OCCUPANCY TYPE (new building)
|
CODE REF. |
DOOR minimum CLEAR WIDTH
|
AMBULATORY (Sprinklered and Not Sprinklered) |
NFPA 101, 2015 (20.2.3.4) |
810 mm. required for diagnostics or treatment area such as x-ray, surgical or physical therapy. |
BUSINESS (Sprinklered and Not Sprinklered) |
NFPA 101, 2015 (7.3.4.1 [2]) |
915 mm. required for any means of egress or calculate using table 7.3.3.1 (capacity factor) |
HEALTHCARE |
NFPA 101, 2015 (18.2.3.6) |
810 mm. required for psychiatric hospitals and limited care facilities
1055 mm. required for hospital and nursing homes |
NFPA 101, 2015 (18.2.3.7) |
810mm. required for exit stair enclosure
810mm. required for newborn nurseries
not less than one of the pair of doors shall be 810mm. |
EDUCATIONAL |
NFPA 101, 2015 (7.3.4.1 [2]) |
915 mm. required for any means of egress or calculate using table 7.3.3.1 (capacity factor) |
ONE & TWO FAMILY DWELLINGS
|
NFPA 101, 2015
(24.2.4.1) |
710 mm. required for doors in the path of travel of a mean of escape and in room <6.5 sqm
610 mm. for Bathroom <6.5 sqm |
HOTELS AND DORMITORIES
|
NFPA 101, 2015 (7.3.4.1 [2]) |
915 mm. required for any means of egress or calculate using table 7.3.3.1 (capacity factor) |
APARTMENTS
|
NFPA 101, 2015 (7.3.4.1 [2]) |
915 mm. required for any means of egress or calculate using table 7.3.3.1 (capacity factor) |
MERCANTILE
|
NFPA 101, 2015 (7.3.4.1 [2]) |
915 mm. required for any means of egress or calculate using table 7.3.3.1 (capacity factor) |
STORAGE
|
NFPA 101, 2015 (7.3.4.1 [2]) |
915 mm. required for any means of egress or calculate using table 7.3.3.1 (capacity factor) |