GA 3.5.2 |
NON-LOAD BEARING EXTERIOR WALLS |
GUIDELINES ANNEX - GA_3.5.2 – Revisions_2015 |
Item No. |
Provisions |
Notes |
1.0 |
General. Requirements of the Exterior Walls shall be as follows: |
|
1.1 |
Any exterior wall of a building or a separated part of a building shall be: |
|
1.1.1 |
Constructed wholly of non-combustible materials apart from any external finishes which complies with Chapter 37 of the latest edition of NFPA 5000 or any internal lining/finishes which complies with chapter 10 of NFPA 5000, and |
|
1.1.2 |
So constructed as to attain the fire resistance based on Table 7.2.1.1 and Table 7.3.2.1 of the latest edition of NFPA 5000 whichever is greater. |
|
1.2 |
Any beam or column forming part of an exterior wall and any structure carrying an exterior wall which is required to be constructed of non-combustible material, shall comply with the provisions of the above-mentioned sub-clause (1.1). |
|
2.0 |
Exceptions. |
|
2.1 |
The above-mentioned requirements for non-combustibility of exterior walls shall not apply to the external walls of a building or separated part of a building containing one-and-two family dwelling if that wall is: |
|
2.1.1 |
Situated 3m or more from the relevant boundary, and |
|
2.1.2 |
Not exceeding 8m in height, and |
|
2.1.3 |
Non-load bearing wall. |
|
2.2 |
The proposed exterior wall shall be tested I accordance with the latest edition of NFPA 285. |
|
2.3 |
The flame spread and smoke development of these exterior walls shall also have Class A rating in accordance with the latest edition of NFPA 255 based on the maximum intended use. |
|
2.4 |
Fire retardant-treated wood shall be permitted in exterior non-load bearing wall when such walls are not required to have fire resistance rating. |
|
2.5 |
Use of plastics, inclusive of foam plastic insulation, shall be in accordance with Chapter 48 of the latest edition of NFPA 5000. |
|
|
|
|
|
|
|