VILLAS TO PRIMARY SCHOOL - BUILDING SERVICES PROTECTION


Height: Ground Floor (6-8 years old)

Maximum 1 Floor Level (G+1) 9 years old and older

Area: Maximum 100 Occupants per Floor or

Maximum 4 Classrooms per Floor level


VII BUILDING SERVICES PROTECTION (ASS* AUTOMATIC SUPPRESSION SYSTEM) VILLAS TO PRIMARY
A BUILDING UTILITIES COMPLYING WITH CHAPTER 9 NFPA 101  
1 ELECTRICAL SYSTEMS COMPLYING WITH NFPA 70 REQUIRED
2 COOKING EQUIPMENT EQUIPMENT USED ONLY FOR FOOR WARMING PERMITTED
B EMERGENCY POWER SUPPLY SYSTEM / GENERATORS COMPLYING WITH NFPA 110 NOT REQUIRED
C SMOKE CONTROL / EMERGENCY VENTILATION COMPLYING WITH NFPA 92 & NFPA 204 NOT REQUIRED
D AIR-CONDITIONING & VENTILATION SYSTEM COMPLYING WITH NFPA 90 & NFPA 90B REQUIRED