| IV |
MEANS OF EGRESS |
HIGH-HAZARD STORAGE |
| A |
MEANS OF EGRESS GENERAL REQUIREMENTS |
|
| 1 |
SEPARATION OF MEANS OF EGRESS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
REQUIRED |
| EXIT ACCESS CORRIDORS |
SERVING AN AREA HAVING AN OCCUPANT LOAD EXCEEDING 30 |
1-HR FRR* |
| EXITS |
CONNECTS 3 OR FEWER STORIES |
1-HR FRR* |
| CONNECTS 4 OR MORE STORIES |
2-HRS FRR* |
| OPENING PROTECTIVE |
FIRE DOOR ASSEMBLIES EQUIPPED WITH DOOR CLOSERS |
REQUIRED |
| CONSTRUCTION |
LIMITED OR NON-COMBUSTIBLE MATERIALS |
REQUIRED |
| OPENINGS AND PENETRATIONS IN EXIT ENCLOSURE |
COMPLYING WITH CHAPTER 7 NFPA 101 |
PERMITTED |
| 2 |
EXITS HEADROOM |
NOT LESS THAN 2285MM |
REQUIRED |
| HEADROOM ON STAIRS |
NOT LESS TAHN 2285MM |
REQUIRED |
| HEADROOM IN INDUSTRIAL EQUIPMENT ACCESS |
AS PROVIDED IN CHAPTER 40 NFPA 101 |
PERMITTED |
| 3 |
WALKING SURFACES IN THE MEANS OF EGRESS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
REQUIRED |
| 4 |
CHANGES IN LEVEL IN THE MEANS OF EGRESS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
REQUIRED |
| 5 |
GUARDS |
PROVIDED AT THE OPEN SIDES OF MEANS OF EGRESS 760MM ABOVE THE FLOOR OR FINISHED GROUND LEVEL |
REQUIRED |
| 6 |
IMPEDIMENT TO EGRESS |
|
NOT PERMITTED |
| 7 |
MEANS OF EGRESS RELIABILITY |
CONTINUOUSLY MAINTAINED FREE OF ALL OBSTRUCTION OR IMPEDIMENTS |
REQUIRED |
| |
FURNISHING AND DECORATION |
FURNITURES, MOVABLE OBJECTS, MIRRORS, ETC. |
NOT PERMITTED |
| B |
MEANS OF EGRESS COMPONENTS |
|
|
| 1 |
FIRE DOORS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
REQUIRED |
| SIDE-HINGE OR PIVOTED-SWINGING TYPE |
ANY DOOR ASSEMBLY IN A MEANS OF EGRESS |
REQUIRED |
| MINIMUM DOOR LEAF WIDTH |
810MM |
| HORIZONTAL SLIDING DOORS |
OCCUPANT LOAD OF FEWER THAN 10 |
PERMITTED |
| VERTICAL ROLLING DOORS |
OCCUPANT LOAD OF FEWER THAN 10 |
PERMITTED |
| REVOLVING DOOR / POWERED DOORS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
PERMITTED |
| SELF-CLOSING DEVICES |
DOORS REQUIRED TO BE NORMALLY KEPT CLOSED |
REQUIRED |
| 2 |
STAIRS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
REQUIRED |
| NON-COMBUSTIBLE GRATED STAIR TREADS AND LANDINGS |
PERMITTED |
| STANDARD STAIRS |
FEWER THAN 50 PERSON |
915MM CLEAR WIDTH |
| <2000 PERSON |
1120MM CLEAR WIDTH |
| ≥2000 PERSON |
1420MM CLEAR WIDTH |
| SPIRAL STAIRS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
PERMITTED |
| CURVE STAIRS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
NO REQUIREMENTS |
| WINDERS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
NO REQUIREMENTS |
| GUARDS AND HANDRAILS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
REQUIRED |
| OUTSIDE STAIRS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
PERMITTED |
| ENCLOSURE AND PROTECTION OF STAIRS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
REQUIRED |
| ENCLOSURES |
ALL INSIDE STAIR SERVING AS AN EXIT COMPONENT |
REQUIRED |
| DOORS FPR* |
≤3 STORIES / ≥3 STORIES |
1-HR FPR** / 1.5-HRS FPR** |
| ENCLOSURES FRR* |
≤3 STORIES / ≥3 STORIES |
1-HR FRR** / 2-HRS FRR** |
| ENCLOSURE EXEMPTION |
PENETRATING ONE FLOOR LEVEL OR SERVING MEZZANINE ONLY |
PERMITTED |
| EXPOSURES |
WALLS AND OPENINGS WITHIN 3050MM HORIZONTALLY OF AN EXTERIOR STAIRWAY ENCLOSURE |
1-HR FRR* |
| USABLE SPACE |
WITHIN EXIT ENCLOSURE |
NOT PERMITTED |
| UNDER STAIRS IN ACCORDANCE WITH NFPA 101 |
PERMITTED |
| STAIRWAY IDENTIFICATION |
SERVING 3 OR MORE STOREYS |
REQUIRED |
| EXIT STAIR PATH MARKINGS |
ALL STAIR COMPONENTS |
REQUIRED |
| PERIMETER DEMARCATION MARKING |
COMPLYING WITH NFPA 101 |
REQUIRED |
| LOCK, LATCHES & ALARM DEVICES |
COMPLYING WITH NFPA 101 |
PERMITTED |
| RE-ENTRY PROVISIONS |
LOCKED STAIRS EXCEEDING 4 STOREYS |
REQUIRED |
| 3 |
RAMPS |
COMPLYING WITH NFPA 101 |
PERMITTED |
| 4 |
INDUSTRIAL EQUIPMENT ACCESS RAMPS / PLATFORMS / WALKWAYS / STAIRS AND DOORS |
COMPLYING WITH THE SIMENSIONAL CRITERIA IN NFPA 101 TABLE 40.2.5.2.1 |
PERMITTED |
| 5 |
ROOF ACCESS |
BUILDING EQUAL OR MORE THAN 4 STOREYS (G+3) OR ROOFS 12M ABOVE GRADE PLANE |
REQUIRED |
| ONE AT EACH 9300 SQM ROOF AREA |
REQUIRED |
| FLAT ROOFS OR ROOF PITCH <3 IN 12 |
REQUIRED |
| STAIRS AS ACCESS WITH OPERABLE DOORS |
REQUIRED |
| 6 |
SMOKE PROOF ENCLOSURES |
FRR* (FIRE RESISTANCE RATING) |
|
| |
STAIR ENCLOSURES |
ALL INSIDE STAIRS SERVING AS AN EXIT COMPONENT |
REQUIRED |
| OPEN STAIR PENETRATING ONE (1) FLOOR / LEVEL ONLY |
NOT PERMITTED |
| |
FIRE FIGHTING LOBBY (F/F LOBBY) |
IN EVERY FIRE LIFT PROVISIONS |
REQUIRED WHEN FIRE LIFTS PROVIDED |
| ADJACENT AND ACCESIBLE TO AN EXIT STAIRCASE |
| SERVES AS A COMMON LOBBY FOR BOTH FIRE LIFT AND THE ADJACENT EXIT STAIRCASE |
| 6 SQM MINIMUM AREA / WORKING SPACE (LEAST SIDE DIMENSION 2.0M) |
| PROVISIONS AT THE LEVEL OF EXIT DISCHARGE |
NOT REQUIRED IF EXITS COMPLIES WITH EXIT DISCHARGE REQUIREMENTS |
| |
SMOKE-STOP LOBBY (S/S LOBBY) |
HIGH-RISE BUILDINGS WITH HABITABLE HEIGHT HIGHER THAN 28 METERS |
REQUIRED |
| BASEMENT LEVEL/S EXCEED 9.0 M DEPTH |
REQUIRED |
| BUILDING TRAVERSES MORE THAN FIVE (5) FLOOR LEVELS INCLUDING BASEMENT/S AND BELONGS TO A PLACE OF PUBLIC RESORT (ASSEMBLY & HEALTHCARE OCCUPANCY) REGARDLESS OF THE HABITABLE HEIGHT. |
NOT APPLICABLE |
| 3 SQM MIN. AREA (LEAST SIDE DIMENSION 1.8M) |
REQUIRED |
| PROVISIONS AT THE LEVEL OF EXIT DISCHARGE |
NOT REQUIRED IF EXITS COMPLIES WITH EXIT DISCHARGE REQ'TS |
| |
SMOKE-STOP LOBBY AND FIRE FIGHTING LOBBY DOORS AND WALL ENCLOSURES |
1.5-HR FPR** FIRE PROTECTION RATING / 2-HRS FRR* FIRE RESISTANCE RATING |
REQUIRED WHEN LOBBY'S PROVIDED |
| 7 |
HORIZONTAL EXITS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
NOT PERMITTED |
| 8 |
EXIT PASSAGEWAYS |
ENCLOSURE AND SEPARATION FIRE RESISTANCE RATING COMPLYING WITH CHAPTER 7 NFPA 101 |
REQUIRED |
| MIN. WIDTH NOT LESS THAN 2/3 OF THE WIDTH OF THE EXIT STAIR |
REQUIRED |
| 8 |
ESCALATORS & MOVING WALKS |
AS PART OF THE REQUIRED MEANS OF EGRESS |
NOT PERMITTED |
| 9 |
FIRE ESCAPE STAIRS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
PERMITTED |
| 10 |
FIRE ESCAPE LADDERS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
NOT PERMITTED |
| 11 |
SLIDE ESCAPES |
COMPLYING WITH CHAPTER 7 NFPA 101 |
PERMITTED |
| 12 |
ALTERNATING TREAD DEVICES |
COMPLYING WITH CHAPTER 7 NFPA 101 |
NOT PERMITTED |
| 13 |
AREAS OF REFUGE |
COMPLYING WITH CHAPTER 7 NFPA 101 |
REQUIRED |
| 14 |
ELEVATORS |
AS PART OF THE REQUIRED MEANS OF EGRESS |
NOT PERMITTED |
| AS PER NFPA 101 & ASME A17.1 / CSA B44 |
PERMITTED |
| ELEVATOR DOORS |
OPENING INTO EXIT ENCLOSURES |
NOT PERMITTED |
| C |
CAPACITY OF MEANS OF EGRESS |
|
| 1 |
OCCUPANT LOAD |
NFPA 101 TABLE 7.3.1.2 OCCUPANT LOAD FACTOR |
THE MAXIMUM PROBABLE NUMBER OF OCCUPANTS PRESENT AT ANYTIME |
| 2 |
EGRESS CAPACITY |
NFPA 101 TABLE 7.3.3.1 CAPACITY FACTORS |
REQUIRED |
| D |
NUMBER OF EXITS |
COMPLYING WITH NFPA 101 CHAPTER 7 |
|
| 1 |
SINGLE EXIT |
SERVING ALL FLOOR LEVELS |
NOT LESS THAN 2 EXITS REQUIRED |
| IN MEZZANINES WITH EXIT TRAVEL WITHIN COMMON PATH LIMIT |
NOT PERMITTED |
| ANY STORY OR SECTION WITH EXIT TRAVEL WITHIN COMMON PATH LIMIT |
NOT PERMITTED |
| 2 |
2 SEPARATE EXITS |
50 - 500 OCCUPANTS |
REQUIRED |
| 3 |
3 SEPARATE EXITS |
EQUAL OR MORE THAN 500 OCCUPANTS |
REQUIRED |
| 4 |
4 SEPARATE EXITS |
EQUAL OR MORE THAN 1000 OCCUPANTS |
REQUIRED |
| E |
ARRANGEMENT OF EXITS |
NS*-NOT SPRINKLERED / S**-SPRINKLERED |
S** |
NS* |
| 1 |
TRAVEL DISTANCE |
NFPA 101 TABLE 42.2.6 |
23M |
30M |
| 2 |
COMMON PATH LIMIT |
NFPA 101 TABLE 42.2.5 |
0 |
0 |
| 3 |
DEAD-END CORRIDOR |
NFPA 101 TABLE 42.2.5 |
0 |
0 |
| 4 |
EXIT DISCHARGE |
COMPLYING WITH NFPA 101 |
REQUIRED |
| 5 |
EXTERIOR WAYS OF EXIT |
COMPLYING WITH NFPA 101 |
PERMITTED |
| 6 |
ACCESIBLE MEANS OF EGRESS |
EXIT PROVISIONS FOR PEOPLE WITH SEVERE MOBILITY IMPAIRMENT |
2 EXITS REQUIRED |
| 7 |
ILLUMINATION OF MEANS OF EGRESS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
REQUIRED |
| 8 |
EMERGENCY LIGHTING |
COMPLYING WITH CHAPTER 7 NFPA 101 |
REQUIRED |
| 9 |
MARKINGS OF MEANS OF EGRESS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
REQUIRED |
| F |
SPECIAL MEANS OF EGRESS PROVISIONS |
|
|
| 1 |
FIREMEN ACCESS PANELS |
ANY NUMBER OF STORIES |
REQUIRED |
| 2 |
REFUGE FLOORS |
AT AN INTERVAL OF 20 STORIES |
BUILDINGS EXCEEDING 30 STORIES |
| 3 |
ELEVATORS FOR OCCUPANT CONTROLLED EVACUATION PRIOR TO PHASE 1 EMERGENCY RECALL OPERATIONS |
COMPLYING WITH CHAPTER 7 NFPA 101 |
PERMITTED |