GA 6.3 | FIRE ALARM SYSTEM | |
---|---|---|
GA_6.3 – Revisions_2015 | ||
Item No. | Provisions | Notes |
1.0 | Fire alarm systems shall be provided for all buildings and structure that provide public access. See Guidelines for Fire Alarm System for reference. | Where and what required |
2.0 | Fire alarm systems shall be of the conventional type or addressable type or combination of both. This shall be QCD approved for use in the State of Qatar. | Types |
3.0 | Fire Alarm Systems shall be designed and installed in accordance with the latest edition of NFPA 72 except as clearly modified by these requirements. Where ambiguities in either these requirements of the NFPA 72 exist, it shall be the responsibility of the engineering endorsing the fire safety plans to obtain clarification from the Qatar Civil Defence Department. | NFPA 72 |
4.0 | All fire alarm system shall have the following: | System Architecture |
4.1 Main fire alarm control unit/panel (addressable / conventional type) | ||
4.2 Main Indicating Mimic Panel shall use red coloured Light Emitting Diode (LED) to indicate graphically the building, the floor, location and the initiating device that is in alarm; or if provided with PC based workstation, an information stating that graphic user interface (GUI) is integrated in the software/application in lieu of the Main Indicating Mimic Panel. | ||
5.0 | Fire alarm control unit/panel shall be provided inside each building and located in any of the following: | Fire Alarm Control Panel |
|
||
6.0 | Zone Chart shall clearly depict the location of all fire zones, the type and location of all initiating devices with labels on that floor with a “YOU ARE HERE” indication and shall be provided on each floor of every building located within the firefighting lobby and smoke-stop lobby or common lobby in close proximity to the exit staircase. | Zone Chart |
7.0 |
|
Detectors |
8.0 | Manual call points shall be located within 1.5M of each fire exit. The initiating device shall be located such that no part of any floor is further than 30M from the nearest manual call point | Manual Call Point |
9.0 | Fire alarm wiring shall be in accordance with the latest edition of NFPA 70 & 72. Where fire alarm wires are exposed and subject to possible damage from normal use of the occupancy, they shall be provided with mechanical protection | Fire Alarm Cables |
10.0 | Power Supplies | |
10.1 Primary Power Supply shall be an alternating current (AC) supply from an authorized electricity provided and shall be exclusive to the alarm system.
|
Primary Power Supply | |
10.2 Secondary Power supply shall be in the form of the following:
|
Secondary Power Supply | |
10.3 A fault warning shall be given in the event of failure of either primary or secondary power supply | Fault Indication | |
10.4 A battery charger of appropriate type and rating shall be provided to keep the storage batteries under constant voltage charge.
|
Battery Charger | |
10.5 Battery Capacity
|
Battery Capacity | |