III |
BUILDING AND SITE ACCESS FOR FIRE FIGHTING & RESCUE |
GENERAL INDUSTRIAL BUILDINGS |
LOW HAZARD |
ORDINARY HAZARD |
A |
SITE ACCESS |
4.0M MINIMUM CLEAR WIDTH & 4.5M MIN. CLEAR HEIGHT |
REQUIRED |
B |
ACCESS ROAD |
4.0M MIN. WIDTH AND 24 TON LOAD CAPACITY |
REQUIRED |
WITHIN A TRAVEL DISTANCE OF 45M FROM EVERY POINT ON PROJECTED PLAN AREA OF ANY BUILDING. |
C |
FIRE ENGINE HARDSTANDING |
LENGTH OR NUMBER BASE ON THE GROSS FLOOR AREA OF THE BUILDING |
REQUIRED |
6M X 15M (MINIMUM), WITH LONGER SIDE PARALLEL TO THE FACADE OF THE BUILDING |
POSITIONED SO THAT THE NEARER EDGE SHALL BE NOT LESS THAN 2M OR NOT MORE THAN 10M FROM THE CENTER POSITION OF THE ACCESS OPENING, MEASURED HORIZONTALLY. |
REQUIRED |
D |
FIRE COMMAND CENTER |
OTHER THAN HIGH-RISE WITH EMERGENCY VOICE COMMUNICATION SYSTEM AND/OR SMOKE CONTROL SYSTEM |
REQUIRED |
9 SQM MINIMUM FLOOR AREA (LEAST DIMENSION 2.5M) |
E |
FIRE LIFT |
COMPLYING WITH ALL FIRE LIFTS REQUIREMENTS |
TO COMPLY WITH REQUIREMENTS WHEN PROVIDED AS REQUIRED |