MECHANICAL VENTILATION SYSTEM for INDUSTRIAL OCCUPANCY
Occupancy Classification Building Configuration Ventilation & Smoke Control Requirements
Ventilation System in Smoke Proof Enclosure Mechanical Ventilation, Extract / Smoke Ventilation Exhaust System
Max. Area
(sq.m.)
Habitable Height
(m)
Exit Staircase Smoke-Stop Lobby Fire Fighting Lobby Operation / Process Space Basement Fire Pump Room Generator Room Fire Command Center Atrium, Communicating Space Zoned Smoke Controlled Spaces
SPECIAL PURPOSE INDUSTRIAL OCCUPANCY 5 or more storeys in height ≥15m R 1 R 2 R 2 R 13 R 4 R 6 R 7 R 8 R 5 R 3
> 1,115 NA NR NR NR R 13 R 4 R 6 R 7 R 8 R 5 R 3
Gross or total area of all floors exceeds 2,230 M² VARIES *** 1 *** 2 *** 2 R 13 R 4 R 6 R 7 R 8 R 5 R 3
Wood working operation with floor area exceeding 232 M² VARIES NR NR NR R 13 R 4 R 6 R 7 R 8 R 5 R 3
GENERAL INDUSTRIAL OCCUPANCY 5 or more storeys in height ≥15m R 1 R 2 R 2 R 13 R 4 R 6 R 7 R 8 R 5 R 3
> 1,115 NA NR NR NR R 13 R 4 R 6 R 7 R 8 R 5 R 3
Gross or total area of all floors exceeds 2,230 M² VARIES *** 1 *** 2 *** 2 R 13 R 4 R 6 R 7 R 8 R 5 R 3
Wood working operation with floor area exceeding 232 M² VARIES NR NR NR R 13 R 4 R 6 R 7 R 8 R 5 R 3
HIGH HAZARD INDUSTRIAL OCCUPANCY 5 or more storeys in height ≥15m R 1 R 2 R 2 R 13 R 4 R 6 R 7 R 8 R 5 R 3
> 1,115 NA NR NR NR R 13 R 4 R 6 R 7 R 8 R 5 R 3
Gross or total area of all floors exceeds 2,230 M² VARIES *** 1 *** 2 *** 2 R 13 R 4 R 6 R 7 R 8 R 5 R 3
Wood working operation with floor area exceeding 232 M² VARIES NR NR NR R 13 R 4 R 6 R 7 R 8 R 5 R 3

ABBREVIATIONS:
ACH = Air Change per hour| R = Required | NR = Not Required | N/A = Not Applicable| R = (Letter/Number) - Addendum subscript description | *** = Refer to Note/s | sq.m. = square meters | m = meters | Max. = maximum | MEP = Mechanical, Electrical, Plumbing

Note:
* Other requirement not covered nor specified in this standard / guideline must be referred to relevant NFPA code & standards or consult with QCDD engineers for compliance.
** For superscript descriptions, refer to Addendum.
*** Provide Ventilation if the Smoke/Fire Enclosure or MEP Rooms were provided.
**** Smoke control system shall be supplied with 2 power sources.
Provides control capability over equipment of the smoke control system.

Superscript Description: