Medium-Rise Apartment Building (Type-B) - FIRE PROTECTION


Height: > 18m to <28m

Area: > 1,000 sqm


VII FIRE PROTECTION (FRR* FIRE RESISTANCE RATING / FPR** FIRE PROTECTION RATING) MEDIUM-RISE APARTMENT (TYPE-B)
A DETECTION ALARM AND COMMUNICATION SYSTEMS    
1 FIRE ALARM SYSTEM *INCLUDE REQUIREMENTS FOR CARBON MONOXIDE ALARMS & CARBON MONOXIDE DETECTION SYSTEM AS NFPA 101 2012 & NFPA 72 REQUIRED
B EXTINGUISHING REQUIREMENTS COMPLIANCE WITH INDIVIDUAL CODES & STANDARDS REQUIRED
1 PROTABLE FIRE EXTINGUISHERS TYPE AND RATING IN ACCORDANCE WITH NFPA 10 REQUIRED
2 FIRE BLANKETS IN KITCHEN OR PANTRY REQUIRED
3 STANDPIPE SYSTEM BUILDING EXCEEDING 9M IN HABITABLE HEIGHT REQUIRED
4 FIRE HOSE REELS 25MM DIAMETER HOSE REQUIRED
5 AUTOMATIC SPRINKLER SYSTEM THROUGHOUT PROTECTION NOT REQUIRED
PROVIDED IN LIAEU OF THE REQUIRED DRAFTSTOPS IN CONCEALED SPACES NOT REQUIRED
ONE BASEMENT LEVEL USED AS CARPARK ONLY (WITH FLOOR AREA EXCEEDING 1115 SQM) REQUIRED
ONE BASEMENT LEVEL USED AS MIXED OCCUPANCY REQUIRED
MORE THAN ONE BASEMENT LEVEL REQUIRED
6 OTHER EXTINGUISHING EQUIPMENT COMPLIANCE FROM INDIVIDUAL NFPA CODES & STANDARDS NOT REQUIRED