BUILDING AND SITE ACCESS FOR FIRE FIGHTING & RESCUE |
LOW-RISE HOTEL |
A |
SITE ACCESS |
4.0M MINIMUM CLEAR WIDTH |
REQUIRED |
4.5M MINIMUM CLEAR HEIGHT |
B |
ACCESS ROAD |
4.0M MIN. WIDTH AND 24 TON LOAD CAPACITY |
REQUIRED |
WITHIN A TRAVEL DISTANCE OF 45M FROM EVERY POINT ON PROJECTED PLAN AREA OF ANY BUILDING. |
C |
FIRE ENGINE HARDSTANDING |
LENGTH OR NUMBER BASE ON THE GROSS FLOOR AREA OF THE BUILDING |
REQUIRED WHEN BUILDING HABITABLE HEIGHT EXCEEDS 10M |
6M X 15M (MINIMUM), WITH LONGER SIDE PARALLEL TO THE FACADE OF THE BUILDING |
POSITIONED SO THAT THE NEARER EDGE SHALL BE NOT LESS THAN 2M OR NOT MORE THAN 10M FROM THE CENTER POSITION OF THE ACCESS OPENING, MEASURED HORIZONTALLY. |
D |
FIRE COMMAND CENTER |
HIGH-RISE BUILDING AND OTHER THAN HIGH-RISE WITH EMERGENCY VOICE COMMUNICATION SYSTEM AND/OR SMOKE CONTROL SYSTEM |
REQUIRED |
9 SQM MINIMUM AREA (LEAST DIMENSION 2.5M) |
WITH 1M CLEARANCE FROM ALL EQUIPMENT |
2-HOURS ENCLOSURES (WALLS, OPENINGS & PENETRATIONS) |
PROVIDED WITH PROMINENTLY MARKED EXTERIOR ENTRANCES |
INSTEAD OF A DEDICATED FIRE RATED ROOM: LOBBIES OR OTHER SPACES ADJACENT TO THE MAIN ENTRANCE OF THE BUILDING |
PERMITTED |
E |
FIRE LIFT |
BUILDINGS EQUAL OR MORE THAN 28M HIGH ABOVE ENGINE ACCESS LEVEL |
NOT APPLICABLE |
BUILDINGS EXCEEDING 9.0M BELOW THE LEVEL OF EXIT DISCHARGE |
REQUIRED |
SERVES ALL HABITABLE FLOORS |
REQUIRED IN EVERY FIRE SERVICE ACCESS ELEVATOR/FIRE LIFT PROVISIONS |
CONTAINED WITHIN A DEDICATED PROTECTED SHAFT |
APPROACHED BY FIRE FIGHTING LOBBY AT EACH STOREY |
ADJACENT AND ACCESIBLE TO AN EXIT STAIRCASE |
FIRE SERVICE ACCESS ELEVATORS / FIRE LIFT AS PER NFPA 5000 (2012 ed.) CHAP.54.12 |
NOT REQUIRED |
AMBULANCE STRETCHER ACCOMODATION ELEVATOR/LIFT AS PER NFPA 5000 (2012 ed.) CHAP.54.3 |
NOT REQUIRED |
WHEN REQUIRED, AT LEAST ONE (1) FIRE LIFT FOR EVERY 900 SQM. FLOOR AREA |
REQUIRED IN EVERY FIRE LIFT PROVISIONS |