OCCUPANCY TYPE (new building)
|
CODE REF. |
TRAVEL DISTANCE LIMITS
|
AMBULATORY (Not Sprinklered) |
20.2.6.2.1, 7.6 |
46 m. (from any point in a room to exit) |
AMBULATORY (Sprinklered) |
20.2.6.2.2, 7.6 |
61 m. (from any point in a room to exit) |
ASSEMBLY (Not Sprinklered) |
12.2.6.2 |
61 m. (from any point to exit) |
ASSEMBLY (Sprinklered) |
12.2.6.2(1) |
76 m. (from any point to exit) |
BUSINESS (Not Sprinklered) |
38.2.6.2, 7.6 |
61 m. (from any point in the building to exit) |
BUSINESS (Sprinklered) |
38.2.6.3, 7.6 |
91 m. (from any point in the building to exit) |
HEALTHCARE |
18.2.6.2.1, 7.6, 18.2.6.2.3 |
61 m. (from any point in a room to exit)
15 m. (from any point in sleeping room to room access door) |
EDUCATIONAL(Not Sprinklered) |
(14.2.6.2) |
46 m. (from any point in the building to exit) |
EDUCATIONAL(Sprinklered) |
14.2.6.3, 7.6 |
61 m. (from any point in the building to exit) |
ONE & TWO FAMILY DWELLINGS
|
(-) |
No Requirements |
HOTELS AND DORMITORIES (Not Sprinklered) |
(28.2.6.1, 28.2.6.3.1) |
23 m. (within guest room to corridor door)
30 m. (from corridor door to exit)
(see also 28.2.6.3.3.2) |
HOTELS AND DORMITORIES (Sprinklered) |
(28.2.6.2, 28.2.6.3.2) |
38 m. (within guest room to corridor door)
61 m. (from corridor door to exit) |
APARTMENTS (Not Sprinklered) |
(30.2.6.1, 30.2.6.3.1) |
23 m. (within dwelling unit to corridor door)
30 m. (from apt. entrance door to exit) |
APARTMENTS (Sprinklered) |
(30.2.6.2, 30.2.6.3.2) |
38 m. (within dwelling unit to corridor door)
61 m. (from apt. entrance door to exit) |
MERCANTILE (Not Sprinklered) |
(36.2.6.1, 36.2.6.3) |
46 m. (if ordinary hazard)
23 m. (if high hazard) |
MERCANTILE (Sprinklered) |
(26.2.6.2) |
76 m. (if ordinary hazard) |
STORAGE
|
(42.2.6)(42.8.2.6.1) |
(see table 42.2.6 for Travel distance to exit for storage occupancy)(see table 42.8.2.6.1 for Travel distance to exit for basement parking) |
INDUSTRIAL
|
(Table 40.2.6) |
Refer to Table 40.2.6 |