FIRE ALARM SYSTEM
OCCUPANCY CLASSIFICATION BUILDING CONFIGURATION Fire Alarm System¹ Requirements
FLOOR AREA M² HABITABLE HEIGHT (METER) AUTOMATIC - MANUAL CONTROL PANEL ZONE CHART / FIRE EVACUATION PLAN GRAPHIC ANNUNCIATOR / MIMIC PANEL DETECTORS (SMOKE/HEAT) MANUAL CALL POINT / INTERFACE MODULE AUDIBLE (SOUNDER/BELL) / VISIBLE (STROBE/FLASHER) MASS NOTIFICATION SYSTEM FIRE TELEPHONE (TWO-WAY COMMUNICATION SYSTEM)
BUSINESS                    
CLASS A - LOW RISE BUILDING ≤500M² ≤15M R R NR R R R NR NR
CLASS B - MEDIUM RISE BUILDING, TYPE A >500M² - ≤1,000M² >15M - ≤18M R R P R R R P P
CLASS B - MEDIUM RISE BUILDING, TYPE B >1,000M² >18M - ≤28M R R R R R R P P
CLASS C - HIGH RISE BUILDING UL >28M R R R R R R R R

ABBREVIATIONS:
R = REQUIRED | NA = NOT APPLICABLE | NR = NO REQUIREMENT | P = PERMITTED | NL = NO LIMIT