| IV | MEANS OF EGRESS | SECONDARY SCHOOL | |||
|---|---|---|---|---|---|
| FIRE SAFETY PROVISIONS | MINIMUM REQUIREMENTS | ||||
| A | MEANS OF EGRESS GENERAL REQUIREMENTS | ||||
| 1 | SEPARATION OF MEANS OF EGRESS | ||||
| EXIT ACCESS CORRIDORS | SERVING AN AREA HAVING AN OCCUPANT LOAD EXCEEDING 30 | 1-HR FRR* | |||
| EXITS ENCLOSURE | CONNECTS 3 OR FEWER STORIES | 1-HR FRR* | |||
| OPENING PROTECTIVE | FIRE DOOR ASSEMBLIES EQUIPPED WITH DOOR CLOSERS | REQUIRED | |||
| CONSTRUCTION | LIMITED OR NON-COMBUSTIBLE MATERIALS | REQUIRED | |||
| OPENINGS AND PENETRATIONS IN EXIT ENCLOSURE | COMPLYING WITH CHAPTER 7 NFPA 101 | REQUIRED | |||
| 2 | EXITS HEADROOM (STAIRS) | NOT LESS THAN 2285MM | REQUIRED | ||
| 3 | WALKING SURFACES IN THE MEANS OF EGRESS | COMPLYING WITH CHAPTER 7 NFPA 101 | REQUIRED | ||
| 4 | CHANGES IN LEVEL IN THE MEANS OF EGRESS | COMPLYING WITH CHAPTER 7 NFPA 101 | REQUIRED | ||
| 5 | GUARDS | PROVIDED AT THE OPEN SIDES OF MEANS OF EGRESS | REQUIRED | ||
| 760MM ABOVE THE FLOOR OR FINISHED GROUND LEVEL | |||||
| 6 | IMPEDIMENT TO EGRESS | NOT PERMITTED | |||
| 7 | MEANS OF EGRESS RELIABILITY | CONTINUOUSLY MAINTAINED FREE OF ALL OBSTRUCTION OR IMPEDIMENTS | REQUIRED | ||
| 8 | FURNISHING AND DECORATION | FURNITURES, MOVABLE OBJECTS, MIRRORS, ETC. | NOT PERMITTED | ||
| CLOTHING & PERSONAL EFFECTS | STORED IN NON-SPRINKLER PROTECTED CORRIDORS | NOT PERMITTED | |||
| STORED IN SPRINKLER PROTECTED CORRIDORS | PERMITTED | ||||
| IN CORRIDORS PROVIDED WITH SMOKE DETECTION | |||||
| STORAGE IN METAL LOCKERS ALONG CORRIDORS | PERMITTED PROVIDED REQUIRED EGRESS MAINTAINED | ||||
| ART WORK & TEACHING MATERIALS | SPRINKLER PROTECTED | NOT MORE THAN 50% OF THE WALL AREA | |||
| NOT SPRINKLER PROTECTED | NOT MORE THAN 20% OF THE WALL AREA | ||||
| B | MEANS OF EGRESS COMPONENTS | ||||
| 1 | FIRE DOORS | COMPLYING WITH CHAPTER 7 NFPA 101 | |||
| SIDE-HINGE OR PIVOTED-SWINGING TYPE | ANY DOOR ASSEMBLY IN A MEANS OF EGRESS | REQUIRED | |||
| MINIMUM DOOR LEAF WIDTH | 810MM | ||||
| HORIZONTAL SLIDING DOORS | COMPLYING WITH CHAPTER 7 NFPA 101 | NOT PERMITTED | |||
| VERTICAL ROLLING DOORS | COMPLYING WITH CHAPTER 7 NFPA 101 | NOT PERMITTED | |||
| REVOLVING DOORS / POWERED DOORS | COMPLYING WITH CHAPTER 7 NFPA 101 | ||||
| SELF-CLOSING DEVICES | DOORS REQUIRED TO BE NORMALLY KEPT CLOSED | REQUIRED | |||
| 2 | STAIRS | ||||
| STANDARD STAIRS | FEWER THAN 50 PERSON (CLEAR WIDTH) | 915MM | |||
| <2000 PERSON (CLEAR WIDTH) | 1120MM | ||||
| >2000 PERSON (CLEAR WIDTH) | 1420MM | ||||
| SPRIRAL STAIRS | COMPLYING WITH CHAPTER 7 NFPA 101 | NOT PERMITTED | |||
| CURVE STAIRS | COMPLYING WITH CHAPTER 7 NFPA 101 | ||||
| WINDERS | COMPLYING WITH CHAPTER 7 NFPA 101 | ||||
| GUARDS AND HANDRAILS | COMPLYING WITH CHAPTER 7 NFPA 101 | REQUIRED | |||
| ENCLOSURE AND PROTECTION OF STAIRS | |||||
| ENCLOSURES | ALL INSIDE STAIR SERVING AS AN EXIT COMPONENT | REQUIRED | |||
| DOORS FPR* | < 3 STOREYS / > 3 STOREYS | 1-HR FPR** | |||
| ENCLOSURES FRR* | < 3 STOREYS / > 3 STOREYS | 1-HR FRR** | |||
| ENCLOSURE EXEMPTION | PENETRATING ONE FLOOR LEVEL OR SERVING MEZZANINE ONLY | NOT PERMITTED | |||
| EXPOSURES | WALLS AND OPENINGS WITHIN 3050MM HORIZONTALLY OF AN EXTERIOR STAIRWAY ENCLOSURE | 1-HR FRR* | |||
| USABLE SPACE | WITHIN EXIT ENCLOSURE | NOT PERMITTED | |||
| LOCATION UNDER STAIRS IN ACCORDANCE WITH NFPA 101 | PERMITTED | ||||
| STAIRWAY IDENTIFICATION | SERVING 3 OR MORE STOREYS | REQUIRED | |||
| EXIT STAIR PATH MARKINGS | ALL STAIR COMPONENTS | REQUIRED | |||
| PERIMETER DEMARCATION MARKING | COMPLYING WITH NFPA 101 | ||||
| LOCK, LATCHES & ALARM DEVICES | COMPLYING WITH NFPA 101 | PERMITTED | |||
| RE-ENTRY PROVISIONS | LOCKED STAIRS EXCEEDING 4 STOREYS | NOT APPLICABLE | |||
| 3 | RAMPS | COMPLYING WITH CHAPTER 7 NFPA 101 | REQUIRED | ||
| AS SECONDARY EXIT FOR ONE (1) BASEMENT LEVEL | NOT PERMITTED | ||||
| 4 | ROOF ACCESS | BUILDING EQUAL OR MORE THAN 4 STOREYS (G+3) OR ROOFS 12M ABOVE GRADE PLANE | REQUIRED | ||
| WHERE OPEN STAIR/S ARE PERMITTED | |||||
| ONE AT EACH 9300 SQM ROOF AREA OR FLAT ROOFS OR ROOF PITCH <3 IN 12 | |||||
| ROOF ACCESS COMPONENTS | SMOKE VENTS (FIXED WALL OPENING/S) AT THE TOP OF THE STAIRWELL WITH A MINIMUM AREA OF 1.5 SQM | REQUIRED | |||
| STAIR ACCESS TO ROOF EQUIPPED WITH OPERABLE DOORS | |||||
| 5 | SMOKE PROOF ENCLOSURES | FRR* (FIRE RESISTANCE RATING) | |||
| STAIR ENCLOSURES | ALL INSIDE STAIRS SERVING AS AN EXIT COMPONENT | REQUIRED | |||
| OPEN STAIR PENETRATING ONE (1) FLOOR / LEVEL ONLY | PERMITTED IF UTILIZED AS AN ACCESS AND NOT AS AN EXIT COMPONENT | ||||
| FIRE FIGHTING LOBBY (F/F LOBBY) | PROVISIONS AT THE LEVEL OF EXIT DISCHARGE | NOT REQUIRED | |||
| LOBBY DOORS & WALL ENCLOSURES | 1.5-HR FPR** FIRE PROTECTION RATING/ FRR* 2-HRS FIRE RESISTANCE RATING | ||||
| SMOKE-STOP LOBBY (VESTIBULE) | PROVISIONS AT THE LEVEL OF EXIT DISCHARGE | ||||
| 6 | HORIZONTAL EXITS | COMPLYING WITH CHAPTER 7 NFPA 101 | 1-HR FRR* | ||
| 7 | EXIT PASSAGEWAYS | ENCLOSURE AND SEPARATION FIRE RESISTANCE RATING COMPLYING WITH CHAPTER 7 NFPA 101 | REQUIRED | ||
| MIN. WIDTH NOT LESS THAN 2/3 OF THE WIDTH OF THE EXIT STAIR | |||||
| 8 | FIRE ESCAPE STAIRS | COMPLYING WITH CHAPTER 7 NFPA 101 | PERMITTED | ||
| 9 | FIRE ESCAPE LADDERS | COMPLYING WITH CHAPTER 7 NFPA 101 | NOT PERMITTED | ||
| 10 | AREAS OF REFUGE | COMPLYING WITH CHAPTER 7 NFPA 101 | REQUIRED | ||
| 11 | ELEVATORS | AS PART OF THE REQUIRED MEANS OF EGRESS | NOT PERMITTED | ||
| AS SECOND MEANS OF EGRESS | |||||
| ELEVATOR DOORS | OPENING INTO EXIT ENCLOSURES | ||||
| C | CAPACITY OF MEANS OF EGRESS | ||||
| 1 | OCCUPANT LOAD | CLASSROOMS | 1.9 NET SQM/PERSON | ||
| SHOPS, LABORATORIES, VOCATIONAL ROOMS | 4.6 NET SQM/PERSON | ||||
| 2 | EGRESS CAPACITY | STAIRWAYS | 7.6MM | ||
| LEVEL COMPONENTS & RAMPS | 5.0MM | ||||
| 3 | EXIT ACCESS CORRIDORS | REQUIRED MINIMUM CLEAR WIDTH | 1830MM | ||
| D | NUMBER OF EXITS | ||||
| 1 | SINGLE EXIT | ONLY ONE (1) ON EVERY STORY | NOT PERMITTED | ||
| 2 | NOT LESS THAN 2 SEPARATE EXITS (MINIMUM) | REQUIREMENTS FOR ANY NUMBER OF OCCUPANTS | REQUIRED | ||
| 3 | NOT LESS THAN THREE (3) SEPARATE EXITS | EQUAL OR MORE THAN 500 OCCUPANTS | |||
| 4 | NOT LESS THAN FOUR (4) SEPARATE EXITS | EQUAL OR MORE THAN 1000 OCCUPANTS | |||
| E | ARRANGEMENT OF EXITS | NS*-NOT SPRINKLERED / S**-SPRINKLERED | NS* | S** | |
| 1 | TRAVEL DISTANCE | IN ACCORDANCE WITH NFPA 101 TABLE A.7.6 | 46M | 61M | |
| 2 | COMMON PATH LIMIT | IN ACCORDANCE WITH NFPA 101 TABLE A.7.6 | 23M | 30M | |
| 3 | DEAD-END CORRIDOR | IN ACCORDANCE WITH NFPA 101 TABLE A.7.6 | 6.1M | 15M | |
| 4 | ROOM OR SPACES WITH MORE THAN 93 SQM OR WITH AN OCCUPANT LOAD OF MORE THAN 50 PERSONS | MINIMUM TWO (2) ACCESS DOORS | REQUIRED | ||
| REQUIRED DOORS ARRANGED TO PROVIDE ACCESS TO SEPARATE EXITS | |||||
| DOORS OPEN INTO THE DIRECTION OF EXIT TRAVEL | |||||
| 5 | EVERY ROOM NORMALLY SUBJECT TO STUDENT OCCUPANCY | EXIT ACCESS DOORS LEADS DIRECTLY TO AN EXIT ACCESS CORRIDOR OR EXIT | REQUIRED | ||
| 6 | DOORS SWINGING INTO EXIT ACCESS CORRIDOR | ACCESS DOORS ARRANGED TO PREVENT INTERFERENCE WITH CORRIDOR TRAVEL | REQUIRED | ||
| 7 | AISLE | MINIMUM AISLE WIDTH | 760MM | ||
| 8 | SPACES BETWEEN PARALLEL ROWS OF SEATS SUBJECT TO THE MINIMUM AISLE WIDTH | THE NUMBER OF SEATS THAT INTERVENES BETWEEN ANY SEAT AND AN AISLE DOES NOT EXCEED SIX (6) | NOT REQUIRED | ||
| 9 | EXIT DISCHARGE | ||||
| EXTERIOR DISCHARGE | DIRECT TO BUILDING EXTERNAL | REQUIRED | |||
| THROUGH AREAS ON LEVEL OF EXIT DISCHARGE | MAXIMUM 10M TRAVEL DISTANCE TO BUILDING EXTERNAL | PERMITTED WHEN PROTECTED THROUGHOUT WITH SPRINKLER SYSTEM | |||
| 50% OF THE REQUIRED NUMBER OF EXITS AND 50% OF THE REQUIRED EXIT CAPACITY | |||||
| 10 | EXTERIOR WAYS OF EXIT | COMPLYING WITH NFPA 101 | PERMITTED | ||
| 11 | ACCESIBLE MEANS OF EGRESS | EXIT & ACCESS PROVISIONS FOR PEOPLE WITH SEVERE MOBILITY IMPAIRMENT | NOT LESS THAN 2 EXITS REQUIRED | ||
| 12 | ILLUMINATION OF MEANS OF EGRESS | COMPLYING WITH CHAPTER 7 NFPA 101 | REQUIRED | ||
| 13 | EMERGENCY LIGHTING | COMPLYING WITH CHAPTER 7 NFPA 101 | |||
| 14 | MARKINGS OF MEANS OF EGRESS | COMPLYING WITH CHAPTER 7 NFPA 101 | |||
| F | SPECIAL MEANS OF EGRESS PROVISIONS | ||||
| 1 | FIREMEN ACCESS PANELS | HABITABLE HEIGHT EXCEEDING 10M | REQUIRED | ||
| 2 | WINDOWS FOR RESCUE | ROOMS OR SPACE GREATER THAN 23.2 SQM AND NORMALLY SUBJECT TO STUDENT OCCUPANCY | REQUIRED | ||
| BUILDING SPRINKLER PROTECTED THROUGHOUT | NOT REQUIRED | ||||
| ROOMS OR SPACE HAS DOOR LEADING DIRECTLY TO AN EXIT OR OUTSIDE THE BUILDING | NOT REQUIRED | ||||
| ROOMS LOCATED FOUR OR MORE STORIES | |||||
| 3 | LOCKUPS | DOORS & PHYSICAL RESTRAINTS TO FREE EGRESS CAN BE READILY RELEASED BY STAFF WITHIN 2 MINUTES OF ONSET OF FIRE OR ANY EMERGENCY | REQUIRED ON DOORS PROVIDED WITH LOCKUPS | ||
| 3 | ELEVATORS FOR OCCUPANT CONTROLLED EVACUATION PRIOR TO PHASE 1 EMERGENCY RECALL OPERATIONS | COMPLYING WITH CHAPTER 7 NFPA 101 | NOT PERMITTED | ||