IV | MEANS OF EGRESS | PRIMARY SCHOOL | ||||
---|---|---|---|---|---|---|
FIRE SAFETY PROVISIONS | MINIMUM REQUIREMENTS | GF ONLY (6-8 YO) |
G+1 (9-11 YO) |
|||
A | MEANS OF EGRESS GENERAL REQUIREMENTS | |||||
1 | SEPARATION OF MEANS OF EGRESS | |||||
EXIT ACCESS CORRIDORS | SERVING AN AREA HAVING AN OCCUPANT LOAD EXCEEDING 30 | 1-HR FRR* | ||||
EXITS ENCLOSURE | CONNECTS 3 OR FEWER STORIES | NA | 1-HR FRR* | |||
OPENING PROTECTIVE | FIRE DOOR ASSEMBLIES EQUIPPED WITH DOOR CLOSERS | REQUIRED | ||||
CONSTRUCTION | LIMITED OR NON-COMBUSTIBLE MATERIALS | REQUIRED | ||||
OPENINGS AND PENETRATIONS IN EXIT ENCLOSURE | COMPLYING WITH CHAPTER 7 NFPA 101 | PERMITTED | ||||
2 | EXITS HEADROOM (STAIRS) | NOT LESS THAN 2285MM | REQUIRED | |||
3 | WALKING SURFACES IN THE MEANS OF EGRESS | COMPLYING WITH CHAPTER 7 NFPA 101 | REQUIRED | |||
4 | CHANGES IN LEVEL IN THE MEANS OF EGRESS | COMPLYING WITH CHAPTER 7 NFPA 101 | REQUIRED | |||
5 | GUARDS | PROVIDED AT THE OPEN SIDES OF MEANS OF EGRESS | REQUIRED | |||
760MM ABOVE THE FLOOR OR FINISHED GROUND LEVEL | ||||||
6 | IMPEDIMENT TO EGRESS | NOT PERMITTED | ||||
7 | MEANS OF EGRESS RELIABILITY | CONTINUOUSLY MAINTAINED FREE OF ALL OBSTRUCTION OR IMPEDIMENTS | REQUIRED | |||
8 | FURNISHING AND DECORATION | FURNITURES, MOVABLE OBJECTS, MIRRORS, ETC. | NOT PERMITTED | |||
CLOTHING & PERSONAL EFFECTS | STORED IN NON-SPRINKLER PROTECTED CORRIDORS | NOT PERMITTED | ||||
STORED IN SPRINKLER PROTECTED CORRIDORS | PERMITTED | |||||
IN CORRIDORS PROVIDED WITH SMOKE DETECTION | ||||||
STORAGE IN METAL LOCKERS ALONG CORRIDORS | PERMITTED PROVIDED REQUIRED EGRESS MAINTAINED | |||||
ART WORK & TEACHING MATERIALS | SPRINKLER PROTECTED | NOT MORE THAN 50% OF THE WALL AREA | ||||
NOT SPRINKLER PROTECTED | NOT MORE THAN 20% OF THE WALL AREA | |||||
B | MEANS OF EGRESS COMPONENTS | FPR** FIRE PROTECTION RATING | ||||
1 | FIRE DOORS | COMPLYING WITH CHAPTER 7 NFPA 101 | ||||
SIDE-HINGE OR PIVOTED-SWINGING TYPE | ANY DOOR ASSEMBLY IN A MEANS OF EGRESS | REQUIRED | ||||
MINIMUM DOOR LEAF WIDTH | 810MM | |||||
HORIZONTAL SLIDING DOORS | COMPLYING WITH CHAPTER 7 NFPA 101 | NOT PERMITTED | ||||
VERTICAL ROLLING DOORS | COMPLYING WITH CHAPTER 7 NFPA 101 | NOT PERMITTED | ||||
REVOLVING DOORS / POWERED DOORS | COMPLYING WITH CHAPTER 7 NFPA 101 | NOT PERMITTED | ||||
SELF-CLOSING DEVICES | DOORS REQUIRED TO BE NORMALLY KEPT CLOSED | REQUIRED | ||||
2 | STAIRS | |||||
STANDARD STAIRS | FEWER THAN 50 PERSON (CLEAR WIDTH) | 915MM | ||||
<2000 PERSON (CLEAR WIDTH) | 1120MM | |||||
>2000 PERSON (CLEAR WIDTH) | 1420MM | |||||
SPIRAL STAIRS | COMPLYING WITH CHAPTER 7 NFPA 101 | NOT APPLICABLE | NOT PERMITTED | |||
CURVE STAIRS | COMPLYING WITH CHAPTER 7 NFPA 101 | |||||
WINDERS | COMPLYING WITH CHAPTER 7 NFPA 101 | |||||
GUARDS AND HANDRAILS | COMPLYING WITH CHAPTER 7 NFPA 101 | REQUIRED | ||||
ENCLOSURE AND PROTECTION OF STAIRS | ||||||
ENCLOSURES | ALL INSIDE STAIR SERVING AS AN EXIT COMPONENT | N/A | R | |||
DOORS FPR* | < 3 STOREYS / > 3 STOREYS | N/A | 1-HR FPR** | |||
ENCLOSURES FRR* | < 3 STOREYS / > 3 STOREYS | N/A | 1-HR FRR* | |||
ENCLOSURE EXEMPTION | PENETRATING ONE FLOOR LEVEL OR SERVING MEZZANINE ONLY | N/A | NP | |||
EXPOSURES | WALLS AND OPENINGS WITHIN 3050MM HORIZONTALLY OF AN EXTERIOR STAIRWAY ENCLOSURE | N/A | 1-HR FRR* | |||
USABLE SPACE | WITHIN EXIT ENCLOSURE | N/A | NP | |||
LOCATION UNDER STAIRS IN ACCORDANCE WITH NFPA 101 | N/A | P | ||||
STAIRWAY IDENTIFICATION | SERVING 3 OR MORE STOREYS | NOT APPLICABLE | ||||
EXIT STAIR PATH MARKINGS | ALL STAIR COMPONENTS | N/A | R | |||
PERIMETER DEMARCATION MARKING | COMPLYING WITH NFPA 101 | |||||
LOCK, LATCHES & ALARM DEVICES | COMPLYING WITH NFPA 101 | N/A | P | |||
RE-ENTRY PROVISIONS | LOCKED STAIRS EXCEEDING 4 STOREYS | NOT APPLICABLE | ||||
3 | RAMPS | COMPLYING WITH CHAPTER 7 NFPA 101 | REQUIRED | |||
AS SECONDARY EXIT FOR ONE (1) BASEMENT LEVEL | NOT APPLICABLE | |||||
4 | ROOF ACCESS | BUILDING EQUAL OR MORE THAN 4 STOREYS (G+3) OR ROOFS 12M ABOVE GRADE PLANE | NOT APPLICABLE | |||
WHERE OPEN STAIR/S ARE PERMITTED AND PROVIDED | ||||||
ONE AT EACH 9300 SQM ROOF AREA OR FLAT ROOFS OR ROOF PITCH <3 IN 12 | ||||||
ROOF ACCESS COMPONENTS | SMOKE VENTS (FIXED WALL OPENING/S) AT THE TOP OF THE STAIRWELL WITH A MINIMUM AREA OF 1.5 SQM | NOT APPLICABLE | ||||
STAIR ACCESS TO ROOF EQUIPPED WITH OPERABLE DOORS | ||||||
5 | SMOKE PROOF ENCLOSURES | FRR* (FIRE RESISTANCE RATING) | ||||
STAIR ENCLOSURES | ALL INSIDE STAIRS SERVING AS AN EXIT COMPONENT | N/A | R | |||
STAIR ENCLOSURES | OPEN STAIR PENETRATING ONE (1) FLOOR / LEVEL ONLY | N/A | P | |||
FIRE FIGHTING LOBBY (F/F LOBBY) | COMPLYING WITH THE FIRE FIGHTING LOBBY REQUIREMENTS | N/A | NR | |||
LOBBY DOORS & WALL ENCLOSURES | 1.5-HR FPR** FIRE PROTECTION RATING | |||||
SMOKE-STOP LOBBY (VESTIBULE) | COMPLYING WITH THE SMOKE-STOP LOBBY REQUIREMENTS | |||||
6 | HORIZONTAL EXITS | COMPLYING WITH CHAPTER 7 NFPA 101 | 1-HR FRR* | |||
7 | EXIT PASSAGEWAYS | ENCLOSURE AND SEPARATION FIRE RESISTANCE RATING COMPLYING WITH CHAPTER 7 NFPA 101 | REQUIRED | |||
MIN. WIDTH AS PER EXIT CAPACITY FACTOR 7/OR NOT LESS THAN 2/3 OF THE WIDTH OF THE EXIT STAIR | ||||||
8 | FIRE ESCAPE STAIRS | COMPLYING WITH CHAPTER 7 NFPA 101 | PERMITTED | |||
9 | FIRE ESCAPE LADDERS | COMPLYING WITH CHAPTER 7 NFPA 101 | NOT PERMITTED | |||
10 | AREAS OF REFUGE | COMPLYING WITH CHAPTER 7 NFPA 101 | REQUIRED | |||
11 | ELEVATORS | AS PART OF THE REQUIRED MEANS OF EGRESS | NOT PERMITTED | |||
AS SECOND MEANS OF EGRESS | ||||||
ELEVATOR DOORS | OPENING INTO EXIT ENCLOSURES | |||||
C | CAPACITY OF MEANS OF EGRESS | |||||
1 | OCCUPANT LOAD | CLASSROOMS | 1.9 NET SQM/PERSON | |||
SHOPS, LABORATORIES, VOCATIONAL ROOMS | 4.6 NET SQM/PERSON | |||||
2 | EGRESS CAPACITY | STAIRWAYS | 7.6MM | |||
LEVEL COMPONENTS & RAMPS | 5.0MM | |||||
3 | EXIT ACCESS CORRIDORS | REQUIRED MINIMUM CLEAR WIDTH | 1830MM | |||
D | NUMBER OF EXITS | |||||
1 | SINGLE EXIT | ONLY ONE (1) ON EVERY STORY | NOT PERMITTED | |||
2 | NOT LESS THAN 2 SEPARATE EXITS (MINIMUM) | REQUIREMENTS FOR ANY NUMBER OF OCCUPANTS | REQUIRED | |||
3 | NOT LESS THAN THREE (3) SEPARATE EXITS | EQUAL OR MORE THAN 500 OCCUPANTS | ||||
4 | NOT LESS THAN FOUR (4) SEPARATE EXITS | EQUAL OR MORE THAN 1000 OCCUPANTS | ||||
E | ARRANGEMENT OF EXITS | NS*-NOT SPRINKLERED / S**-SPRINKLERED | NS* | S** | ||
1 | TRAVEL DISTANCE | IN ACCORDANCE WITH NFPA 101 TABLE A.7.6 | 46M | 61M | ||
2 | COMMON PATH LIMIT | IN ACCORDANCE WITH NFPA 101 TABLE A.7.6 | 23M | 30M | ||
3 | DEAD-END CORRIDOR | IN ACCORDANCE WITH NFPA 101 TABLE A.7.6 | 6.1M | 15M | ||
4 | ROOM OR SPACES WITH MORE THAN 93 SQM OR WITH AN OCCUPANT LOAD OF MORE THAN 50 PERSONS | MINIMUM TWO (2) ACCESS DOORS | REQUIRED | |||
REQUIRED DOORS ARRANGED TO PROVIDE ACCESS TO SEPARATE EXITS | ||||||
DOORS OPEN INTO THE DIRECTION OF EXIT TRAVEL | ||||||
5 | EVERY ROOM NORMALLY SUBJECT TO STUDENT OCCUPANCY | EXIT ACCESS DOORS LEADS DIRECTLY TO AN EXIT ACCESS CORRIDOR OR EXIT | REQUIRED | |||
6 | DOORS SWINGING INTO EXIT ACCESS CORRIDOR | ACCESS DOORS ARRANGED TO PREVENT INTERFERENCE WITH CORRIDOR TRAVEL | REQUIRED | |||
7 | AISLE | MINIMUM AISLE WIDTH | 760MM | |||
8 | SPACES BETWEEN PARALLEL ROWS OF SEATS SUBJECT TO THE MINIMUM AISLE WIDTH | THE NUMBER OF SEATS THAT INTERVENES BETWEEN ANY SEAT AND AN AISLE DOES NOT EXCEED SIX (6) | NOT REQUIRED | |||
9 | EXIT DISCHARGE | |||||
EXTERIOR DISCHARGE | DIRECT TO BUILDING EXTERNAL | REQUIRED | ||||
THROUGH AREAS ON LEVEL OF EXIT DISCHARGE | MAXIMUM 10M TRAVEL DISTANCE TO BUILDING EXTERNAL | PERMITTED WHEN PROTECTED THROUGHOUT WITH SPRINKLER SYSTEM | ||||
50% OF THE REQUIRED NUMBER OF EXITS AND 50% OF THE REQUIRED EXIT CAPACITY | ||||||
10 | EXTERIOR WAYS OF EXIT | COMPLYING WITH NFPA 101 | PERMITTED | |||
11 | ACCESIBLE MEANS OF EGRESS | EXIT & ACCESS PROVISIONS FOR PEOPLE WITH SEVERE MOBILITY IMPAIRMENT | NOT LESS THAN 2 EXITS REQUIRED | |||
12 | ILLUMINATION OF MEANS OF EGRESS | COMPLYING WITH CHAPTER 7 NFPA 101 | REQUIRED | |||
13 | EMERGENCY LIGHTING | COMPLYING WITH CHAPTER 7 NFPA 101 | ||||
14 | MARKINGS OF MEANS OF EGRESS | COMPLYING WITH CHAPTER 7 NFPA 101 | ||||
F | SPECIAL MEANS OF EGRESS PROVISIONS | |||||
1 | FIREMEN ACCESS PANELS | HABITABLE HEIGHT EXCEEDING 10M | NR | R | ||
2 | WINDOWS FOR RESCUE | ROOMS OR SPACE GREATER THAN 23.2 SQM AND NORMALLY SUBJECT TO STUDENT OCCUPANCY | REQUIRED | |||
BUILDING SPRINKLER PROTECTED THROUGHOUT | NOT REQUIRED | |||||
ROOMS OR SPACE HAS DOOR LEADING DIRECTLY TO AN EXIT OR OUTSIDE THE BUILDING | NOT REQUIRED | |||||
ROOMS LOCATED FOUR OR MORE STORIES | ||||||
4 | LOCKUPS | DOORS & PHYSICAL RESTRAINTS TO FREE EGRESS CAN BE READILY RELEASED BY STAFF WITHIN 2 MINUTES OF ONSET OF FIRE OR ANY EMERGENCY | REQUIRED ON DOORS PROVIDED WITH LOCKUPS | |||
5 | ELEVATORS FOR OCCUPANT CONTROLLED EVACUATION PRIOR TO PHASE 1 EMERGENCY RECALL OPERATIONS | COMPLYING WITH CHAPTER 7 NFPA 101 | NOT PERMITTED |