VILLAS TO PRIMARY SCHOOL - FEATURES OF FIRE PROTECTION


Height: Ground Floor (6-8 years old)

Maximum 1 Floor Level (G+1) 9 years old and older

Area: Maximum 100 Occupants per Floor or

Maximum 4 Classrooms per Floor level


V FEATURES OF FIRE PROTECTION (NFPA 5000 TABLES 7.2.1.1, 7.3.2.1, 7.3.5 (a), (b), 7.3.5.5, 7.4.1) VILLAS TO PRIMARY
A CONSTRUCTION COMPLYING WITH CHAPTER 7 & 8 OF NFPA 5000  
1

CONSTRUCTION

(NON-COMBUSTIBLE OR LIMITED COMBUSTIBLE MATERIALS)
TYPE I OR TYPE II EXTERIOR BEARING WALLS 1-HR FRR* FIRE RESISTANCE RATING OF ALL BUILDING ELEMENTS
FRAMING, COLUMNS, BEAMS, GIRDERS, TRUSSES
FLOOR CONSTRUCTION
B COMPARTMENTATION/SUBDIVISION OF BUILDING SPACES COMPLYING WITH NFPA 101 & NFPA 5000 NOT REQUIRED
1 SEPARATION FROM OTHER OCCUPANCIES AS PER NFPA 101 TABLE 6.1.14.4.1 (a), (b) REQUIRED