTS | COMPLIANCE WITH INDIVIDUAL CODES & STANDARDS | REQUIRED |
1 | PROTABLE FIRE EXTINGUISHERS | TYPE AND RATING IN ACCORDANCE WITH NFPA 10 | REQUIRED |
2 | FIRE BLANKETS | IN KITCHEN OR PANTRY | REQUIRED |
3 | STANDPIPE SYSTEM | BUILDING EXCEEDING 9M IN HABITABLE HEIGHT | REQUIRED |
4 | FIRE HOSE REELS | 25MM DIAMETER HOSE | REQUIRED |
5 | AUTOMATIC SPRINKLER SYSTEM | THROUGHOUT PROTECTION | REQUIRED |
WITH GUEST ROOMS OR GUEST SUITES HAVING A DOOR OPENING DIRECTLY OUTSIDE AT THE STREET LEVEL | NOT APPLICABLE | ||
WITH GUEST ROOMS OR GUEST SUITES HAVING AN EXTERIOR ACCESS COMPLYING WITH CHAPTER 7 OF NFPA 101 | NOT APPLICABLE | ||
PROVIDED IN LIEAU OF THE REQUIRED DRAFTSTOPS IN CONCEALED SPACES | PERMITTED | ||
ONE BASEMENT LEVEL USED AS CARPARK ONLY (WITH FLOOR AREA EXCEEDING 1115 SQM) | REQUIRED | ||
ONE BASEMENT LEVEL USED AS MIXED OCCUPANCY | REQUIRED | ||
BUILDING HAS MORE THAN ONE BASEMENT LEVEL | REQUIRED | ||
6 | OTHER EXTINGUISHING EQUIPMENT | COMPLIANCE FROM INDIVIDUAL NFPA CODES & STANDARDS | NOT REQUIRED |
HEIGHT & AREA ALLOWED
Height : > 15m to < 28m
Area : > 500 sqm - < 1000sqm
HOTEL BUILDINGS
A BUILDING OR GROUP OF BUILDINGS UNDER THE SAME MANAGEMENT IN WHICH THERE ARE SLEEPING ACCOMMODATIONS FOR MORE THAN 16 PERSONS AND PRIMARILY USED BY TRANSIENTS FOR LODGING WITH OR WITHOUT MEALS (AND WITH NO COOKING FACILITIES)