| VIII | BUILDING SERVICES PROTECTION | SPECIAL-PURPOSE INDUSTRIAL - FACTORY AND WORKSHOPS | |||
|---|---|---|---|---|---|
| A | BUILDING UTILITIES | COMPLYING WITH CHAPTER 9 NFPA 101 | |||
| 1 | GAS EQUIPMENT & RELATED PIPING | PROTECTION AS PER NFPA 54 & NFPA 58 | REQUIRED | ||
| 2 | ELECTRICAL SYSTEMS / ELECTRICAL EQUIPMENT ROOMS | ASS OR 2-HRS ENCLOSURE | REQUIRED | ||
| SUBSTATION & SWITHGEARS | ATTACHED TO OCCUPIED BUILDINGS & | 3-HOURS FRR* or ASS | |||
| STANDALONE: TRANSFORMER VAULT REQUIRED PROTECTION | 3-HOURS FRR* or 1-HOUR FRR* WITH ASS | ||||
| 3 | COMMERCIAL COOKING EQUIPMENT | COMPLYING WITH NFPA 96 | REQUIRED | ||
| KITCHEN/PANTRY ENCLOSURE | NOT REQUIRED | ||||
| 4 | ELEVATORS, ESCALATORS & CONVEYORS | COMPLYING WITH ASME A17.1/CSA B44 | REQUIRED | ||
| FIRE FIGHTERS' EMERGENCY OPERATION | COMPLYING WITH ASME A17.1/CSA B44 | REQUIRED | |||
| B | RUBBISH CHUTE, INCINERATORS & LAUNDRY CHUTES | COMPLYING WITH NFPA 82 | REQUIRED | ||
| ENCLOSURES | <3 STOREYS / >3 STOREYS | 1-HOUR FRR* / 2-HRS FRR* | |||
| OPENING PROTECTIVE | <3 STOREYS / >3 STOREYS | 1-HOUR FPR** / 1.5-HR FPR** | |||
| LOW HAZARD | ORDINARY | ||||
| C | EMERGENCY POWER SUPPLY SYSTEM | COMPLYING WITH NFPA 110 | NOT REQUIRED | REQUIRED | |
| 1 | GENERATORS | ENCLOSURE | 1-HOUR FRR* | 1-HOUR FRR* | |
| D | FIRE PUMP ROOM | COMPLYING WITH NFPA 20 | REQUIRED | ||
| PUMP ROOM ENCLOSURES | MORE THAN 15.3 M FROM ANY BUILDING | 1-HOUR FRR* | |||
| WITHIN 15.3 M OR ATTACHED TO BUILDINGS | 2-HOURS FRR* | ||||
| DIRECT SAFE ACCESS | EXTERNAL ACCESS WITHIN THE LEVEL OF DISCHARGE | REQUIRED | |||
| WITHIN 3M FROM ANY EXIT THAT COMPLIES WITH DIRECT DISCHARGE REQUIREMENTS | PERMITTED | ||||
| ACCESS COMPONENT (UNDERGROUND LOCATION) | STANDARD STAIR (NON-COMBUSTIBLE MATERIAL) | REQUIRED | |||
| CAT STEEL LADDER | NOT PERMITTED | ||||
| E | FIRE WATER TANKS | COMPLYING WITH NFPA 22 | REQUIRED | ||
| MATERIALS | NON-COMBUSTIBLE MATERIAL | REQUIRED | |||
| GRP TANKS (WITHIN 1-HR FIRE RATED ENCLOSURE) | PERMITTED | ||||
| DESIGN/COMPARTMENTATION | TWO (2) COMPARTMENTS | REQUIRED | |||
| F | SMOKE CONTROL / EMERGENCY VENTILATION | COMPLYING WITH NFPA 92 & NFPA 204 | REQUIRED | ||
| 1 | VENTILATION / SMOKE CONTROL SYSTEM BY ANY OF THE FOLLOWING; 1.1 NATURAL VENTILATION; 1.2 MECHANICAL VENTILATION & SMOKE CONTROL SYSTEM AND/OR 1.3 MECHANICAL VENTILATION BY POSITIVE VENTILATION (PRESSURIZATION) SYSTEM |
LOW HAZARD | ORDINARY | ||
| FIRE AREA EXCEEDING 1115 SQM | NOT REQUIRED | REQUIRED | |||
| TOTAL AREA OF ALL FLOORS EXCEEDS 2230 SQM | NOT REQUIRED | REQUIRED | |||
| WOODWORKING OPERATIONS EXCEEDING 232 SQM | REQUIRED | ||||
| POWER GENERATION BUILDING | REQUIRED | ||||
| EXIT STAIRCASES CONNECTS MORE THAN FIVE (5) STORIES (LEVELS) INCLUDING THE BASEMENTS | REQUIRED | ||||
| AND/OR WHEN SMOKE STOP &/OR FIRE FIGHTING LOBBIES ARE REQUIRED | REQUIRED | ||||
| G | AIR-CONDITIONING & VENTILATION SYSTEM | COMPLYING WITH NFPA 90A & NFPA 90B | REQUIRED | ||