MECHANICAL VENTILATION SYSTEM for STORAGE OCCUPANCY
Occupancy Classification Building Configuration Ventilation & Smoke Control Requirements
Ventilation System in Smoke Proof Enclosure Mechanical Ventilation, Extract / Smoke Ventilation Exhaust System
Max. Area
(sq.m.)
Habitable Height
(m)
Exit Staircase Smoke-Stop Lobby Fire Fighting Lobby Operational/ Process Space Basement Fire Pump Room Generator Room Fire Command Center Atrium, Communicating Space Zoned Smoke Controlled Spaces
LOW HAZARD STORAGE Exit staircases connecting 5 storeys including basements ≥15m R (1) R (2) R (2) R (13) R (4) R (6) R (7) R (8) R (5) R (3)
> 1,115 NA NR NR NR R (13) R (4) R (6) R (7) R (8) R (5) R (3)
Gross or total area of all floors exceeds 2,230 M² VARIES *** 1 *** 2 *** 2 R (13) R (4) R (6) R (7) R (8) R (5) R (3)
Mini-storage bldg. > 232 M² NA NR NR NR R (13) R (4) R (6) R (7) R (8) R (5) R (3)
Bulk storage of tires exceeds 566 M² NA NR NR NR R (13) R (4) R (6) R (7) R (8) R (5) R (3)
ORDINARY HAZARD STORAGE Exit staircases connecting 5 storeys including basements ≥15m R (1) R (2) R (2) R (13) R (4) R (6) R (7) R (8) R (5) R (3)
> 1,115 NA NR NR NR R (13) R (4) R (6) R (7) R (8) R (5) R (3)
Gross or total area of all floors exceeds 2,230 M² VARIES *** 1 *** 2 *** 2 R (13) R (4) R (6) R (7) R (8) R (5) R (3)
Mini-storage bldg. > 232 M² NA NR NR NR R (13) R (4) R (6) R (7) R (8) R (5) R (3)
Bulk storage of tires exceeds 566 M² NA NR NR NR R (13) R (4) R (6) R (7) R (8) R (5) R (3)
HIGH HAZARD STORAGE Exit staircases connecting 5 storeys including basements ≥15m R (1) R (2) R (2) R (13) R (4) R (6) R (7) R (8) R (5) R (3)
> 1,115 NA NR NR NR R (13) R (4) R (6) R (7) R (8) R (5) R (3)
Gross or total area of all floors exceeds 2,230 M² VARIES *** 1 *** 2 *** 2 R (13) R (4) R (6) R (7) R (8) R (5) R (3)
Mini-storage bldg. > 232 M² NA NR NR NR R (13) R (4) R (6) R (7) R (8) R (5) R (3)
Bulk storage of tires exceeds 566 M² NA NR NR NR R (13) R (4) R (6) R (7) R (8) R (5) R (3)

ABBREVIATIONS:
ACH = Air Change per hour| R = Required | NR = Not Required | N/A = Not Applicable| R = (Letter/Number) - Addendum subscript description | *** = Refer to Note/s | sq.m. = square meters | m = meters | Max. = maximum | MEP = Mechanical, Electrical, Plumbing

Note:
* Other requirement not covered nor specified in this standard / guideline must be referred to relevant NFPA code & standards or consult with QCDD engineers for compliance.
** For superscript descriptions, refer to Addendum.
*** Provide Ventilation if the Smoke/Fire Enclosure or MEP Rooms were provided.
**** Smoke control system shall be supplied with 2 power sources.
Provides control capability over equipment of the smoke control system.

Superscript Description: