FIRE ALARM SYSTEM
OCCUPANCY CLASSIFICATION BUILDING CONFIGURATION Fire Alarm System¹ Requirements
FLOOR AREA M² HABITABLE HEIGHT (METER) AUTOMATIC - MANUAL CONTROL PANEL ZONE CHART / FIRE EVACUATION PLAN GRAPHIC ANNUNCIATOR / MIMIC PANEL DETECTORS (SMOKE/HEAT) MANUAL CALL POINT / INTERFACE MODULE AUDIBLE (SOUNDER/BELL) / VISIBLE (STROBE/FLASHER) MASS NOTIFICATION SYSTEM FIRE TELEPHONE (TWO-WAY COMMUNICATION SYSTEM)
ASSEMBLY                    
MASJID (with or without Imam House) <300 occupants NA NA NR R NR R (4) R R NR NR
MASJID (with or without Imam House) >300 occupants NA NA R R NR R R R NR NR
ASSEMBLY WITH LESS THAN 300 OCCUPANTS (AUDITORIUMS, THEATER AS PER NFPA 101) NA NA R R P R R R NR NR
ASSEMBLY WITH MORE THAN 300 OCCUPANTS (AUDITORIUMS, THEATER AS PER NFPA 101) NA NA R R P R R R R R

ABBREVIATIONS:
R = REQUIRED | NA = NOT APPLICABLE | NR = NO REQUIREMENT | P = PERMITTED | NL = NO LIMIT

Superscript Description:

NOTATION: