TYPE-B MERCANTILE OCCUPANCY - FEATURES OF FIRE PROTECTION


Height: < 3 storeys

Area: > 280 sqm - < 2,800 sqm Gross Area


VI FEATURES OF FIRE PROTECTION (NFPA 5000 TABLES 7.2.1.1, 7.3.2.1, 7.3.5 (a), (b), 7.3.5.5, 7.4.1) TYPE-B MERCANTILE
A CONSTRUCTION COMPLYING WITH CHAPTER 7 & 8 OF NFPA 5000  
1

CONSTRUCTION

(NON-COMBUSTIBLE OR LIMITED COMBUSTIBLE MATERIALS)
TYPE I OR TYPE II EXTERIOR BEARING WALLS HOURLY RATINGS REQUIRED PER TYPE OF CONSTRUCTION BASED ON NFPA 5000 HEIGHT & AREA REQUIREMENTS
FRAMING, COLUMNS, BEAMS, GIRDERS, TRUSSES
FLOOR CONSTRUCTION
B COMPARTMENTATION / SUBDIVISION OF BUILDING SPACES COMPLYING WITH NFPA 101 & NFPA 5000 REQUIRED
1 FIRE BARRIERS COMPLYING WITH NFPA 101 & NFPA 5000 REQUIRED
  TENANT SPACES SPRINKLER PROTECTED OR NON-SPRINKLER PROTECTED NOT REQUIRED
  STORAGE AREAS SPRINKLER PROTECTED NOT REQUIRED
NON-SPRINKLER PROTECTED 1-HR FRR*
2 SEPARATION FROM OTHER OCCUPANCIES AS PER NFPA 101 TABLE 6.1.14.4.1 (a), (b) REQUIRED
  MERCANTILE (BULK AND MALLS) SPRINKLER PROTECTED 1-HR FRR*
NON-SPRINKLER PROTECTED 2-HRS FRR*
  STORAGE (LOW/ORDINARY & HIGH HAZARD) SPRINKLER PROTECTED 1-HR FRR*
NON-SPRINKLER PROTECTED 2-HRS FRR*
3 CORRIDORS RATED SEPARATION COMPLYING WITH NFPA 101.30 &31 REQUIRED
  REQUIRED SEPARATION SPRINKLER PROTECTED NOT REQUIRED
NON-SPRINKLER PROTECTED 1-HR FRR*
4 SMOKE PARTITIONS COMPLYING WITH NFPA 101 & NFPA 5000 NOT REQUIRED
5 SMOKE BARRIERS COMPLYING WITH NFPA 101 & NFPA 5000 NOT REQUIRED
C VERTICAL OPENINGS PROTECTION PROTECTION COMPLYING WITH NFPA CODES REQUIRED
1 COMMUNICATING SPACES COMPLYING WITH CHAPTER 8 NFPA 101 PERMITTED
2 ATRIUMS COMPLYING WITH CHAPTER 8 NFPA 101 PERMITTED
3 CONVENIENCE OPENINGS COMPLYING WITH CHAPTER 8 NFPA 101 PERMITTED
4 SHAFTS COMPLYING WITH CHAPTER 8 NFPA 101 PERMITTED
5 MEZZANINES COMPLYING WITH CHAPTER 8 NFPA 101 PERMITTED
6 CONCEALED SPACES & DRAFTSTOPS COMPLYING WITH CHAPTER 8 NFPA 101 REQUIRED
  EXTERIOR & INTERIOR WALL & PARTITION FIRE STOPPED AT EACH LEVEL, TOP STORY CEILING LEVEL & AT THE LEVEL OF SUPPORT FOR ROOFS REQUIRED
  UNOCCUPIED ATTIC SPACES DRAFTSTOPS INTO AREAS NOT EXCEEDING 280 SQM REQUIRED
  CONCEALED SPACES (CEILINGS & FLOORS) DRAFTSTOPS INTO AREAS NOT EXCEEDING 93 SQM REQUIRED
  CONCEALED SPACES (FLOORS & ROOFS) DRAFTSTOPS INTO AREAS NOT EXCEEDING 280 SQM REQUIRED