Notes: As per NFPA-101-7.1.3.1 - if 'exit' corridor will serve >30 occupants, the walls must be 1-hour fire rated and doors to be 45-minutes fire rated. Though this requirement shall not apply where otherwise provided in table below.
OCCUPANCY TYPE (new building) CODE REF. CORRIDOR DOOR FIRE RATING REQUIREMENTS
AMBULATORY (Not Sprinklered) (20.3.6.1, 38.3.6.2, and 8.2.3.2.3.1 (2) Exception 1) 45 minutes, No requirement if area is occupied by single tenant
AMBULATORY (Sprinklered) NFPA 101, 2012 No Requirement
ASSEMBLY (Not Sprinklered) (12.3.6.1) 45-min if OL > 30, No requirement if 50% of exit capacity is discharging to outside.
ASSEMBLY (Either Sprinklered or with Smoke Detection) NFPA 101, 2012 No Requirement
BUSINESS (Not Sprinklered) (38.3.6.2 and 8.2.3.2.3.1 (2) Exception 1) 20 minutes
BUSINESS (Sprinklered) NFPA 101, 2012 No Requirement
HEALTHCARE (18.3.6.3.1) Resist passage of smoke
EDUCATIONAL (Not Sprinklered) (14.3.6) 45 minutes
EDUCATIONAL (Sprinklered) (14.3.6) Resist passage of smoke
ONE & TWO FAMILY DWELLINGS (-) No Requirement
HOTELS AND DORMITORIES (28.3.6.2) 20 minutes (self-closing and self-latching)
APARTMENTS (30.3.6.2) 20 minutes (self-closing and self-latching)
MERCANTILE (-) -
STORAGE (42.3.6) No Requirement, provision of 7.1.3.1 shall not apply
INDUSTRIAL (40.3.6) No Requirement, provision of 7.1.3.1 shall not apply

Doors are required to be of side-hinged or pivoted-swinging type shall swing in the direction of egress travel where serving a room or area with an occupant load of 50 or more.

Door also shall swing in the direction of egress travel when

 

Notes: