VII | FIRE PROTECTION (NR-NOT REQUIRED / R-REQUIRED) | HIGH HAZARD INDUSTRIAL BUILDINGS | ||
---|---|---|---|---|
A | DETECTION ALARM AND COMMUNICATION SYSTEMS | |||
1 | FIRE ALARM SYSTEM | COMPLYING WITH NFPA 72 | REQUIRED | |
B | EXTINGUISHING REQUIREMENTS | |||
1 | PROTABLE FIRE EXTINGUISHERS | TYPE AND RATING IN ACCORDANCE WITH NFPA 10 | REQUIRED | |
2 | FIRE BLANKETS | IN KITCHEN OR PANTRY | REQUIRED | |
3 | STANDPIPE SYSTEM | COMPLYING WITH NFPA 14 | REQUIRED | |
4 | FIRE HOSE REELS | 25MM DIAMETER HOSE | REQUIRED | |
5 | AUTOMATIC SPRINKLER SYSTEM | LOW HAZARD | ORDINARY | |
3 OR MORE STORIES IN HEIGHT | NR | R | ||
FIRE AREA EXCEEDING 1115 SQM | NR |
R | ||
TOTAL AREA OF ALL FLOORS EXCEEDS 2230 SQM | NR | R | ||
WOODWORKING OPERATIONS EXCEEDING 232 SQM | REQUIRED | |||
POWER GENERATION BUILDING | REQUIRED | |||
6 | OTHER EXTINGUISHING SYSTEM | COMPLIANCE FROM INDIVIDUAL CODES & STANDARDS | IN LIEAU OF AN AUTOMATIC SUPPRESSION SYSTEM |