VII |
FIRE PROTECTION (NR-NOT REQUIRED / R-REQUIRED) |
GENERAL INDUSTRIAL BUILDINGS |
A |
DETECTION ALARM AND COMMUNICATION SYSTEMS |
|
|
1 |
FIRE ALARM SYSTEM |
COMPLYING WITH NFPA 72 |
REQUIRED |
B |
EXTINGUISHING REQUIREMENTS |
|
|
1 |
PORTABLE FIRE EXTINGUISHERS |
TYPE AND RATING IN ACCORDANCE WITH NFPA 10 |
REQUIRED |
2 |
FIRE BLANKETS |
IN KITCHEN OR PANTRY |
REQUIRED |
3 |
STANDPIPE SYSTEM |
COMPLYING WITH NFPA 14 |
REQUIRED |
4 |
FIRE HOSE REELS |
25MM DIAMETER HOSE |
REQUIRED |
5 |
AUTOMATIC SPRINKLER SYSTEM |
|
LOW HAZARD |
ORDINARY |
3 OR MORE STORIES IN HEIGHT |
NR |
R |
FIRE AREA EXCEEDING 1,115 SQM |
NR |
R |
TOTAL AREA OF ALL FLOORS EXCEEDS 2,230 SQM |
NR |
R |
WOODWORKING OPERATIONS EXCEEDING 232 SQM |
REQUIRED |
POWER GENERATION BUILDING |
REQUIRED |
6 |
OTHER EXTINGUISHING SYSTEM |
COMPLIANCE FROM INDIVIDUAL CODES & STANDARDS |
IN LIEAU OF AN AUTOMATIC SUPPRESSION SYSTEM |