| VII | FIRE PROTECTION (FRR* FIRE RESISTANCE RATING / FPR** FIRE PROTECTION RATING) | HIGH-RISE HOTEL | |
|---|---|---|---|
| A | DETECTION ALARM AND COMMUNICATION SYSTEMS | ||
| 1 | FIRE ALARM SYSTEM | COMPLYING WITH NFPA 72 | REQUIRED |
| CARBON MONOXIDE ALARMS AND DETECTION SYSTEM | GUEST ROOM/SUITES WITH COMMUNICATING ATTACHED GARAGE | REQUIRED | |
| GUEST ROOM/SUITES CONTAINING A PERMANENTLY INSTALLED FUEL-BURNING APPLIANCE | REQUIRED | ||
| IN GARAGE | NOT REQUIRED | ||
| GUEST ROOMS/SUITES WITH COMMUNICATING ATTACHED GARAGE THAT ARE CONSIDERED AS OPEN PARKING STRUCTURE | NOT REQUIRED | ||
| GUEST ROOMS/SUITES WITH COMMUNICATING ATTACHED GARAGE THAT ARE MECHANICALLY VENTILATED | NOT REQUIRED | ||
| B | EXTINGUISHING REQUIREMENTS | COMPLIANCE WITH INDIVIDUAL CODES & STANDARDS | REQUIRED |
| 1 | PROTABLE FIRE EXTINGUISHERS | TYPE AND RATING IN ACCORDANCE WITH NFPA 10 | REQUIRED |
| 2 | FIRE BLANKETS | IN KITCHEN OR PANTRY | REQUIRED |
| 3 | STANDPIPE SYSTEM | BUILDING EXCEEDING 9M IN HABITABLE HEIGHT | REQUIRED |
| 4 | FIRE HOSE REELS | 25MM DIAMETER HOSE | REQUIRED |
| 5 | AUTOMATIC SPRINKLER SYSTEM | THROUGHOUT PROTECTION | REQUIRED |
| WITH GUEST ROOMS OR GUEST SUITES HAVING A DOOR OPENING DIRECTLY OUTSIDE AT THE STREET LEVEL | NOT APPLICABLE | ||
| WITH GUEST ROOMS OR GUEST SUITES HAVING AN EXTERIOR ACCESS COMPLYING WITH CHAPTER 7 OF NFPA 101 | NOT APPLICABLE | ||
| PROVIDED IN LIEAU OF THE REQUIRED DRAFTSTOPS IN CONCEALED SPACES | PERMITTED | ||
| ONE BASEMENT LEVEL USED AS CARPARK ONLY (WITH FLOOR AREA EXCEEDING 1115 SQM) | REQUIRED | ||
| ONE BASEMENT LEVEL USED AS MIXED OCCUPANCY | REQUIRED | ||
| BUILDING HAS MORE THAN ONE BASEMENT LEVEL | REQUIRED | ||
| 6 | OTHER EXTINGUISHING EQUIPMENT | COMPLIANCE FROM INDIVIDUAL NFPA CODES & STANDARDS | NOT REQUIRED |