QCD

BUILDING SERVICES PROTECTION

VIIIBUILDING SERVICES PROTECTION (ASS* AUTOMATIC SUPPRESSION SYSTEM)HIGH-RISE APARTMENT
A BUILDING UTILITIES COMPLYING WITH CHAPTER 9 NFPA 101 REQUIRED
1 GAS EQUIPMENT & RELATED PIPING PROTECTION AS PER NFPA 54 & NFPA 58 REQUIRED
2 ELECTRICAL SYSTEMS COMPLYING WITH NFPA 70 REQUIRED
  ELECTRICAL EQUIPMENT ROOMS AUTOMATIC SUPPRESSION SYSTEM OR 2-HOURS ENCLOSURE REQUIRED
  SUBSTATION & SWITHGEARS ATTACHED TO OCCUPIED BUILDINGS REQUIRED PROTECTION 3-HOURS FRR* or 2-HRS FRR & ASS*
STANDALONE TRANSFORMER VAULT REQUIRED PROTECTION 3-HOURS FRR* or 1-HOUR FRR* & ASS
EXPLOSION PROTECTION (ENCLOSURES) ASS* & 2-HOURS FRR*
3 COMMERCIAL COOKING EQUIPMENT COMPLYING WITH NFPA 96 NOT APPLICABLE
  KITCHEN/PANTRY ENCLOSURES - FIRE RESISTANCE RATING (FRR*) NOT REQUIRED
  COOKING EQUIPMENT EQUIPMENT USED ONLY FOR FOOR WARMING NOT APPLICABLE
4 ELEVATORS, ESCALATORS & CONVEYORS COMPLYING WITH ASME A17.1/CSA B44 REQUIRED
  FIRE FIGHTERS' EMERGENCY OPERATION COMPLYING WITH CHAPTER 9 NFPA 101 & ASME A17.1/CSA B44 REQUIRED
B RUBBISH CHUTE, INCINERATORS & LAUNDRY CHUTES COMPLYING WITH NFPA 82 REQUIRED
  ENCLOSURES TRAVERSES EQUAL OR LESS THAN 3 STOREYS 1-HOUR FRR*
TRAVERSES MORE THAN 3 STOREYS 2-HOURS FRR*
  OPENING PROTECTIVE TRAVERSES EQUAL OR LESS THAN 3 STOREYS 1-HOUR FPR**
TRAVERSES MORE THAN 3 STOREYS 1.5-HOURS FPR**
C EMERGENCY POWER SUPPLY SYSTEM COMPLYING WITH NFPA 110 REQUIRED
1 GENERATORS ENCLOSURE 1-HOUR FRR*
D FIRE PUMP ROOM COMPLYING WITH NFPA 20 REQUIRED
  ENCLOSURES MORE THAN 15.3 M FROM ANY BUILDING 1-HOUR FRR*
WITHIN 15.3 M OR ATTACHED TO BUILDINGS 2-HOURS FRR*
THROUGHOUT SPRINKLER (BUILDING/S & PUMP ROOM) 1-HOUR FRR*
  DIRECT SAFE ACCESS EXTERNAL ACCESS WITHIN THE LEVEL OF DISCHARGE REQUIRED
WITHIN 3M FROM ANY EXIT THAT COMPLIES WITH DIRECT DISCHARGE REQUIREMENTS PERMITTED
  ACCESS COMPONENT (UNDERGROUND LOCATION) STANDARD STAIR (NON-COMBUSTIBLE MATERIAL) REQUIRED
CAT STEEL LADDER NOT PERMITTED
E FIRE WATER TANKS COMPLYING WITH NFPA 22 REQUIRED
  WATER TANK MATERIALS NON-COMBUSTIBLE MATERIAL REQUIRED
GRP TANKS (WITHIN 1-HR FIRE RATED ENCLOSURE) PERMITTED
  DESIGN/COMPARTMENTATION TWO (2) COMPARTMENTS REQUIRED
F SMOKE CONTROL / EMERGENCY VENTILATION COMPLYING WITH NFPA 92 & NFPA 204 REQUIRED
1 VENTILATION BY ANY OF THE FOLLOWING; a. NATURAL VENTILATION; b. MECHANICAL VENTILATION BY POSITIVE VENTILATION (PRESSURIZATION) SYSTEM EXIT STAIRCASES CONNECTS MORE THAN FIVE (5) STOREYS (LEVELS) INCLUDING BASEMENT/S REQUIRED
AND/OR WHEN SMOKE-STOP &/OR FIRE FIGHTING LOBBIES ARE REQUIRED REQUIRED
2 VENTILATION BY ANY OF THE FOLLOWING; a. NATURAL VENTILATION; b. MECHANICAL VENTILATION & SMOKE CONTROL SYSTEM BASEMENT LEVEL/S WITH FLOOR AREA (FA) EXCEEDING 500 SQM REQUIRED
VERTICAL OPENINGS, ATRIUMS & OTHER LARGE VOLUME OF SPACES REQUIRED
G AIR-CONDITIONING & VENTILATION SYSTEM COMPLYING WITH NFPA 90A & NFPA 90B AND OTHER RELEVANT, APPLICABLE NFPA CODES & STANDARDS REQUIRED

FIRE PROTECTION

VIIFIRE PROTECTION (FRR* FIRE RESISTANCE RATING / FPR** FIRE PROTECTION RATING)HIGH-RISE APARTMENT
A DETECTION ALARM AND COMMUNICATION SYSTEMS    
1 FIRE ALARM SYSTEM *INCLUDE REQUIREMENTS FOR CARBON MONOXIDE ALARMS & CARBON MONOXIDE DETECTION SYSTEM AS NFPA 101 2012 & NFPA 72 REQUIRED
B EXTINGUISHING REQUIREMENTS COMPLIANCE WITH INDIVIDUAL CODES & STANDARDS REQUIRED
1 PROTABLE FIRE EXTINGUISHERS TYPE AND RATING IN ACCORDANCE WITH NFPA 10 REQUIRED
2 FIRE BLANKETS IN KITCHEN OR PANTRY REQUIRED
3 STANDPIPE SYSTEM BUILDING EXCEEDING 9M IN HABITABLE HEIGHT REQUIRED
4 FIRE HOSE REELS 25MM DIAMETER HOSE REQUIRED
5 AUTOMATIC SPRINKLER SYSTEM THROUGHOUT PROTECTION REQUIRED
PROVIDED IN LIAEU OF THE REQUIRED DRAFTSTOPS IN CONCEALED SPACES PERMITTED
ONE BASEMENT LEVEL USED AS CARPARK ONLY (WITH FLOOR AREA EXCEEDING 1115 SQM) REQUIRED
ONE BASEMENT LEVEL USED AS MIXED OCCUPANCY REQUIRED
MORE THAN ONE BASEMENT LEVEL REQUIRED
6 OTHER EXTINGUISHING EQUIPMENT COMPLIANCE FROM INDIVIDUAL NFPA CODES & STANDARDS NOT REQUIRED

INTERIOR FINISH CONTENTS AND FURNISHING

VINTERIOR FINISH CONTENTS AND FURNISHINGHIGH-RISE APARTMENT
A INTERIOR FINISH COMPLYING WITH CHAPTER 10 OF NFPA 101 REQUIRED
1 INTERIOR WALL & CEILING FINISHES EXIT ENCLOSURES CLASS A
LOBBIES & CORRIDORS CLASS A OR CLASS B
OTHER SPACES CLASS A, CLASS B OR CLASS C
2 INTERIOR FLOOR FINISHES EXIT ENCLOSURES, EXIT ACCESS CORRIDORS AND SPACES NOT SEPARATED FROM THEM CLASS II

FEATURES OF FIRE PROTECTION

VIFEATURES OF FIRE PROTECTION (NFPA 5000 TABLES 7.2.1.1, 7.3.2.1, 7.3.5 (a), (b), 7.3.5.5, 7.4.1)HIGH-RISE APARTMENT
A CONSTRUCTION COMPLYING WITH CHAPTER 7 & 8 OF NFPA 5000 REQUIRED
1 CONSTRUCTION (NON-COMBUSTIBLE OR LIMITED COMBUSTIBLE MATERIALS) TYPE I OR TYPE II EXTERIOR BEARING WALLS HOURLY RATINGS REQUIRED PER TYPE OF CONSTRUCTION BASED ON NFPA 5000 HEIGHT & AREA REQUIREMENTS
FRAMING, COLUMNS, BEAMS, GIRDERS, TRUSSES
FLOOR CONSTRUCTION
B SUBDIVISION OF BUILDING SPACES COMPLYING WITH NFPA 101 & NFPA 5000 REQUIRED
1 FIRE BARRIERS COMPLYING WITH NFPA 101 & NFPA 5000 REQUIRED
2 SEPARATION FROM OTHER OCCUPANCIES AS PER NFPA 101 TABLE 6.1.14.4.1 (a), (b) REQUIRED
3 CORRIDORS RATED SEPARATION COMPLYING WITH NFPA 101.30 &31  
  REQUIRED SEPARATION NOT SPRINKLERED 1-HR FRR*
SPRINKLERED 0.5-HR FRR*
  DOORS OPENING ONTO EXIT ACCES CORRIDORS 20-MIN FPR*
4 SMOKE PARTITIONS COMPLYING WITH NFPA 101 & NFPA 5000 NOT REQUIRED
5 SMOKE BARRIERS COMPLYING WITH NFPA 101 & NFPA 5000 NOT REQUIRED
C VERTICAL OPENINGS PROTECTION PROTECTION COMPLYING WITH NFPA CODES REQUIRED
1 COMMUNICATING SPACES COMPLYING WITH CHAPTER 8 NFPA 101 PERMITTED
2 ATRIUMS COMPLYING WITH CHAPTER 8 NFPA 101 PERMITTED
3 CONVENIENCE OPENINGS COMPLYING WITH CHAPTER 8 NFPA 101 PERMITTED
4 SHAFTS COMPLYING WITH CHAPTER 8 NFPA 101 PERMITTED
5 MEZZANINES COMPLYING WITH CHAPTER 8 NFPA 101 PERMITTED
6 CONCEALED SPACES & DRAFTSTOPS COMPLYING WITH CHAPTER 8 NFPA 101 REQUIRED
  EXTERIOR & INTERIOR WALL & PARTITION FIRE STOPPED AT EACH LEVEL, TOP STORY CEILING LEVEL & AT THE LEVEL OF SUPPORT FOR ROOFS REQUIRED
  UNOCCUPIED ATTIC SPACES DRAFTSTOPS INTO AREAS NOT EXCEEDING 280 SQM REQUIRED
  CONCEALED SPACES (CEILINGS & FLOORS) DRAFTSTOPS INTO AREAS NOT EXCEEDING 93 SQM REQUIRED
  CONCEALED SPACES (FLOORS & ROOFS) DRAFTSTOPS INTO AREAS NOT EXCEEDING 280 SQM REQUIRED

MEANS OF EGRESS

IVMEANS OF EGRESSHIGH-RISE APARTMENT
A MEANS OF EGRESS GENERAL REQUIREMENTS  
1 SEPARATION OF MEANS OF EGRESS COMPLYING WITH CHAPTER 7 NFPA 101 REQUIRED
  EXIT ACCESS CORRIDORS SERVING AN AREA HAVING AN OCCUPANT LOAD EXCEEDING 30 1-HR FRR*
  EXITS CONNECTS 3 OR FEWER STORIES 1-HR FRR*
CONNECTS 4 OR MORE STORIES 2-HRS FRR*
  OPENING PROTECTIVE FIRE DOOR ASSEMBLIES EQUIPPED WITH DOOR CLOSERS REQUIRED
  CONSTRUCTION LIMITED OR NON-COMBUSTIBLE MATERIALS REQUIRED
  OPENINGS AND PENETRATIONS IN EXIT ENCLOSURE COMPLYING WITH CHAPTER 7 NFPA 101 PERMITTED
2 EXITS HEADROOM NOT LESS THAN 2285MM REQUIRED
  HEADROOM ON STAIRS NOT LESS TAHN 2285MM REQUIRED
3 WALKING SURFACES IN THE MEANS OF EGRESS COMPLYING WITH CHAPTER 7 NFPA 101 REQUIRED
4 CHANGES IN LEVEL IN THE MEANS OF EGRESS COMPLYING WITH CHAPTER 7 NFPA 101 REQUIRED
5 GUARDS PROVIDED AT THE OPEN SIDES OF MEANS OF EGRESS 760MM ABOVE THE FLOOR OR FINISHED GROUND LEVEL REQUIRED
6 IMPEDIMENT TO EGRESS   NOT PERMITTED
7 MEANS OF EGRESS RELIABILITY CONTINUOUSLY MAINTAINED FREE OF ALL OBSTRUCTION OR IMPEDIMENTS REQUIRED
  FURNISHING AND DECORATION FURNITURES, MOVABLE OBJECTS, MIRRORS, ETC. NOT PERMITTED
B MEANS OF EGRESS COMPONENTS    
1 FIRE DOORS COMPLYING WITH CHAPTER 7 NFPA 101 REQUIRED
SIDE-HINGE OR PIVOTED-SWINGING TYPE ANY DOOR ASSEMBLY IN A MEANS OF EGRESS REQUIRED
MINIMUM DOOR LEAF WIDTH 810MM
HORIZONTAL SLIDING DOORS COMPLYING WITH CHAPTER 7 NFPA 101 (NP) ACROSS CORRIDORS
VERTICAL ROLLING DOORS COMPLYING WITH CHAPTER 7 NFPA 101 NOT PERMITTED
REVOLVING DOOR / POWERED DOORS COMPLYING WITH CHAPTER 7 NFPA 101 PERMITTED
SELF-CLOSING DEVICES DOORS REQUIRED TO BE NORMALLY KEPT CLOSED REQUIRED
2 STAIRS COMPLYING WITH CHAPTER 7 NFPA 101 REQUIRED
STANDARD STAIRS FEWER THAN 50 PERSON (CLEAR WIDTH) 915MM
1120MM
>2000 PERSON (CLEAR WIDTH) 1420MM
SPIRAL STAIRS COMPLYING WITH CHAPTER 7 NFPA 101 PERMITTED ONLY WITHIN A SINGLE DWELLING UNIT
CURVE STAIRS COMPLYING WITH CHAPTER 7 NFPA 101 NOT PERMITTED
WINDERS COMPLYING WITH CHAPTER 7 NFPA 101 PERMITTED
GUARDS AND HANDRAILS COMPLYING WITH CHAPTER 7 NFPA 101 REQUIRED
ENCLOSURE AND PROTECTION OF STAIRS COMPLYING WITH CHAPTER 7 NFPA 101 REQUIRED
ENCLOSURES ALL INSIDE STAIR SERVING AS AN EXIT COMPONENT REQUIRED
DOORS FPR* < 3 STOREYS / > 3 STOREYS 1-HR FPR**/2-HRS FPR**
ENCLOSURES FRR* < 3 STOREYS / > 3 STOREYS 1-HR FRR**/2-HRS FRR*
ENCLOSURE EXEMPTION PENETRATING ONE FLOOR LEVEL OR SERVING MEZZANINE ONLY PERMITTED
EXPOSURES WALLS AND OPENINGS WITHIN 3050MM HORIZONTALLY OF AN EXTERIOR STAIRWAY ENCLOSURE 1-HR FRR*
USABLE SPACE WITHIN EXIT ENCLOSURE NOT PERMITTED
LOCATION UNDER STAIRS IN ACCORDANCE WITH NFPA 101 NOT PERMITTED
STAIRWAY IDENTIFICATION SERVING 3 OR MORE STOREYS REQUIRED
EXIT STAIR PATH MARKINGS ALL STAIR COMPONENTS REQUIRED
PERIMETER DEMARCATION MARKING COMPLYING WITH NFPA 101 REQUIRED
LOCK, LATCHES & ALARM DEVICES COMPLYING WITH NFPA 101 PERMITTED
RE-ENTRY PROVISIONS LOCKED STAIRS EXCEEDING 4 STOREYS REQUIRED
3 RAMPS COMPLYING WITH CHAPTER 7 NFPA 101 PERMITTED
AS SECONDARY EXIT FOR ONE (1) BASEMENT LEVEL PERMITTED
4 ROOF ACCESS BUILDING EQUAL OR MORE THAN 4 STOREYS (G+3) OR ROOFS 12M ABOVE GRADE PLANE REQUIRED
WHERE OPEN STAIR/S ARE PERMITTED NOT APPLICABLE
ONE AT EACH 9300 SQM ROOF AREA OR FLAT ROOFS OR ROOF PITCHREQUIRED
ROOF ACCESS COMPONENTS SMOKE VENTS (FIXED WALL OPENING/S) AT THE TOP OF THE STAIRWELL WITH A MINIMUM AREA OF 1.5 SQM NOT APPLICABLE
STAIR ACCESS TO ROOF EQUIPPED WITH OPERABLE DOORS REQUIRED
5 SMOKE PROOF ENCLOSURES FRR* (FIRE RESISTANCE RATING)  
STAIR ENCLOSURES INTERIOR STAIRS SERVING AS AN EXIT COMPONENT REQUIRED
OPEN STAIR PENETRATING ONE (1) FLOOR / LEVEL ONLY NOT PERMITTED
FIRE FIGHTING LOBBY (F/F LOBBY) IN EVERY FIRE LIFT PROVISIONS REQUIRED IN EVERY FIRE LIFT PROVISIONS
ADJACENT AND ACCESSIBLE TO AN EXIT STAIRCASE
SERVES AS A COMMON LOBBY FOR BOTH FIRE LIFT AND THE ADJACENT EXIT STAIRCASE
6 SQM MINIMUM AREA / WORKING SPACE (LEAST SIDE DIMENSION 2.0M)
PROVISIONS AT THE LEVEL OF EXIT DISCHARGE NOT REQUIRED IF EXITS COMPLIES WITH EXIT DISCHARGE REQUIREMENTS
F/F LOBBY DOORS & WALL ENCLOSURES 1.5-HR FPR** FIRE PROTECTION RATING/ FRR* 2-HRS FIRE RESISTANCE RATING REQUIRED
SMOKE-STOP LOBBY (S/S LOBBY) HIGH-RISE BUILDINGS WITH HABITABLE HEIGHT HIGHER THAN 28 METERS REQUIRED
BASEMENT LEVEL/S EXCEED 9.0 M DEPTH REQUIRED ON ALL FLOOR LEVELS
BUILDING TRAVERSES MORE THAN FIVE (5) FLOOR LEVELS INCLUDING BASEMENT/S AND BELONGS TO A PLACE OF PUBLIC RESORT (ASSEMBLY & HEALTHCARE OCCUPANCY) REGARDLESS OF THE HABITABLE HEIGHT. NOT APPLICABLE
3 SQM MIN. AREA (LEAST SIDE DIMENSION 1.8M) REQUIRED
PROVISIONS AT THE LEVEL OF EXIT DISCHARGE NOT REQUIRED IF EXITS COMPLIES WITH EXIT DISCHARGE REQUIREMENTS
  S/S LOBBY DOORS & WALL ENCLOSURES 1.5-HR FPR** FIRE PROTECTION RATING/ FRR* 2-HRS FIRE RESISTANCE RATING REQUIRED
6 HORIZONTAL EXITS COMPLYING WITH CHAPTER 7 NFPA 101 PERMITTED
7 EXIT PASSAGEWAYS ENCLOSURE AND SEPARATION FIRE RESISTANCE RATING COMPLYING WITH CHAPTER 7 NFPA 101 REQUIRED 1-HR FRR*
MIN. WIDTH NOT LESS THAN 2/3 OF THE WIDTH OF THE EXIT STAIR REQUIRED
8 ESCALATORS & MOVING WALKS AS PART OF THE REQUIRED MEANS OF EGRESS NOT PERMITTED
9 FIRE ESCAPE STAIRS COMPLYING WITH CHAPTER 7 NFPA 101 PERMITTED
10 FIRE ESCAPE LADDERS COMPLYING WITH CHAPTER 7 NFPA 101 NOT PERMITTED
11 SLIDE ESCAPES COMPLYING WITH CHAPTER 7 NFPA 101 PERMITTED
12 ALTERNATING TREAD DEVICES COMPLYING WITH CHAPTER 7 NFPA 101 NOT PERMITTED
13 AREAS OF REFUGE COMPLYING WITH CHAPTER 7 NFPA 101 REQUIRED
14 ELEVATORS AS PART OF THE REQUIRED MEANS OF EGRESS NOT PERMITTED
AS SECOND MEANS OF EGRESS FROM A TOWER AND COMPLYING WITH ASME A17.1/CSA B44 NOT APPLICABLE
ELEVATOR DOORS OPENING INTO EXIT ENCLOSURES NOT PERMITTED
C CAPACITY OF MEANS OF EGRESS  
1 OCCUPANT LOAD NFPA 101 TABLE 7.3.1.2 OCCUPANT LOAD FACTOR 18.6 SQM / PERSON
2 EGRESS CAPACITY NFPA 101 TABLE 7.3.3.1 CAPACITY FACTORS REQUIRED
D NUMBER OF EXITS COMPLYING WITH NFPA 101 CHAPTER 7  
1 SINGLE EXIT SERVING ALL FLOOR LEVELS NOT PERMITTED
IN MEZZANINES WITH EXIT TRAVEL WITHIN COMMON PATH LIMIT PERMITTED
IN ANY SECTION WITH EXIT TRAVEL WITHIN COMMON PATH LIMIT PERMITTED
DWELLING UNIT HAS AN EXIT DOOR OPENING DIRECTLY TO A STREET OR YARD AT FINISHED GROUND LEVEL NOT APPLICABLE
DWELLING UNIT HAS DIRECT ACCESS TO OUTSIDE STAIR AND SERVES A MAX. OF 2 UNITS BOTH OF WHICH ARE LOCATED ON THE SAME FLOOR LEVEL NOT APPLICABLE
DWELLING UNIT HAS DIRECT ACCESS TO AN INSIDE STAIR SERVING ONLY THAT UNIT AND SEPARATED FROM OTHER PARTS OF THE BUILDING WITH 1-HR FIRE BARRIERS NOT APPLICABLE
CONDITIONS * PERMITTING SINGLE EXIT PROVISIONS (REQUIRES COMPLIANCE TO ALL STATED CONDITIONS) 1 LARGEST FLOOR AREA IS EQUAL OR LESS THAN 500 SQM NOT APPLICABLE
2 TRAVEL DISTANCE FROM THE ENTRANCE DOOR OF ANY DWELLING UNIT TO AN EXIT DOES NOT EXCEED 10.7M. NOT APPLICABLE
3 EXIT STAIRWAY IS COMPLETELY ENCLOSED OR SEPARATED FROM THE REST OF THE BUILDING NOT APPLICABLE
4 STAIRWAY SERVE ONLY ONE (1) BASEMENT LEVEL ONLY NOT APPLICABLE
5 ALL OPENINGS BETWEEN THE EXIT ENCLOSURE AND THE BUILDING ARE PROTECTED WITH SELF-CLOSING DOOR ASSEMBLIES OF 1-HOUR FPR** NOT APPLICABLE
6 ALL CORRIDORS SERVING AS ACCESS TO EXITS HAVE A MINIMUM OF 1-HOUR FRR* NOT APPLICABLE
7 HORIZONTAL & VERTICAL SEPARATION OF 1.0-HR FRR* IS PROVIDED BETWEEN DWELLING UNITS NOT APPLICABLE
8 PROVIDED WITH SMOKE VENTS (FIXED WALL OPENING/S) THE TOP OF THE STAIRWELL (MAXIMUM 300MM BELOW SLAB SOFFIT/CEILING) WITH A MINIMUM AREA OF 1.5 SQM, OR NOT APPLICABLE
9 FOR BUILDING/S THAT TRAVERSES MORE THAN FIVE (5) STORIES INCLUDING BASEMENTS, THE EXIT STAIRCASE IS PRESSURIZED. REQUIRED
2 NOT LESS THAN 2 SEPARATE EXITS 50 - 500 OCCUPANTS REQUIRED
ON EVERY STORY AND ACCESSIBLE FROM EVERY PART OF EVERY STORY REQUIRED
3 NOT LESS THAN THREE (3) SEPARATE EXITS EQUAL OR MORE THAN 500 OCCUPANTS REQUIRED
4 NOT LESS THAN FOUR (4) SEPARATE EXITS EQUAL OR MORE THAN 1000 OCCUPANTS REQUIRED
E ARRANGEMENT OF EXITS NS*-NOT SPRINKLERED / S**-SPRINKLERED NS* S**
1 TRAVEL DISTANCE NFPA 101 TABLE A.7.6 WITHIN DWELLING UNIT TO CORRIDOR DOOR 23M 38M
FROM DWELLING UNIT ENTRANCE DOOR TO THE NEAREST EXIT 30M 61M
FROM A DWELLING UNIT ENTRANCE DOOR TO THE NEAREST EXIT FOR EXTERIOR WAYS OF EXIT ACCESS 61M 61M
AREAS OTHER THAN THOSE WITHIN LIVING UNITS TO AN EXIT 61M 76M
TOTAL TRAVEL DISTANCE PERMITTED FROM THE REMOTEST PORTION OF THE APARTMENT TO THE NEAREST EXIT 53M 99M
2 COMMON PATH LIMIT NFPA 101 TABLE A.7.6 NOTE: TRAVEL WITHIN A DWELLING UNIT IS NOT INCLUDED WHEN DETERMINING COMMON PATH OF TRAVEL 10.7M 15M
3 DEAD-END CORRIDOR NFPA 101 TABLE A.7.6 10.7M 15M
4 EXIT DISCHARGE    
  EXTERIOR DISCHARGE (DIRECT TO BUILDING EXTERNAL) COMPLYING WITH NFPA 101 REQUIRED
  THROUGH AREAS ON LEVEL OF EXIT DISCHARGE (INTERNAL DISCHARGE) MAXIMUM 10.7M TRAVEL DISTANCE TO BUILDING EXTERNAL PERMITTED IF SPRINKLER PROTECTED
50% OF THE REQUIRED NUMBER OF EXITS & 50% OF THE REQUIRED EXIT CAPACITY (SPRINKLER PROTECTED) PERMITTED IF SPRINKLER PROTECTED
5 EXTERIOR WAYS OF EXIT COMPLYING WITH NFPA 101 PERMITTED
6 ACCESSIBLE MEANS OF EGRESS EXIT PROVISIONS FOR PEOPLE WITH SEVERE MOBILITY IMPAIRMENT (NOT LESS THAN 2 EXITS REQUIRED) REQUIRED
7 ILLUMINATION OF MEANS OF EGRESS COMPLYING WITH CHAPTER 7 NFPA 101 REQUIRED
8 EMERGENCY LIGHTING THE BUILDING IS THREE (3) OR MORE STORIES IN HEIGHT REQUIRED
THE OCCUPANCY IS SUBJECT TO 50 OR MORE OCCUPANTS ABOVE OR BELOW THE LEVEL OF EXIT DISCHARGE REQUIRED
THE OCCUPANCY IS SUBJECT TO 300 OR MORE TOTAL OCCUPANTS REQUIRED
9 MARKINGS OF MEANS OF EGRESS COMPLYING WITH CHAPTER 7 NFPA 101 REQUIRED
F SPECIAL MEANS OF EGRESS PROVISIONS    
1 FIREMEN ACCESS PANELS HABITABLE HEIGHT EXCEEDING 10M REQUIRED
2 REFUGE FLOORS HIGH-RISE BUILDING EXCEEDING 30 STORIES REQUIRED IF BUILDING/S EXCEEDS 30 STOREYS
3 ELEVATORS FOR OCCUPANT CONTROLLED EVACUATION PRIOR TO PHASE 1 EMERGENCY RECALL OPERATIONS COMPLYING WITH CHAPTER 7 NFPA 101 PERMITTED

High rise Apartment

HEIGHT & AREA ALLOWED

Height: > 28m

Area: UL - UNLIMITED AREA 


APARTMENT BUILDINGS 

Residential Occupancy Containing Three or More Dwelling Units With Independent Bathroom and Cooking Facilities