| VII | FIRE PROTECTION (FRR* FIRE RESISTANCE RATING / FPR** FIRE PROTECTION RATING) | TYPE-B MERCANTILE | |
|---|---|---|---|
| A | DETECTION ALARM AND COMMUNICATION SYSTEMS | ||
| 1 | FIRE ALARM SYSTEM | BUILDING IS THREE (3) OR MORE STORIES IN HEIGHT | REQUIRED |
| OCCUPANCY IS SUBJECT TO 50 OR MORE OCCUPANTS ABOVE OR BELOW THE LEVEL OF EXIT DISCHARGE | REQUIRED | ||
| OCCUPANCY IS SUBJECT TO 300 OR MORE TOTAL OCCUPANTS | REQUIRED | ||
| B | EXTINGUISHING REQUIREMENTS | COMPLIANCE WITH INDIVIDUAL CODES & STANDARDS | REQUIRED |
| 1 | PROTABLE FIRE EXTINGUISHERS | TYPE AND RATING IN ACCORDANCE WITH NFPA 10 | REQUIRED |
| 2 | FIRE BLANKETS | IN KITCHEN OR PANTRY | REQUIRED |
| 3 | STANDPIPE SYSTEM | BUILDING EXCEEDING 9M IN HABITABLE HEIGHT | REQUIRED |
| 4 | FIRE HOSE REELS | 25MM DIAMETER HOSE | REQUIRED |
| 5 | AUTOMATIC SPRINKLER SYSTEM | >3 STOREYS OR 1115SQM GROSS AREA | REQUIRED |
| 232 SQM BASEMENT USED FOR SALE & STORAGE | REQUIRED | ||
| MIXED OCCUPANCIES | REQUIRED | ||
| PROVIDED IN LIEAU OF THE REQUIRED DRAFTSTOPS IN CONCEALED SPACES | NOT REQUIRED | ||
| 6 | OTHER EXTINGUISHING EQUIPMENT | COMPLIANCE FROM INDIVIDUAL NFPA CODES & STANDARDS | NOT REQUIRED |