{"id":1947,"date":"2020-12-08T08:10:43","date_gmt":"2020-12-08T08:10:43","guid":{"rendered":"http:\/\/shared4.info\/buildingcodes\/?p=1947"},"modified":"2020-12-08T08:34:37","modified_gmt":"2020-12-08T08:34:37","slug":"electrical-room","status":"publish","type":"post","link":"https:\/\/shared4.info\/buildingcodes\/electrical-room\/","title":{"rendered":"Electrical Room"},"content":{"rendered":"<p>Considering QCDD Guidelines;<\/p>\n<p>As per <a href=\"http:\/\/shared4.info\/qcd\/annexes\/electrical-rooms-substation-swithgears-and-others.htm\">QCD-GA 1.2<\/a>, if Electrical room &lt; 5.1sqm and with 2-hrs enclosure, then Automatic Suppression system is NOT required.<\/p>\n<p>As per <a href=\"http:\/\/shared4.info\/qcd\/annexes\/electrical-rooms-substation-swithgears-and-others.htm\">QCD-GA 1.2<\/a>, if Electrical room &gt; 5.1sqm, then Automatic Suppression system is required. The wall enclosure fire rating doesn&#8217;t need to be 2-hrs as per below table;<\/p>\n<table class=\"checked\">\n<tbody>\n<tr>\n<th scope=\"col\" align=\"center\" width=\"40\">VIII<\/th>\n<th colspan=\"3\" scope=\"col\">BUILDING SERVICES PROTECTION (ASS* AUTOMATIC SUPPRESSION SYSTEM)<\/th>\n<th scope=\"col\">ANY OCCUPANCY<\/th>\n<\/tr>\n<tr id=\"pale\">\n<td align=\"center\" width=\"40\">A<\/td>\n<td>BUILDING UTILITIES<\/td>\n<td colspan=\"2\">COMPLYING WITH CHAPTER 9 NFPA 101<\/td>\n<td><\/td>\n<\/tr>\n<tr>\n<td rowspan=\"5\" align=\"center\" width=\"40\">2<\/td>\n<td>ELECTRICAL SYSTEMS<\/td>\n<td colspan=\"2\">COMPLYING WITH NFPA 70<\/td>\n<td>REQUIRED<\/td>\n<\/tr>\n<tr>\n<td>ELECTRICAL EQUIPMENT ROOMS<\/td>\n<td colspan=\"2\">AUTOMATIC SUPPRESSION SYSTEM OR 2-HOURS ENCLOSURE<\/td>\n<td>REQUIRED<\/td>\n<\/tr>\n<tr>\n<td rowspan=\"3\">SUBSTATION &amp; SWITHGEARS<\/td>\n<td colspan=\"2\">ATTACHED TO OCCUPIED BUILDINGS REQUIRED PROTECTION<\/td>\n<td>3-HOURS FRR* or ASS*<\/td>\n<\/tr>\n<tr>\n<td colspan=\"2\">STANDALONE TRANSFORMER VAULT REQUIRED PROTECTION<\/td>\n<td>3-HOURS FRR* or 2-HOURS FRR* with ASS<\/td>\n<\/tr>\n<tr>\n<td colspan=\"2\">EXPLOSION PROTECTION<\/td>\n<td>ASS* &amp; 2-HOURS FRR* ENCLOSURE<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<p>Considering NFPA 13;<\/p>\n<ol>\n<li>8.15.10.3 Sprinklers shall not be required in electrical equipment rooms where all of the following conditions are met:<br \/>\n(1) The room is dedicated to electrical equipment only.<br \/>\n(2) Only dry-type electrical equipment is used.<br \/>\n(3) Equipment is installed in a 2-hour fire-rated enclosure including protection for penetrations.<br \/>\n(4) No combustible storage is permitted<\/li>\n<\/ol>\n","protected":false},"excerpt":{"rendered":"<p>Considering QCDD Guidelines;<\/p>\n<p>As per <a href=\"http:\/\/shared4.info\/qcd\/annexes\/electrical-rooms-substation-swithgears-and-others.htm\">QCD-GA 1.2<\/a>, if Electrical room &lt; 5.1sqm and with 2-hrs enclosure, then Automatic Suppression system is NOT required.<\/p>\n<p>As per <a href=\"http:\/\/shared4.info\/qcd\/annexes\/electrical-rooms-substation-swithgears-and-others.htm\">QCD-GA 1.2<\/a>, if Electrical room &gt;<\/p>\n<p><span class=\"ellipsis\">&hellip;<\/span><\/p>\n<div class=\"read-more\"><a href=\"https:\/\/shared4.info\/buildingcodes\/electrical-room\/\">Read more &#8250;<\/a><\/div>\n<p><!-- end of .read-more --><\/p>\n","protected":false},"author":1,"featured_media":0,"comment_status":"closed","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"footnotes":""},"categories":[57],"tags":[],"_links":{"self":[{"href":"https:\/\/shared4.info\/buildingcodes\/wp-json\/wp\/v2\/posts\/1947"}],"collection":[{"href":"https:\/\/shared4.info\/buildingcodes\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/shared4.info\/buildingcodes\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/shared4.info\/buildingcodes\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/shared4.info\/buildingcodes\/wp-json\/wp\/v2\/comments?post=1947"}],"version-history":[{"count":3,"href":"https:\/\/shared4.info\/buildingcodes\/wp-json\/wp\/v2\/posts\/1947\/revisions"}],"predecessor-version":[{"id":1953,"href":"https:\/\/shared4.info\/buildingcodes\/wp-json\/wp\/v2\/posts\/1947\/revisions\/1953"}],"wp:attachment":[{"href":"https:\/\/shared4.info\/buildingcodes\/wp-json\/wp\/v2\/media?parent=1947"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/shared4.info\/buildingcodes\/wp-json\/wp\/v2\/categories?post=1947"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/shared4.info\/buildingcodes\/wp-json\/wp\/v2\/tags?post=1947"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}