OCCUPANCY TYPE (new building)
|
CODE REF. |
DEAD-END
|
AMBULATORY
(Not Sprinklered) |
(20.2.5 AND 38.2.5.2) |
6 m. |
AMBULATORY
(Sprinklered) |
(20.2.5 AND 38.2.5.2) |
15 m. |
ASSEMBLY (Sprinklered and Not Sprinklered) |
(12.2.5.1.3) |
6 m. |
BUSINESS
(Not Sprinklered) |
(38.2.5.2.2) |
6 m. |
BUSINESS
(Sprinklered) |
(38.2.5.2.1) |
15 m. |
HEALTHCARE
(Sprinklered and Not Sprinklered) |
(18.2.5.2) |
9 m. |
EDUCATIONAL (Not Sprinklered) |
(14.2.5.2) |
6 m. |
EDUCATIONAL (Sprinklered |
(14.2.5.2) |
15 m. |
ONE & TWO FAMILY DWELLINGS
|
(-) |
No Requirement |
HOTELS AND DORMITORIES
(Not Sprinklered) |
(Table A.7.6) |
10.7 m. |
HOTELS AND DORMITORIES
(Sprinklered) |
(Table A.7.6) |
15 m. |
APARTMENTS
(Not Sprinklered) |
(Table A.7.6) |
10.7 m. |
APARTMENTS
(Sprinklered) |
(Table A.7.6) |
15 m. |
MERCANTILE
(Not Sprinklered) |
(Table A.7.6) |
6 m. |
MERCANTILE
(Sprinklered) |
(Table A.7.6) |
15 m. |
STORAGE
(Sprinklered and Not Sprinklered) |
(Table A.7.6) |
15 m. |
STORAGE
|
(Table 42.2.5) |
(see Table 42.2.5 for Arrangement of means of exit) |
INDUSTRIAL
|
(Table 40.2.5) |
Refer to Table 40.2.5 |