III | BUILDING AND SITE ACCESS FOR FIRE FIGHTING & RESCUE | PRIMARY SCHOOL | ||
---|---|---|---|---|
FIRE SAFETY PROVISIONS | MINIMUM REQUIREMENTS | GF ONLY (6-8 YO) |
G + 1 (9-11 YO) |
|
A | SITE ACCESS | 4.0M MINIMUM CLEAR WIDTH | REQUIRED | |
4.5M MINIMUM CLEAR HEIGHT | ||||
B | ACCESS ROAD | 4.0M MIN. WIDTH AND 24 TON LOAD CAPACITY | REQUIRED | |
WITHIN A TRAVEL DISTANCE OF 45M FROM EVERY POINT ON PROJECTED PLAN AREA OF ANY BUILDING. | ||||
C | FIRE ENGINE HARDSTANDING | LENGTH OR NUMBER BASE ON THE GROSS FLOOR AREA OF THE BUILDING | NOT REQUIRED | |
6M X 15M (MINIMUM), WITH LONGER SIDE PARALLEL TO THE FACADE OF THE BUILDING | ||||
POSITIONED SO THAT THE NEARER EDGE SHALL BE NOT LESS THAN 2M OR NOT MORE THAN 10M FROM THE CENTER POSITION OF THE ACCESS OPENING, MEASURED HORIZONTALLY. | ||||
D | FIRE COMMAND CENTER | WITH PROVISIONS OF AN EMERGENCY VOICE COMMUNICATION SYSTEM AND/OR SMOKE CONTROL SYSTEM | REQUIRED | |
9 SQM MINIMUM AREA (LEAST DIMENSION 2.5M) | ||||
AT LEAST WITH 1M CLEARANCE FROM ALL EQUIPMENT | ||||
2-HOURS ENCLOSURES (WALLS & OPENINGS) | ||||
PROVIDED WITH PROMINENTLY MARKED EXTERIOR ENTRANCES | ||||
E | FIRE LIFT | BUILDINGS EQUAL OR MORE THAN 28M ABOVE ENGINE ACCESS LEVEL. | NOT APPLICABLE | |
BUILDINGS EXCEEDS 9.0M BELOW THE LEVEL OF EXIT DISCHARGE | REQUIRED | |||
SERVES ALL HABITABLE FLOORS | REQUIRED IN EVERY FIRE SERVICE ACCESS ELEVATOR/FIRE LIFT PROVISIONS | |||
CONTAINED WITHIN A DEDICATED PROTECTED SHAFT | ||||
APPROACHED BY FIRE FIGHTING LOBBY AT EACH STOREY | ||||
ADJACENT AND ACCESIBLE TO AN EXIT STAIRCASE | ||||
FIRE SERVICE ACCESS ELEVATORS/FIRE LIFT AS PER NFPA 5000 (2012 Ed.) CHAPTER 54.12 | BUILDINGS EXCEEDS 9.0M BELOW THE LEVEL OF EXIT DISCHARGE | |||
AMBULANCE STRETCHER ACCOMODATION ELEVATOR/LIFT AS PER NFPA 5000 (2012 Ed.) CHAPTER 54.3 | NOT REQUIRED | |||
WHEN REQUIRED, AT LEAST ONE (1) FIRE LIFT FOR EVERY 900 SQM. FLOOR AREA | REQUIRED (R) IN EVERY FIRE LIFT PROVISIONS |