STORAGE (HIGH-HAZARD) - BUILDING AND SITE ACCESS FOR FIRE FIGHTING & RESCUE


In accordance with NFPA 5000 Table 7.4.1 - for the Allowable Building Height and Area


WAREHOUSE / BARNS / BULK OIL STORAGE / COLD STORAGE / GRAIN ELEVATORS / FREIGHT TERMINALS / HANGARS (FOR STORAGE ONLY) / TRUCKS & MARINE TERMINALS / PARKING STRUCTURES

AN OCCUPANCY USED PRIMARILY FOR THE STORAGE OR SHELTERING OF GOODS, MECHANDISE, PRODUCTS OR VEHICLES CHARACTERIZED BY THE PRESENCE OF RELATIVELY SMALL NUMBERS OF PERSON IN PROPOSRTION TO THE AREA. INCIDENTAL STORAGE IN OTHER OCCUPANCY IS EXCLUDED.

STORAGE USE OTHER THAN LOW HAZARDS: AEROSOL, LEVEL 2 AND LEVEL 3 / AIRCRAFT HANGARS / BAGS, CLOTH, BURLAP, AND PAPER / BAMBOO AND RATTAN / BASKETS / BELTING, CANVAS AND LEATHER / BOOKS AND PAPER IN ROLLS OR PACKS / BOOTS AND SHOES / BUTTONS, INCLUDING CLOTH COVERED, PEARL, OR BONE / CARDBOARD AND CARDBOARD BOXES / CLOTHING, WOOLEN WEARING APPAREL / CORDAGE / FURNITURE / FURS / GLUES, MUCILAGE, PASTES AND SIZE / GRAINS / HORNS AND COMBS, OTHER THAN CELLULOID / LEATHER / LINOLEUM / LUMBER / PETROLEUM WAREHOUSES FOR STORAGE OF LUBRICATING OILS WITH A FLASHPOINT OF 200 DEF. F (93 DEG. C) OR HIGHER / PHOTO ENGRAVINGS / RESILIENT FLOORING / SILKS / SOAPS / SUGAR / TIRES, BULK STORAGE / TOBACCO, CIGARS, CIGARETTES, AND SNUFF / UPHOLSTERY AND MATTRESSES / WAX CANDLES

III BUILDING AND SITE ACCESS FOR FIRE FIGHTING & RESCUE HIGH-HAZARD STORAGE
A SITE ACCESS 4.0M MINIMUM CLEAR WIDTH REQUIRED
4.5M MINIMUM CLEAR HEIGHT
B ACCESS ROAD 4.0M MIN. WIDTH AND 24 TON LOAD CAPACITY REQUIRED
WITHIN A TRAVEL DISTANCE OF 45M FROM EVERY POINT ON PROJECTED PLAN AREA OF ANY BUILDING.
C FIRE ENGINE HARDSTANDING LENGTH OR NUMBER BASE ON THE GROSS FLOOR AREA OF THE BUILDING REQUIRED
6M X 15M (MINIMUM), WITH LONGER SIDE PARALLEL TO THE FACADE OF THE BUILDING
POSITIONED SO THAT THE NEARER EDGE SHALL BE NOT LESS THAN 2M OR NOT MORE THAN 10M FROM THE CENTER POSITION OF THE ACCESS OPENING, MEASURED HORIZONTALLY.
D FIRE COMMAND CENTER PROVISIONS IN OTHER THAN HIGH-RISE BUILDINGS EQUIPPED WITH EMERGENCY VOICE COMMUNICATION SYSTEM AND/OR SMOKE CONTROL SYSTEM REQUIRED
9 SQM MINIMUM FLOOR AREA (LEAST DIMENSION 2.5M) REQUIRED
E FIRE LIFT SERVING ALL HABITABLE FLOORS AND LOCATED WITHIN A DEDICATED SHAFT. TO COMPLY WITH REQUIREMENTS WHEN PROVIDED AS REQUIRED