Primary School Building - FIRE PROTECTION


Height:
Ground Floor only
(6-8 YO)

G+1 (9-11 YO)

Area: as per OLF 1.9 sqm / person net


PRIMARY STUDENTS OF AGES 5-11 YEARS OLD

OCCUPANCY USED FOR EDUCATIONAL PURPOSES THROUGH THE TWELFTH GRADE BY SIX OR MORE PERSONS FOR 4 OR MORE HOURS PER DAY OR MORE THAN 12 HOURS PER WEEK

VII FIRE PROTECTION (FRR* FIRE RESISTANCE RATING / FPR** FIRE PROTECTION RATING) PRIMARY SCHOOL
    GF ONLY
(6-8 YO)
G+1
(9-11 YO)
A DETECTION ALARM AND COMMUNICATION SYSTEMS    
1 FIRE ALARM SYSTEM AUTOMATIC AND MANUAL SYSTEM REQUIRED
B EXTINGUISHING REQUIREMENTS COMPLIANCE TO RELEVANT CODES & STANDARDS REQUIRED
1 PORTABLE FIRE EXTINGUISHERS TYPE AND RATING AS PER NFPA 10 REQUIRED
2 FIRE BLANKETS IN KITCHEN OR PANTRY REQUIRED
3 STANDPIPE SYSTEM BUILDING EXCEEDING 9M IN HABITABLE HEIGHT NR R
4 FIRE HOSE REELS 25MM DIAMETER HOSE REQUIRED
5 AUTOMATIC SPRINKLER SYSTEM AREA EXCEEDING 1120 SQM REQUIRED
EVERY PORTION BELOW THE LEVEL OF EXIT DISCHARGE (BESEMENTS)
6 OTHER EXTINGUISHING EQUIPMENT COMPLIANCE TO RELEVANT CODES & STANDARDS PERMITTED