I | APPLICATIONS | A BUILDING OR GROUP OF BUILDINGS REQUIRED IN CONNECTION WITH ANY BUILDING WORKS RELATING TO PERMANENT BUILDINGS DESIGNED TO BE EASILY MOVED FROM LOCATION TO LOCATION THAT MAY BE BROUGHT ON TO SITE OR CONSTRUCTED FOR DEFINED PERIOD OF USE PRIOR TO REMOVAL | |
---|---|---|---|
II | OCCUPANCY CLASSIFICATION** | BUILDING HEIGHT REQUIREMENTS | BUILDING AREA REQUIREMENTS |
A | TEMPORARY BUILDINGS | < 10M (G+2) WITH OPEN-SIDED CORRIDORS <7.5M (G+1) WITH INTERNAL CORRIDORS |
< 500 SQM 20M MAX LENGTH OF EACH COMPARTMENT |
FIRE SAFETY PROVISIONS | MINIMUM REQUIREMENTS | TEMPORARY BUILDINGS | |
---|---|---|---|
III | SITE ACCESS | ||
A | SITE ACCESS & ACCESS ROAD | CLEAR WIDTH | 4.0M |
IV | BUILDINGS SETBACKS | ||
A | DISTANCE FROM LOT BOUNDARY | 3.0 METERS | REQUIRED |
B | FIRE BREAKS FROM EACH UNIT/STRUCTURES | 4.0 METERS | REQUIRED |
C | DISTANCE FROM ANY COOKING FACILITIES | 5.0 METERS | REQUIRED |
DISTANCE WITHIN 5M | 1-HR FRP ENCLOSURE | REQUIRED | |
V | MEANS OF EGRESS (FRR* FIRE RESISTANCE RATING / FPR** FIRE PROTECTION RATING | ||
A | COMPONENTS AND CAPACITY OF MEANS OF EGRESS | ||
1 | SWING-TYPE DOORS | MINIMUM CLEAR WIDTH (<5 PERSONS) | 810 MM |
2 | STAIRS | DOORS FRP (FIRE RESISTANCE PERIOD) | 1/2-HR FRR* |
WALL ENCLOSURES FRP | 1-HR FRR* | ||
STANDARD STAIRS | MINIMUM CLEAR WIDTH | 1000 MM | |
SPIRAL STAIRS | COMPLYING WITH NFPA 101 | PERMITTED AS SECONDARY EXIT | |
3 | CORRIDORS | MIN. CLEAR WIDTH INTERNAL CORRIDORS | 1500 MM |
MIN. CLEAR WIDTH OPEN-SIDED CORRIDORS | 1000 MM | ||
4 | FIREMEN ACCESS PANEL | OPENABLE WINDOWS (0.53 SQM) | 510MM X 610MM |
B | NUMBER OF EXITS | ||
SINGLE EXIT | DOOR AS MAIN EXIT/S | 2 SEPARATE EXITS REQUIRED | |
WINDOW AS SECONDARY EXIT | REQUIRED | ||
2 EXITS | STAIR/S AS MAIN EXIT/S | REQUIRED | |
C | CAPACITY OF MEANS OF EGRESS | ||
1 | OCCUPANT LOAD FACTOR | 3 SQM / PERSON | |
D | ARRANGEMENT OF EXITS | ||
1 | TRAVEL DISTANCE | ESCAPE ROUTE VIA OPEN-SIDED CORRIDORS | 45 M |
ESCAPE ROUTE VIA INTERNAL CORRIDORS | 30 M | ||
2 | COMMON PATH LIMIT | ESCAPE ROUTE VIA OPEN-SIDED CORRIDORS | 20 M |
ESCAPE ROUTE VIA INTERNAL CORRIDORS | 15 M | ||
3 | DEAD END CORRIDOR | NOT PERMITTED | |
4 | EXIT DISCHARGE | DIRECT EXIT DISCHARGE TO BUILDING EXTERNAL | REQUIRED |
E | ILLUMINATION OF EXITS AND MARKINGS OF THE MEANS OF EGRESS | ||
1 | EXIT LIGHTS | EXITS, EXIT ACCESS & EXIT DISCHARGE | REQUIRED |
2 | EXITS SIGNS | EXIT ACCESS, EXIT DISCHARGE & EXITS OTHER THAN MAIN EXTERIOR EXIT DOORS | REQUIRED |
VI | BUILDING CONSTRUCTION | ||
A | CONSTRUCTION | ||
1 | NON-COMBUSTIBLE OR STEEL MATERIALS | REQUIRED | |
2 | TIMBER MATERIALS | EXTERIOR BEARING MATERIALS | 1-HR FRR* |
FRAMING, COLUMNS, BEAMS, GIRDERS, TRUSSES | 1-HR FRR* | ||
FLOOR CONSTRUCTION | 1-HR FRR* | ||
3 | BASE SUPPORT | ERECTED ON HARDBASE (CONCRETE) | REQUIRED |
B | COMPARTMENTATION | ||
1 | WALLS BETWEEN EACH COMPARTMENT | 20M MAX LENGTH OF EACH COMPARTMENT | 1-HR FRR* |
2 | WALLS BETWEEN UNITS | WITHIN EACH COMPARTMENT | NOT REQUIRED |
3 | EXIT ACCESS CORRIDORS | INTERNAL CORRIDORS | 1/2-HR FRR* |
OPEN-SIDED CORRIDORS | NOT REQUIRED | ||
FIRE DOORS (INTERNAL CORRIDORS) | 1/2-HR FRR* | ||
VII | FIRE PROTECTION | ||
A | DETECTION ALARM AND COMMUNICATION SYSTEMS | ||
1 | FIRE ALARM SYSTEM | STAND ALONE DETECTORS (SMOKE ALARMS WIRED AND/OR BATTERY OPERATED) | PERMITTED |
MANUAL CALL POINT | REQUIRED | ||
B | EXTINGUISHING REQUIREMENTS | ||
1 | PORTABLE FIRE EXTINGUISHERS | AT ENTRANCE IN EVERY UNIT | REQUIRED |
NEXT TO EVERY STAIRCASE AT EACH FLOOR | REQUIRED | ||
2 | FIRE HOSE REELS | 25 MM DIAMETER HOSE | REQUIRED |
3 | FIRE HYDRANTS | TEMPORARY BUILDINGS >100M AWAY FROM PUBLIC ROAD | NOT REQUIRED |
C | AIR-CONDITIONING & MECHANICAL VENTILATION | ||
1 | ALL HABITABLE ROOMS | NATURAL OR MECHANICAL VENTILATION | REQUIRED |
OPENINGS FOR AIR-CIRCULATION | REQUIRED |