FIRE SAFETY PROVISIONS |
MINIMUM REQUIREMENTS |
PORTA CABINS |
| III |
SITE ACCESS |
|
|
| A |
SITE ACCESS & ACCESS ROAD |
CLEAR WIDTH |
4.0M |
| IV |
BUILDINGS SETBACKS |
|
|
| A |
DISTANCE FROM LOT BOUNDARY |
3.0 METERS |
REQUIRED |
| B |
FIRE BREAKS FROM EACH UNIT/STRUCTURES |
4.0 METERS |
REQUIRED |
| C |
DISTANCE FROM ANY COOKING FACILITIES |
5.0 METERS |
REQUIRED |
| |
DISTANCE WITHIN 5M |
1-HR FRP ENCLOSURE |
REQUIRED |
| V |
MEANS OF EGRESS (FRR* FIRE RESISTANCE RATING / FPR** FIRE PROTECTION RATING |
| A |
COMPONENTS AND CAPACITY OF MEANS OF EGRESS |
|
|
| 1 |
SWING-TYPE DOORS |
MINIMUM CLEAR WIDTH (<5 PERSONS) |
750 MM |
| 2 |
STAIRS |
DOORS FRP (FIRE RESISTANCE PERIOD) |
NOT REQUIRED |
| WALL ENCLOSURES FRP |
NOT REQUIRED |
| STANDARD STAIRS |
MINIMUM CLEAR WIDTH |
1000 MM |
| SPIRAL STAIRS |
COMPLYING WITH NFPA 101 |
PERMITTED |
| 3 |
CORRIDORS |
MIN. CLEAR WIDTH INTERNAL CORRIDORS |
1500 MM |
| MIN. CLEAR WIDTH OPEN-SIDED CORRIDORS |
1000 MM |
| 4 |
FIREMEN ACCESS PANEL |
OPENABLE WINDOWS (0.53 SQM) |
510MM X 610MM |
| B |
NUMBER OF EXITS |
|
|
| |
SINGLE EXIT |
DOOR AS MAIN EXIT/S |
REQUIRED |
| WINDOW AS SECONDARY EXIT |
REQUIRED |
| |
2 EXITS |
STAIR/S AS MAIN EXIT/S |
REQUIRED |
| C |
CAPACITY OF MEANS OF EGRESS |
|
|
| 1 |
OCCUPANT LOAD FACTOR |
|
3 SQM / PERSON |
| D |
ARRANGEMENT OF EXITS |
|
|
| 1 |
TRAVEL DISTANCE |
ESCAPE ROUTE VIA OPEN-SIDED CORRIDORS |
9 M |
| ESCAPE ROUTE VIA INTERNAL CORRIDORS |
NO REQUIREMENT |
| 2 |
COMMON PATH LIMIT |
ESCAPE ROUTE VIA OPEN-SIDED CORRIDORS |
9 M |
| ESCAPE ROUTE VIA INTERNAL CORRIDORS |
NO REQUIREMENT |
| 3 |
DEAD END CORRIDOR |
|
NOT PERMITTED |
| 4 |
EXIT DISCHARGE |
DIRECT EXIT DISCHARGE TO BUILDING EXTERNAL |
REQUIRED |
| E |
ILLUMINATION OF EXITS AND MARKINGS OF THE MEANS OF EGRESS |
|
|
| 1 |
EXIT LIGHTS |
EXITS, EXIT ACCESS & EXIT DISCHARGE |
REQUIRED |
| 2 |
EXITS SIGNS |
EXIT ACCESS, EXIT DISCHARGE & EXITS OTHER THAN MAIN EXTERIOR EXIT DOORS |
REQUIRED |
| VI |
BUILDING CONSTRUCTION |
|
PORTA-CABINS |
| A |
CONSTRUCTION |
|
|
| 1 |
NON-COMBUSTIBLE OR STEEL MATERIALS |
|
REQUIRED |
| 2 |
TIMBER MATERIALS |
EXTERIOR BEARING MATERIALS |
1-HR FRR* |
| FRAMING, COLUMNS, BEAMS, GIRDERS, TRUSSES |
1-HR FRR* |
| FLOOR CONSTRUCTION |
1-HR FRR* |
| 3 |
BASE SUPPORT |
ERECTED ON HARDBASE (CONCRETE) |
REQUIRED |
| B |
COMPARTMENTATION |
|
|
| 1 |
WALLS BETWEEN EACH COMPARTMENT |
20M MAX LENGTH OF EACH COMPARTMENT |
NOT REQUIRED |
| 2 |
WALLS BETWEEN UNITS |
WITHIN EACH COMPARTMENT |
NOT REQUIRED |
| 3 |
EXIT ACCESS CORRIDORS |
INTERNAL CORRIDORS |
1/2-HR FRR* |
| OPEN-SIDED CORRIDORS |
NOT REQUIRED |
| FIRE DOORS (INTERNAL CORRIDORS) |
NOT REQUIRED |
| VII |
FIRE PROTECTION |
|
|
| A |
DETECTION ALARM AND COMMUNICATION SYSTEMS |
|
|
| 1 |
FIRE ALARM SYSTEM |
STAND ALONE DETECTORS (SMOKE ALARMS WIRED AND/OR BATTERY OPERATED) |
PERMITTED |
| MANUAL CALL POINT |
REQUIRED |
| B |
EXTINGUISHING REQUIREMENTS |
|
|
| 1 |
PORTABLE FIRE EXTINGUISHERS |
AT ENTRANCE IN EVERY UNIT |
REQUIRED |
| NEXT TO EVERY STAIRCASE AT EACH FLOOR |
REQUIRED |
| 2 |
FIRE HOSE REELS |
25 MM DIAMETER HOSE |
NOT REQUIRED |
| 3 |
FIRE HYDRANTS |
TEMPORARY BUILDINGS >100M AWAY FROM PUBLIC ROAD |
NOT REQUIRED |
| C |
AIR-CONDITIONING & MECHANICAL VENTILATION |
|
|
| 1 |
ALL HABITABLE ROOMS |
NATURAL OR MECHANICAL VENTILATION |
REQUIRED |
| OPENINGS FOR AIR-CIRCULATION |
REQUIRED |