COLLEGE DORMITORIES / STUDENT HOUSING / MILITARY BARRACKS / LABOR/WORKERS & STAFF HOUSING.
A BUILDING OR GROUP OF BUILDINGS THAT PROVIDES SLEEPING ACCOMODATIONS ON A TRANSIENT OR PERMANENT BASIS WITH OR WITHOUT MEALS BUT WITHOUT SEPARATE COOKING FACILITIES FOR INDIVIDUAL OCCUPANTS
| VII |
FIRE PROTECTION (FRR* FIRE RESISTANCE RATING / FPR** FIRE PROTECTION RATING) |
HIGH-RISE DORMITORY & ACCOMODATIONS BUILDINGS |
| A |
DETECTION ALARM AND COMMUNICATION SYSTEMS |
|
|
| 1 |
FIRE ALARM SYSTEM |
COMPLYING WITH NFPA 72 |
REQUIRED |
| B |
EXTINGUISHING REQUIREMENTS |
COMPLIANCE WITH INDIVIDUAL CODES & STANDARDS |
REQUIRED |
| 1 |
PORTABLE FIRE EXTINGUISHERS |
TYPE AND RATING IN ACCORDANCE WITH NFPA 10 |
REQUIRED |
| 2 |
FIRE BLANKETS |
IN KITCHEN OR PANTRY |
REQUIRED |
| 3 |
STANDPIPE SYSTEM |
BUILDING EXCEEDING 9M IN HABITABLE HEIGHT |
REQUIRED |
| 4 |
FIRE HOSE REELS |
25MM DIAMETER HOSE |
REQUIRED |
| 5 |
AUTOMATIC SPRINKLER SYSTEM |
THROUGHOUT PROTECTION (ALL FLOOR LEVELS) |
REQUIRED |
| IN BASEMENTS IRREGARDLESS OF USAGE |
REQUIRED |
| ACCOMODATIONS OF NOT MORE THAN 2 STORIES & FLOOR AREA NOT EXCEEDING 1115 SQM, PROVIDED WITH NOT LESS THAN 2-EXITS COMPLYING WITH EXIT DISCHARGE REQUIREMENTS |
NOT APPLICABLE |
| SLEEPING ROOMS HAVING A DOOR OPENING DIRECTLY OUTSIDE AT THE STREET LEVEL |
NOT APPLICABLE |
| SLEEPING ROOMS HAVING AN EXTERIOR ACCESS COMPLYING WITH CHAPTER 7 OF NFPA 101 |
NOT APPLICABLE |
| 6 |
OTHER EXTINGUISHING EQUIPMENT |
PROVIDED IN LIEAU OF THE REQUIRED DRAFTSTOPS IN CONCEALED SPACES |
PERMITTED |