| III | BUILDING AND SITE ACCESS FOR FIRE FIGHTING & RESCUE | SPECIAL-PURPOSE INDUSTRIAL BUILDINGS | ||
|---|---|---|---|---|
| LOW HAZARD | ORDINARY HAZARD | |||
| A | SITE ACCESS | 4.0M MINIMUM CLEAR WIDTH & 4.5M MIN. CLEAR HEIGHT | REQUIRED | |
| B | ACCESS ROAD | 4.0M MIN. WIDTH AND 24 TON LOAD CAPACITY | REQUIRED | |
| WITHIN A TRAVEL DISTANCE OF 45M FROM EVERY POINT ON PROJECTED PLAN AREA OF ANY BUILDING. | ||||
| C | FIRE ENGINE HARDSTANDING | LENGTH OR NUMBER BASE ON THE GROSS FLOOR AREA OF THE BUILDING | REQUIRED | |
| 6M X 15M (MINIMUM), WITH LONGER SIDE PARALLEL TO THE FACADE OF THE BUILDING | ||||
| POSITIONED SO THAT THE NEARER EDGE SHALL BE NOT LESS THAN 2M OR NOT MORE THAN 10M FROM THE CENTER POSITION OF THE ACCESS OPENING, MEASURED HORIZONTALLY. | REQUIRED | |||
| D | FIRE COMMAND CENTER | OTHER THAN HIGH-RISE WITH EMERGENCY VOICE COMMUNICATION SYSTEM AND/OR SMOKE CONTROL SYSTEM | REQUIRED | |
| 9 SQM MINIMUM FLOOR AREA (LEAST DIMENSION 2.5M) | ||||
| E | FIRE LIFT | COMPLYING WITH ALL FIRE LIFTS REQUIREMENTS | TO COMPLY WITH REQUIREMENTS WHEN PROVIDED AS REQUIRED | |