| IV |
MEANS OF EGRESS |
TYPE-B FACILITIES |
| A |
MEANS OF EGRESS GENERAL REQUIREMENTS |
|
| 1 |
SEPARATION OF MEANS OF EGRESS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
REQUIRED |
| |
EXIT ACCESS CORRIDORS |
SERVING AN AREA HAVING AN OCCUPANT LOAD EXCEEDING 30 |
1-HR FRR* |
| |
EXITS |
CONNECTS 3 OR FEWER STORIES |
1-HR FRR* |
| |
CONNECTS 4 OR MORE STORIES |
2-HRS FRR* |
| |
OPENING PROTECTIVE |
FIRE DOOR ASSEMBLIES EQUIPPED WITH DOOR CLOSERS |
REQUIRED |
| |
CONSTRUCTION |
LIMITED OR NON-COMBUSTIBLE MATERIALS |
REQUIRED |
| |
OPENINGS AND PENETRATIONS IN EXIT ENCLOSURE |
COMPLYING WITH CHAPTER 7 NFPA 101 |
PERMITTED |
| 2 |
EXITS HEADROOM |
NOT LESS THAN 2285MM |
REQUIRED |
| |
HEADROOM ON STAIRS |
NOT LESS TAHN 2285MM |
REQUIRED |
| 3 |
WALKING SURFACES IN THE MEANS OF EGRESS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
REQUIRED |
| 4 |
CHANGES IN LEVEL IN THE MEANS OF EGRESS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
REQUIRED |
| 5 |
GUARDS |
PROVIDED AT THE OPEN SIDES OF MEANS OF EGRESS 760MM ABOVE THE FLOOR OR FINISHED GROUND LEVEL |
REQUIRED |
| 6 |
IMPEDIMENT TO EGRESS |
|
NOT PERMITTED |
| 7 |
MEANS OF EGRESS RELIABILITY |
CONTINUOUSLY MAINTAINED FREE OF ALL OBSTRUCTION OR IMPEDIMENTS |
REQUIRED |
| |
FURNISHING AND DECORATION |
FURNITURES, MOVABLE OBJECTS, MIRRORS, ETC. |
NOT PERMITTED |
| B |
MEANS OF EGRESS COMPONENTS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
|
| 1 |
FIRE DOORS |
HOSPITAL AND NURSING HOMES |
1055MM |
| NEWBORN NURSERIES AND PSYCHIATRIC HOSPITALS |
810MM |
| DOORS NOT SUBJECT TO HEALTH CARE OCCUPANT'S USE |
| EXIT ENCLOSURES |
| SIDE-HINGE OR PIVOTED-SWINGING TYPE |
ANY DOOR ASSEMBLY IN A MEANS OF EGRESS |
REQUIRED |
| MINIMUM DOOR LEAF WIDTH |
810MM |
| HORIZONTAL SLIDING DOORS |
SERVING AN OCCUPANT LOAD OF FEWER THAN 10 |
PERMITTED |
| VERTICAL ROLLING DOORS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
NOT PERMITTED |
| REVOLVING DOOR / POWERED DOORS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
NOT PERMITTED |
| SELF-CLOSING DEVICES |
IN ALL DOORS REQUIRED TO BE NORMALLY KEPT CLOSED |
REQUIRED |
| 2 |
STAIRS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
REQUIRED |
| STANDARD STAIRS |
FEWER THAN 50 PERSON (CLEAR WIDTH) |
915MM |
| <2000 PERSON (CLEAR WIDTH) |
1120MM |
| >2000 PERSON (CLEAR WIDTH) |
1420MM |
| SPRIRAL STAIRS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
NOT PERMITTED |
| CURVE STAIRS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
NOT PERMITTED |
| WINDERS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
NOT PERMITTED |
| GUARDS AND HANDRAILS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
REQUIRED |
| ENCLOSURE AND PROTECTION OF STAIRS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
REQUIRED |
| ENCLOSURES |
INTERIOR STAIR SERVING AS AN EXIT COMPONENT |
REQUIRED |
| DOORS FPR* |
< 3 STOREYS / > 3 STOREYS |
1-HR FPR** / 2-HRS FPR** |
| ENCLOSURES FRR* |
< 3 STOREYS / > 3 STOREYS |
1-HR FRR** / 2-HRS FRR** |
| ENCLOSURE EXEMPTION |
PENETRATING ONE FLOOR LEVEL OR SERVING MEZZANINE ONLY |
PERMITTED |
| EXPOSURES |
WALLS AND OPENINGS WITHIN 3050MM HORIZONTALLY OF AN EXTERIOR STAIRWAY ENCLOSURE |
1-HR FRR* |
| USABLE SPACE |
WITHIN EXIT ENCLOSURE |
NOT PERMITTED |
| UNDER STAIRS IN ACCORDANCE WITH NFPA 101 |
PERMITTED |
| STAIRWAY IDENTIFICATION |
SERVING 3 OR MORE STOREYS |
REQUIRED |
| EXIT STAIR PATH MARKINGS |
ALL STAIR COMPONENTS |
REQUIRED |
| PERIMETER DEMARCATION MARKING |
COMPLYING WITH NFPA 101 |
REQUIRED |
| LOCK, LATCHES & ALARM DEVICES |
COMPLYING WITH NFPA 101 |
PERMITTED |
| RE-ENTRY PROVISIONS |
LOCKED STAIRS EXCEEDING 4 STOREYS |
REQUIRED |
| 3 |
RAMPS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
PERMITTED |
| AS SECONDARY EXIT FOR ONE (1) BASEMENT LEVEL |
PERMITTED |
| RAMPS ENCLOSED AS EXIT SHALL BE OF SUFFICIENT WIDTH TO PROVIDE EGRESS CAPACITY |
REQUIRED |
| 4 |
ROOF ACCESS |
BUILDING EQUAL OR MORE THAN 4 STOREYS (G+3) OR ROOFS 12M ABOVE GRADE PLANE |
REQUIRED |
| WHERE OPEN STAIR/S ARE PERMITTED AND PROVIDED IN HEALTH CARE OCCUPANCY |
NOT APPLICABLE |
| ONE AT EACH 9300 SQM ROOF AREA OR FLAT ROOFS OR ROOF PITCH <3 IN 12 |
REQUIRED |
| ROOF ACCESS COMPONENTS |
SMOKE VENTS (FIXED WALL OPENING/S) AT THE TOP OF THE STAIRWELL WITH A MIN. AREA OF 1.5 SQM |
NOT APPLICABLE |
| STAIR ACCESS TO ROOF EQUIPPED WITH OPERABLE DOORS |
REQUIRED |
| 5 |
SMOKE PROOF ENCLOSURES |
FRR* (FIRE RESISTANCE RATING) |
|
| STAIR ENCLOSURES |
ALL INSIDE STAIR SERVING AS AN EXIT COMPONENT |
REQUIRED |
| OPEN STAIR PENETRATING ONE (1) FLOOR / LEVEL ONLY |
PERMITTED |
| FIRE FIGHTING LOBBY |
IN EVERY FIRE LIFT PROVISIONS |
REQUIRED IN BUILDINGS EXCEEDING 9M BELOW THE LEVEL OF EXIT DISCHARGE |
| ADJACENT AND ACCESIBLE TO AN EXIT STAIRCASE |
| SERVES AS A COMMON LOBBY FOR BOTH FIRE LIFT AND THE ADJACENT FIRE EXIT STAIRCASE |
| 6 SQM MINIMUM AREA / WORKING SPACE (LEAST SIDE DIMENSION 2.0M) |
| PROVISIONS AT THE LEVEL OF EXIT DISCHARGE |
| SMOKE-STOP LOBBY (VESTIBULE) |
HIGH-RISE BUILDINGS WITH HABITABLE HEIGHT HIGHER THAN 28 METERS |
REQUIRED |
| BASEMENT LEVEL/S EXCEED 9.0 M DEPTH |
| BUILDING TRAVERSES MORE THAN 5 FLOOR LEVELS INCLUDING BASEMENTS REGARDLESS OF THE HABITABLE HEIGHT. |
REQUIRED |
| 3 SQM MIN. AREA (LEAST SIDE DIMENSION 1.8M) |
REQUIRED |
| PROVISIONS AT THE LEVEL OF EXIT DISCHARGE |
NOT REQUIRED IF EXITS COMPLIES WITH EXIT DISCHARGE REQUIREMENTS |
| SMOKE-STOP / FIRE FIGHTING LOBBY DOORS & WALL ENCLOSURES |
1.5-HR FIRE PROTECTION RATING (FPR) / 2-HRS FIRE RESISTANCE RATING (FRR) |
REQUIRED |
| 6 |
HORIZONTAL EXITS |
AS PER CHAPTER 7 AND 18 OF NFPA 101 |
PERMITTED |
| HORIZONTAL EXIT DOORS |
APPROVED VISION PANEL |
REQUIRED |
| CENTRAL MULLIONS IN DOOR OPENINGS |
NOT PERMITTED |
| 7 |
EXIT PASSAGEWAYS |
ENCLOSURE AND SEPARATION FIRE RESISTANCE RATING COMPLYING WITH CHAPTER 7 |
REQUIRED |
| MIN. WIDTH NOT LESS THAN 2/3 EXIT STAIR WIDTH |
REQUIRED |
| 8 |
ESCALATORS & MOVING WALKS |
AS PART OF THE REQUIRED MEANS OF EGRESS |
NOT PERMITTED |
| 9 |
FIRE ESCAPE STAIRS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
PERMITTED |
| 10 |
FIRE ESCAPE LADDERS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
NOT PERMITTED |
| 11 |
SLIDE ESCAPES |
COMPLYING WITH CHAPTER 7 NFPA 101 |
NOT PERMITTED |
| 12 |
ALTERNATING TREAD DEVICES |
COMPLYING WITH CHAPTER 7 NFPA 101 |
NOT PERMITTED |
| 13 |
AREAS OF REFUGE |
COMPLYING WITH CHAPTER 7 NFPA 101 |
REQUIRED |
| 14 |
ELEVATORS |
AS PART OF THE REQUIRED MEANS OF EGRESS |
NOT PERMITTED |
| AS SECOND MEANS OF EGRESS |
NOT APPLICABLE |
| ELEVATOR DOORS |
OPENING INTO EXIT ENCLOSURES |
NOT PERMITTED |
| C |
CAPACITY OF MEANS OF EGRESS |
|
| 1 |
OCCUPANT LOAD |
NFPA 101 TABLE 7.3.1.2 OCCUPANT LOAD FACTOR |
REQUIRED |
| INPATIENT TREATMENT DEPARTMENTS |
22.3 |
| SLEEPING DEPARTMENTS |
11.1 |
| 2 |
EGRESS CAPACITY |
NFPA 101 TABLE 7.3.3.1 CAPACITY FACTORS |
REQUIRED |
| 3 |
AISLE, CORRIDORS AND RAMPS |
AS EXIT ACCESS IN HOSPITALS & NURSING HOMES |
2440MM |
| AS REQUIRED AS EXIT ACCESS IN LIMITED CARE FACILITY OR HOSPITAL FOR PSYCHIATRIC CARE |
1830MM |
| NOT INTENDED FOR IN-PATIENTS |
1120MM |
| |
CROSS CORRIDOR DOORS OPENING INTO CORRIDORS WITH THE REQUIRED WIDTH OF 2440MM |
PAIRS OF DOORS |
2110MM |
| SINGLE DOOR |
1055MM |
| CROSS CORRIDOR DOORS OPENING INTO CORRIDORS WITH THE REQUIRED WIDTH OF 1830MM |
PAIRS OF DOORS |
1625MM |
| SINGLE DOOR |
810MM |
| NO-CONTINUOUS PROJECTIONS / PROJECTIONS INTO THE REQUIRED WIDTH |
COMPLYING WITH NFPA 101 CHAPTER 18 |
REQUIRED |
| 4 |
DOOR MINIMUM CLEAR WIDTH IN SLEEPING ROOMS, DIAGNOSTIC AND TREATMENT AREAS (X-RAY, SURGERY OR PHYSICAL THERAPY) AND NURSERY ROOMS |
HOSPITALS AND NURSING HOMES |
1055MM |
| PSYCHIATRIC HOSPITALS AND LIMITED CARE FACILITIES |
810MM |
| NOT SUBJECT TO HEALTH CARE OCCUPANT |
810MM |
| EXIT STAIR ENCLOSURE |
810MM |
| NEWBORN NURSERIES |
810MM |
| |
PAIR OF DOORS |
CLEAR WIDTH OF NOT LESS THAN 1 DOOR |
810MM |
| RABBET, BEVEL/ASTRAGAL AT THE MEETING EDGE |
REQUIRED |
| AUTOMATIC FLUSH BOLT TO PROVIDE POSITIVE LATCHING IN THE INACTIVE DOOR LEAF |
REQUIRED |
| D |
NUMBER OF EXITS |
COMPLYING WITH NFPA 101 CHAPTER 7 |
|
| 1 |
SINGLE EXIT |
SERVING ALL FLOOR LEVELS |
NOT PERMITTED |
| IN MEZZANINES OR ANY SECTION WITH EXIT TRAVEL WITHIN COMMON PATH LIMIT |
PERMITTED |
| SLEEPING & NON SLEEPING ROOMS OPENING DIRECTLY INTO THE CORRIDOR WITH EXIT TRAVEL WITHIN COMMON PATH LIMIT |
PERMITTED |
| 2 |
TWO (2) SEPARATE EXITS |
MORE THAT 50 - 500 OCCUPANTS |
REQUIRED |
| ON EVERY STORY |
REQUIRED |
| ACCESIBLE FROM EVERY PART OF EVERY STORY |
REQUIRED |
| SMOKE COMPARTMENTS |
REQUIRED |
| PATIENTS SLEEPING ROOM >93SQM |
REQUIRED |
| NON-SLEEPING ROOMS >230 SQM |
REQUIRED |
| 3 |
THREE (3) SEPARATE EXITS |
EQUAL OR MORE THAN 500 OCCUPANTS |
REQUIRED |
| 4 |
FOUR (4) SEPARATE EXITS |
EQUAL OR MORE THAN 1000 OCCUPANTS |
REQUIRED |
| E |
ARRANGEMENT OF EXITS |
NS*-NOT SPRINKLERED / S**-SPRINKLERED |
NS* |
S** |
| 1 |
TRAVEL DISTANCE |
MAXIMUM TRAVEL DISTANCE INCLUDES EXIT TRAVEL FROM NON-PATIENT CARE SUITE |
N/A |
61M |
| |
SLEEPING SUITE |
ANY POINT IN A SLEEPING SUITE & AN EXIT ACCESS DOOR |
NA |
30 |
| BETWEEN ANY POINT IN A SLEEPING SUITE & EXIT |
NA |
61M |
| |
PATIENT CARE NON-SLEEPING SUITES |
WITHIN A NON-SLEEPING SUITES TO AN EXIT ACCESS DOOR |
NA |
30 |
| BETWEEN ANY POINT IN A SLEEPING SUITE & AN EXIT |
NA |
61M |
| 2 |
COMMON PATH LIMIT |
NFPA 101 TABLE A.7.6 |
NA |
30M |
| 3 |
DEAD-END CORRIDOR |
NFPA 101 TABLE A.7.6 |
NA |
9.1M |
| 4 |
SLEEPING SUITE ARRANGEMENT |
COMPLYING WITH NFPA 101 CHAPTER 18 |
REQUIRED |
| MAXIMUM SIZE |
700 SQM |
| MAXIMUM SIZES CONDITIONS* |
PROVIDED WITH STAFF DIRECT VISUAL SUPERVISION |
930 SQM PERMITTED WITH CONDITIONS* |
| TOTAL COVERAGE (COMPLETE) AUTOMATIC SMOKE DETECTION |
| 5 |
PATIENT CARE NON-SLEEPING SUITES |
COMPLYING WITH NFPA 101 CHAPTER 18 |
REQUIRED |
| MAXIMUM SIZE |
930 SQM |
| 6 |
NON-PATIENT-CARE SUITES |
EGRESS PROVISIONS IN ACCORDANCE WITH THE PRIMARY USE AND OCCUPANCY OF SPACE |
REQUIRED |
| 7 |
EXIT DISCHARGE |
|
|
| |
EXTERIOR DISCHARGE (DIRECT TO BUILDING EXTERNAL) |
COMPLYING WITH NFPA 101 |
REQUIRED |
| |
THROUGH AREAS ON LEVEL OF EXIT DISCHARGE |
MAXIMUM 10M TRAVEL DISTANCE TO BUILDING EXTERNAL |
PERMITTED |
| 50% OF REQUIRED NUMBER OF EXITS AND 50% OF REQUIRED EXIT CAPACITY (SPRINKLER PROTECTED) |
PERMITTED |
| 8 |
EXTERIOR WAYS OF EXIT |
COMPLYING WITH NFPA 101 |
PERMITTED |
| 9 |
ACCESIBLE MEANS OF EGRESS |
EXIT PROVISIONS FOR PEOPLE WITH SEVERE MOBILITY IMPAIRMENT |
REQUIRED |
| NOT LESS THAN TWO (2) EXITS |
REQUIRED |
| 10 |
ILLUMINATION OF MEANS OF EGRESS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
REQUIRED |
| 11 |
EMERGENCY LIGHTING |
COMPLYING WITH CHAPTER 7 NFPA 101 |
REQUIRED |
| |
EQUIPPED WITH LIFE SUPPORT SYSTEM |
EMERGENCY LIGHTING EQUIPMENT SUPPLIED BY THE LIFE SAFETY BRANCH OF THE ELECTRICAL SYSTEM AS PER NFPA 99 HEALTH CARE FACILITIES CODE |
REQUIRED |
| 12 |
MARKINGS OF MEANS OF EGRESS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
REQUIRED |
| ACCESS TO EXITS WITHIN SLEEPING ROOMS WHERE STAFF IS RESPONSIBLE FOR RELOCATING OR EVACUATING OCCUPANTS |
NOT REQUIRED |
| |
ILLUMINATION OF REQUIRED EXIT AND DIRECTIONAL SIGNS |
SUPPLIED BY THE LIFE SAFETY BRANCH OF THE ELECTRICAL SYSTEM (NFPA 99 HEALTH CARE CODE) |
REQUIRED |
| SELF-LUMINOUS EXIT SIGNS |
PERMITTED |
| F |
SPECIAL MEANS OF EGRESS PROVISIONS |
|
|
| 1 |
FIREMEN ACCESS PANELS |
HABITABLE HEIGHT EXCEEDING 10M |
REQUIRED |
| 2 |
REFUGE FLOORS |
BUILDING EXCEEDIGN 30 STORIES |
NOT REQUIRED |
| 3 |
ELEVATORS FOR OCCUPANT CONTROLLED EVACUATION PRIOR TO PHASE 1 EMERGENCY RECALL OPERATIONS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
PERMITTED |