OCCUPANCY TYPE (new building) CODE REF. MINIMUM CORRIDOR WIDTH
AMBULATORY (Sprinklered or Not Sprinklered) (20.2.3.2) 1120 mm.
BUSINESS (Sprinklered or Not Sprinklered) (38.2.3.2) 1120 mm. serving occupant load > 50, 900 mm. serving occupant load < 50
HEALTHCARE (18.2.3.4) 2440 mm. on hospital and nursing homes 1120 mm. on other areas
EDUCATIONAL (14.2.3.2) 1830 mm.
ONE & TWO FAMILY DWELLINGS (-) No Requirement
HOTELS AND DORMITORIES (28.2.3.3) 1120 mm.
APARTMENTS (30.2.3.3) 1120 mm. serving occupant load > 50
MERCANTILE (7.3) Compute width based on egress capacity factor. (see table below)
STORAGE (7.3) Compute width based on egress capacity factor. (see table below)
image source: HCare Facilities Today

Notes:
Table 7.3.3.1 Egress Capacity Factors
Stairways (width per person) Ramps, Aisles and Corridors (width per person)
Area mm mm
Board and Care 10 5
Health Care (sprinklered) 7.6 5
Health Care (nonsprinklered) 15 13
High Hazard Contents 18 10
All Others 7.6 5

Data below extracted from page 204 of UAE Fire and Life Safety Code (for ASSEMBLY occupancy).. see also DOOR SWING ENCROACHMENT