| IV | MEANS OF EGRESS | VILLAS TO PRE-SCHOOL | ||
|---|---|---|---|---|
| FIRE SAFETY PROVISIONS | MINIMUM REQUIREMENTS | |||
| A | MEANS OF EGRESS GENERAL REQUIREMENTS | |||
| 1 | GUARDS | PROVIDED AT THE OPEN SIDES OF MEANS OF EGRESS 760MM ABOVE THE FLOOR OR FINISHED GROUND LEVEL | REQUIRED | |
| 2 | IMPEDIMENT TO EGRESS & MEANS OF EGRESS RELIABILITY | CONTINUOUSLY MAINTAINED FREE OF ALL OBSTRUCTION OR IMPEDIMENTS | REQUIRED | |
| 3 | FURNISHING AND DECORATION | FURNITURES, MOVABLE OBJECTS, MIRRORS, ETC. | NOT PERMITTED | |
| ART WORK & TEACHING MATERIALS | COVERAGE NOT TO EXCEED 20% OF THE WALL AREA | REQUIRED | ||
| B | MEANS OF EGRESS COMPONENTS | |||
| 1 | FIRE DOORS | FRR* FIRE PROTECTION RATING | 1-HR FPR* | |
| SIDE-HINGE OR PIVOTED-SWINGING TYPE | ANY DOOR ASSEMBLY IN A MEANS OF EGRESS | REQUIRED | ||
| MINIMUM DOOR LEAF WIDTH | 810MM | |||
| SELF-CLOSING DEVICES | DOORS REQUIRED TO BE NORMALLY KEPT CLOSED | REQUIRED | ||
| 2 | STAIRS | COMPLYING WITH CHAPTER 7 NFPA 101 | ||
| STANDARD STAIRS | FEWER THAN 50 PERSON (CLEAR WIDTH) | NOT APPLICABLE | ||
| MORE THAN 50 PERSON (CLEAR WIDTH) | NOT APPLICABLE | |||
| GUARDS AND HANDRAILS | COMPLYING WITH CHAPTER 7 NFPA 101 | REQUIRED | ||
| STAIRWAY IDENTIFICATION & EXIT STAIR PATH MARKINGS | ALL STAIR COMPONENTS | NOT APPLICABLE | ||
| 3 | STAIR ENCLOSURES | ALL INSIDE STAIRS SERVING AS AN EXIT COMPONENT | NOT APPLICABLE | |
| 4 | FIRE FIGHTING LOBBY | COMPLYING WITH ALL FF LOBBY REQUIREMENTS | NOT APPLICABLE | |
| 5 | SMOKE-STOP LOBBY (VESTIBULE) | COMPLYING WITH ALL SS LOBBY REQUIREMENTS | NOT APPLICABLE | |
| 6 | FIRE ESCAPE STAIRS (EXTERNAL EXIT STAIR) | AS SECONDARY MEANS OF EXIT | NOT APPLICABLE | |
| C | CAPACITY OF MEANS OF EGRESS | |||
| 1 | OCCUPANT LOAD | NFPA 101 TABLE 7.3.1.2 OCCUPANT LOAD FACTOR | 3.3 NET SQM / PERSON | |
| AGES 0-24 MONTHS OLD | 1:3 STAFF TO CHILD RATIO | |||
| AGES 25-36 MONTHS OLD | 1:4 STAFF TO CHILD RATIO | |||
| AGES 37-60 MONTHS OLD | 1:7 STAFF TO CHILD RATIO | |||
| CLASSROOMS | CHILD TO STAFF RATIO APPLIES | |||
| SHOPS & LABORATORIES | CHILD TO STAFF RATIO APPLIES | |||
| D | NUMBER OF EXITS | |||
| 1 | SINGLE EXIT | NOT PERMITTED | ||
| 2 | NOT LESS THAN 2 SEPARATE EXITS | PROVIDED ON EVERY STORY | REQUIRED | |
| ACCESIBLE FROM EVERY PART OF EVERY STORY | ||||
| E | ARRANGEMENT OF EXITS | NS*-NOT SPRINKLERED / S**-SPRINKLERED | NS* | S** |
| 1 | TRAVEL DISTANCE | NFPA 1-1 TABLE A.7.6 | 30M | NA |
| BETWEEN ANY ROOM DOOR INTENDED AS EXIT ACCESS ANS AS AN EXIT | 30M | NA | ||
| BETWEEN ANY POINT IN A ROOM TO AN EXIT | 46M | NA | ||
| BETWEN ANY POINT IN CHILDRENS SLEEPING ROOM AND AN EXIT ACCESS DOOR IN THAT ROOM | 15M | NA | ||
| 2 | COMMON PATH LIMIT | NFPA 101 TABLE A.7.6 | 23M | NA |
| 3 | DEAD-END CORRIDOR | NFPA 101 TABLE A.7.6 | 6.1M | NA |
| 4 | ROOM OR SPACES WITH MORE THAN 93 SQM OR WITH AN OCCUPANT LOAD OF MORE THAN 50 PERSONS | MINIMUM TWO (2) ACCESS DOORS | REQUIRED | |
| REQUIRED DOORS ACCESS TO SEPARATE EXITS | ||||
| DOORS OPEN INTO THE DIRECTION OF EXIT TRAVEL | ||||
| 5 | EVERY ROOM NORMALLY SUBJECT TO STUDENT OCCUPANCY | EXIT ACCESS DOORS LEADS DIRECTLY TO AN EXIT ACCESS CORRIDOR OR EXIT | REQUIRED | |
| 6 | DOORS SWINGING INTO EXIT ACCESS CORRIDOR | ARRANGED TO PREVENT INTERFERENCE WITH CORRIDOR TRAVEL | REQUIRED | |
| 7 | AISLES | MINIMUM AISLE WIDTH | 760MM | |
| 8 | SPACES (AISLE) BETWEEN PARALLEL ROWS OD SEATS | MINIMUM WIDTH 760MM | NOT REQUIRED IF THE NUMBER OF SEATS THAT INTERVENES BETWEEN ANY SEAT AND AN AISLE DOES NOT EXCEED SIX (6) | |
| 9 | EXIT DISCHARGE (DIRECT TO BUILDING EXTERNAL) | COMPLYING WITH CHAPTER 7 NFPA 101 | REQUIRED | |
| 10 | ACCESIBLE MEANS OF EGRESS | EXIT PROVISIONS FOR PEOPLE WITH SEVERE MOBILITY IMPAIRMENT (NOT LESS THAN 2 EXITS REQUIRED) | 2 EXIT REQUIRED | |
| 11 | ILLUMINATION OF EXITS / EMERGENCY LIGHTING | COMPLYING WITH CHAPTER 7 NFPA 101 | REQUIRED | |
| 12 | MARKINGS OF MEANS OF EGRESS | COMPLYING WITH CHAPTER 7 NFPA 101 | REQUIRED | |
| F | SPECIAL MEANS OF EGRESS PROVISIONS | |||
| 1 | FIREMEN ACCESS PANELS | HABITABLE HEIGHT EXCEEDING 10M | NOT REQUIRED | |
| 2 | WINDOWS FOR RESCUE | ROOMS OR SPACE GREATER THAN 23.2 SQM AND NORMALLY SUBJECT TO STUDENT OCCUPANCY | REQUIRED | |
| 3 | LOCKUPS | DOORS AND PHYSICAL RESTRAINTS TO FREE EGRESS CAN BE READILY RELEASED BY STAFF WITHIN 2 MINUTES OF ONSET OF FIRE OR SIMILAR EMERGENCY | REQUIRED ON DOORS PROVIDED WITH LOCKUPS | |